Professional Documents
Culture Documents
Fire & Gas Theory
Fire & Gas Theory
After ignition has occurred, and the invisible products ar3e being
released.
When visible smoke is being produced.
When the fire is producing flame and a degree of illumination.
When the temperature in the vicinity of the fire rises rapidly or reaches
a predetermined figure.
iii)
iv)
Types of detectors
1. Line-Type detectors
A device in which detection is continuous along a path.
2. Spot-Type detector
A device whose detecting element is concerned at a particular location.
MODULE 2
MODULE 2
The Theory
These detectors are based on the fact that certain metal-alloys are
normally used-melt at relatively low temperature; the general range
available extends from about 55 oC to 180 o C. As the metal used
predetermines the temperature at which the alarm will sound it will be
chosen after due consideration of the type of risk to be protected and
the normal ambient temperature in the protected area.
(b)
The practice
1) Eutectic metals
Alloys of bismuth, lead, tin and cadmium, that melt rapidly at a predetermined
temperature, can be used as operating elements for heat detection.
The eutectic metal is often used as a solder to secure a spring under tension.
When the element fuses, the spring action closes contracts and initiates an
alarm. Devices using the eutectic metals cannot be restored. Either the device
or its operating element must be replaced following operation.
MODULE 2
MODULE 2
The Theory
Where gas is used as the expanding element in a heat detector,
air is the gas most commonly used; such detectors are sometimes
referred to as pneumatic detectors.
When subjected to heat the air in the chamber expands and
applies pressure to the flexible diaphragm. This gradually
pushes it up until it meets the electrical contact, completes the
circuit and raises the alarm.
By introducing a small compensation vent into the side of the
air chamber a rate-of-rise element is added to the detector. The
compensating vent will allow a certain amount of expanding
air to escape; it will be carefully calibrated so as to compensate
only for expansion caused by the normal and legitimate
increases in the ambient temperature.
MODULE 2
The practice
(i)
MODULE 2
MODULE 2
Temperature
Classification
Ordinary
Temp Rating
Range, Degrees F
135 to 174
Intermediate
High
Extra High
325 to 399
Uncoloured
175 to 249
250 to 324
400 to 499
500 to 575
Colour
Code
White
Blue
Red
Green
Orange
MODULE 2
MODULE 2
10
MODULE 2
11
MODULE 2
12
Sampling Detector
They comprise a series of small bore sampling tubes, which are located in
the fire risk zone. These sampling tubes are connected to a central
monitor unit. The monitor unit continuously samples the atmosphere in
the protected zone by drawing air through an ionization chamber, which
is designed to raise the alarm when the level of combustion products
reaches a predetermined level.
Radiation detectors
A radiation or flame detector responds to the appearance of radiant
energy visible to the human eye or to radiant energy outside the range of
human vision, i.e. infra-red radiation or ultra violet radiation. Radiation
detectors have a quick response capability and they are not dependent on
combustion products actually reaching the detector head. Early warning
will obviously only be achieved if the goods or materials being protected
are readily flammable. The relative amount of smoke likely to be
produced by the goods is another important factor. In a smoky fire infrared detectors may preferable to ultra-violet types because infra-red
radiation can penetrate smoke better, but where goods are likely to
smoulder and produce smoke for a long period before flame appear,
radiation detectors are obviously of little value.
(I)
MODULE 2
13
MODULE 2
14