Professional Documents
Culture Documents
Common Incineration Problems: Contact Us
Common Incineration Problems: Contact Us
Page 1 of 1
2. The equipment supplier didn't design the system correctly or there were fabrication errors.
3. The installation crew omitted some important part of the system.
4. The incinerator safeties were poorly maintained or preventative maintenance was not
performed.
5. Plant production changed, the waste changed, but incinerator was left "as is".
Ultimately all users would like their incinerator system to run like a Swiss watch and need no
maintenance, ever! But routine checks, cleaning and refurbishment will be necessary to avoid
nuisance shutdowns and even safety problems. Spare parts is big business for hardware suppliers and for good reason.
Click on the topics below - maybe one fits your situation. If not, or if you want to contribute, contact
us!
1.
2.
3.
4.
5.
6.
7.
8.
9.
Definitions
Burner Related Problems
Combustion Pulsation and Noise
Waste Handling Problems
Corrosion / Erosion
Thermal Damage
Thermal Expansion Problems
Scrubber Problems
Boiler Problems
http://www.banksengineering.com/common.htm
7/10/2013
DEFINITIONS
Page 1 of 1
DEFINITIONS:
Waste: Usually a byproduct of hydrocarbon processing or chemical manufacture. If a liquid, it may
be mostly water or can range up to waste solvents with fuel qualities. If a vapor, it can range from
lightly contaminated air to near fuel gas. Some vapors are an inert such as nitrogen or CO2 mixed
with oxygen and/or hydrocarbons. Vapor waste compositions often vary according to process plant
operation. Both liquid and vapor wastes can contain acid components (Cl, F, S) and "ash" such as
Na, Fe, etc.
Incinerator: Refractory lined chamber with a fuel burner, air supply, quench medium (for high BTU
wastes), waste injector(s) and optional heat recovery and flue gas scrubbing. An instrumented safety
and control system is used to assure proper addition of fuel, air, wastes and quench plus operation
of the optional hardware.
Chemistry: Waste is heated above its ignition temperature in the presence of fuel and air to provide
for complete combustion. Time is allowed for the combustion reactions to proceed far enough to
satisfy legal emission requirements.
Safety: Avoiding dangerous conditions which may lead to injury to personnel or damage to
equipment.
Performance: Ultimately each incinerator system has to meet the requirements of the air permit
under which it operates. Specified levels of destruction for each waste component must be achieved.
Specified limits on NOx, CO, acid gases, particulates, etc. must not be exceeded. Failures in this
area are mostly caused by mis-specified waste streams or errors in sizing the equipment - fixes may
require major and costly modifications.
Scrubber: Any device intended to remove particulates, acidic gases or odorous compounds from a
gas stream. Usually scrubbers absorb the target material into a liquid stream for later separation or
treatment. Occasionally a dry scrubber is used, where adsorbent particles are used to remove
components (usually acidic gases) from a fouled gas stream.
Boiler: A heat recovery device where hot combustion products transfer heat to water, forming steam
for use elsewhere. Boilers may include Economizers and Superheaters for more complete heat
recovery. Boilers may be "firetube" where the hot gas passes through tubes (water outside) or
"watertube" where the evaporating water is contained within tubes and the hot gases flow outside.
Return to Home or Problems Page. Send us a comment about this topic?
http://www.banksengineering.com/definiti.htm
7/10/2013
BURNER STABILITY:
Page 1 of 2
BURNER STABILITY:
Stable burner operation is critical to good incinerator operation. A few incinerators can operate with zero fuel, but most
benefit from at least a small burner. Where the waste contains almost all of the heating value needed for operation, the
entire waste entry area should be considered part of the "burner"! At best, an unstable burner will cause variations in waste
destruction efficiency or irritating combustion noise. At worst, burner instability can be responsible for repeated nuisance
shutdowns of the incinerator system and damage to expansion joints and other components.
Air Availability: Most often the total air supply is OK, but air and fuel / waste positioning within the burner or furnace is the
problem. Errors in mixing the air and fuel components create localized instability although the stack gas may contain
precisely the amount of excess O2 desired. Combustion noise (pulsation) is generated as the flame enters and then leaves
zones where the air / fuel mixture is in the combustible range.
Too much air: Quench combustion reactions => flame unstable or generates products of incomplete combustion (PIC) like
carbon monoxide and even soot. Excessive fuel usage - if you heat a little air that you don't have to, you are wasting fuel.
Too little air: Combustion reactions cannot go to completion => flame unstable or generates PIC. Stack smokes.
Combustion noise may be present as the flame pulsates.
Source of problem: Air flow control (control logic problem), air blower too small, or bad air placement relative to fuel
placement (burner layout problem)
A well designed burner injects high BTU (high air demand) fluids well inside the main air flow path. Inerts (nitrogen, aqueous
wastes) are added away from the main flame area in order to avoid quenching the flame before it fully develops. Switching
the locations of the fuel and inert streams here would make the burner unworkable.
Waste Flow / Composition Variations: Waste is an undesired byproduct plant production. The flow and composition might
swing as the plants control loops focus on keeping the main product on spec.
Waste flow varies too rapidly: air flow cannot track and air availability is a problem or auxiliary fuel / quench medium
http://www.banksengineering.com/burner.htm
7/10/2013
BURNER STABILITY:
Page 2 of 2
cannot track and furnace temperature varies out of range (possible system shutdown).
Waste composition varies too rapidly: can cause the same problems as rapid waste flow changes.
Source of problem: the control system can't anticipate the shifting combustion requirements so adjustments are often out
of phase.
http://www.banksengineering.com/burner.htm
7/10/2013
Page 1 of 1
http://www.banksengineering.com/combusti.htm
7/10/2013
Fact Sheet
Page 1 of 4
Actually noise in the first category is seldom a problem unless a flame is also involved. Noise
inherent in the system appears to be amplified by the flame energy. A few field reports illustrate this:
Field Report No. 1 "Claus Plant Incinerator"
A new Claus tail gas incinerator was built at a refinery in the Houston area. It included a relatively
long tail gas duct running from the last sulfur condenser down to the incinerator burner. The burner
was natural gas fired and included a centrifugal air blower to overcome the pressure drop across a
water tube waste heat boiler positioned at the incinerator furnace outlet and exhausting to a carbon
steel stack.
This system was designed for future plant expansion, so throughput was only a fraction of design.
Immediately upon startup, the operators heard a very loud, relatively high frequency noise. The noise
disappeared when the burner was fired at its design rate, and of course it went away when the
burner was off.
Attempts to modify the burner fuel gas injection geometry had little effect on the noise, even though
this step often eliminates or at least reduces similar problems.
An acoustics expert was called in. Microphones were installed at several locations throughout the
system but the problem source remained elusive until, with the burner turned off, low level noise at
the problem frequency was detected. This meant that the noise was being triggered somewhere in
the system and the burner was simply amplifying the signal into a container accidentally sized for
resonance.
http://www.banksengineering.com/fact_sheet_noise.htm
7/10/2013
Fact Sheet
Page 2 of 4
Ideas to alter the resonant frequency of the equipment were considered. For instance, shortening or
lengthening the stack would have changed the resonant point and cut the noise amplitude. The fix
finally selected consisted of installing a perforated stainless steel plate across the boiler outlet flange.
The perforations were sized to create as much flue gas pressure drop as the blower and Claus plant
could handle. That fixed the noise problem by interrupting the resonance.
Field Report No. 2 "Chemical Plant Thermal Oxidizer"
At a chemical plant, also near Houston, a new thermal oxidizer system was installed to dispose of
offgas from an acrylonitrile plant. The system was to have a waste heat boiler installed later, so the
horizontal furnace was connected via a long duct to the exhaust stack. A forced draft natural gas
burner was used to bring the furnace up to temperature. Once the refractory was cured out, the
operator switched the vent gas stream away from atmospheric vent and into the burner. Immediately
a very loud, high pitched noise was heard. Apparently the furnace system was sized just right for
resonance and the burner provided the amplification, while the noise was started at the inlet valve.
Fortunately, a simple change to the inlet valve position changed the frequency enough to reduce the
noise to acceptable levels. In this case the change was easy to accomplish and worked "like magic".
Field Report No. 3 "Elevated Flare"
A refinery in California installed a large, steam assist, elevated flare. Steam injection was necessary
for smokeless burning of the waste gases. Upon startup, a very loud, low frequency (2 Hz) noise was
produced. It resulted in complaints of vibrating floors and walls from workers well away from the flare
site and steps were immediately taken to find the cause and eliminate it. With trial and error and a
few lucky guesses, the cause was determined to be the steam jet position in relation to the waste
gas injection passage. By raising the steam jet elevation about 2 inches, the problem noise was
eliminated and smokeless operation maintained.
Field Report No. 4 "North Dakota Hydrogen Vent Incinerator"
A petrochemical plant in North Dakota produced a waste gas rich in hydrogen. It was to be used to
fire a process heater. The heater was equipped with a number of floor mounted burners, each with a
central fuel gas gun mounted inside a refractory throat. Upon startup, a very loud noise was
produced. In this case there were operator complaints, and the amplitude was so great that it was
loosening the nuts holding the furnace platforms and other hardware in place. With nuts falling, the
furnace could not operated while personnel were below. This problem was solved by adding a
central gas passage through the center of each burner gas gun. This changed the flame geometry
enough to "detune" the burners and reduce the noise to acceptable levels.
Field Report No. 5 "Houston Chemical Plant Waste Heat Recovery Plant"
A petrochemical plant near Houston operated a large horizontally fired incinerator mated to a water
tube heat recovery boiler and economizer. The flue gas was ducted to atmosphere through a 100 ft.
stack close coupled to the economizer. The waste gas had very low heating value and was injected,
along with the combustion air, through a series of stainless pipes installed through the furnace
refractory lining. A natural gas burner started the combustion and two waste liquids were sprayed in
between the burner and the waste gas injectors. With increased plant production, a "noise" began to
appear. In this case, the frequency was only 1 or 2 cycles per second, and was detected by rhythmic
swelling of the fabric expansion joints connecting the economizer to the stack. Expansion joint life
was reduced to about 6 months, and the system had to be taken down for fabric replacement (total
shutdown about 3 days each time). Previously, the plant could be run about 2 years between
shutdowns. In this case, modifying the waste distribution across the pipe injectors resulted in enough
amplitude reduction to solve the problem. The low frequency noise was still present, but flexing of
http://www.banksengineering.com/fact_sheet_noise.htm
7/10/2013
Fact Sheet
Page 3 of 4
z
z
z
Rhythmic flame body displacement (flame detection device may lose sight of the flame),
Brief loss of combustion air flow as furnace pressure peaks, briefly reducing air flow (low flow
switch may trip),
"Breathing" of the furnace shell and expansion joints leading to material failure through fatigue.
Structural damage to the furnace if the amplitude is high enough.
Extremely irritated operators and neighbors.
Eliminating combustion pulsation and excessive noise is possible through changes in burner
operation (reduce or increase air flow, change steam flow, etc.), but often some sort of hardware
change is required. One approach involves changing the location or velocity of fuel injection. Another
involves changing the location direction of combustion air flow, steam flow or waste flow. And in
some cases, steps must be taken to change the resonant frequency of the furnace/stack assembly.
These changes are typically accomplished in an experimental manner - change only one thing at a
time, record results and move on till all options have been tried. Sometimes observation of the flame
body will give a clue as to the best approach. There is some hope from acoustic analysis of the
resonating chamber(s) as in Report No. 1, but this is presently very difficult and typically too
expensive to use prior to a problem showing up.
http://www.banksengineering.com/fact_sheet_noise.htm
7/10/2013
Fact Sheet
Page 4 of 4
Combustion noise is inevitable, but excessive noise can always be controlled without resorting to
magic.
Dan Banks, P.E.
Banks Engineering Inc.
Tulsa, OK
www.banksengineering.com
Phone 877-747-2354
http://www.banksengineering.com/fact_sheet_noise.htm
7/10/2013
WASTE HANDLING
Page 1 of 1
WASTE HANDLING: Liquid wastes can normally be run thru tankage to even out flow and composition swings.
Some liquid wastes must be hot in order to flow, so heat tracing and insulation design are critical. Solids in liquid
wastes can deposit on injection equipment, causing plugging or poor distribution inside the burner. Vapor wastes
must flow directly to the incinerator, so variations have to be accommodated quickly by the burner and instrument
system.
Waste Stream Isolation: Many incinerators have to handle multiple waste streams. Mixing several vapor streams
or several liquid streams for movement from the source to the incinerator can save money, but if mixing causes
reactions and deposits, the cost savings are soon forgotten. Prematurely mixing a gaseous waste high in oxygen
with one high in hydrocarbons can create a highly combustible mixture, and should be avoided if possible!
Keeping these streams isolated until injected into the incinerator is always preferable. Where these problems are
not present, it may still make sense to avoid premature mixing, since differing stream characteristics often dictate
specific injection points in the burner or furnace - loss of one of the streams changes the combined waste stream
characteristics and may cause burner stability problems.
Source of problem: Premature mixing of waste streams.
Flame Arrestor Plugging: Waste gases with the potential to be in the combustible range are normally run though
a flame arrestor (or detonation arrestor) just prior to incinerator entry. Some waste gases can be saturated with a
heavy compound such as tar. Cooling in the waste gas duct can create droplets of tar, plugging most types of
flame arrestor. Some wastes contain ash or other particulate matter, creating similar plugging problems. Usually
duct heat tracing, ash filtering or selection of a packed bed or other type of arrestor more resistant to fouling will
solve the problem.
Source of problem: Contaminants within a vapor waste and improper flame arrestor selection.
Flash-back Protection: Sometimes a waste gas stream will pass through the combustible range in the course of
plant operations. The incinerator is an ignition source. Once started, a flame proceeds at specific velocities
through a combustible mixture until it is cooled below ignition temperature or passes into a noncombustible zone.
Flash-back from the incinerator to the source is a common safety hazard. Methods to prevent flash-back are (1)
dilution with air or inert gas, (2) enrichment with fuel gas, (3) maintenance of gas velocity above the flame velocity,
(4) cooling the traveling flame using a commercial flame arrestor or (5) breaking the continuity of the combustible
mixture (typically by bubbling it through a water bath). Flashback can still occur if these measures are applied
improperly.
Source of problem: Waste gas enters the combustible range and proper safety hardware and logic is not
present.
http://www.banksengineering.com/waste.htm
7/10/2013
Page 1 of 8
Flammability:
Overview
Flammability refers to the ability of a mixture of fuel and air to sustain combustion when ignited. Hydrocarbon molecules will
react with oxygen (burn) if heated sufficiently, for instance by a spark or similar ignition source. The required temperature is
different for different compounds and is called the "Ignition Temperature".
The heat released by burning the hydrocarbons in the vicinity of the spark is absorbed by the hydrocarbon/air mixture nearby. If
the nearby mixture picks up enough heat, it will also burn, releasing heat into the adjacent gas and resulting in burning of all of
the surrounding mixture.
If the mixture contains too few hydrocarbon molecules, the released heat will be too little and burning will not progress.
If the mixture contains too few oxygen molecules, only part of the hydrocarbon molecules will be burned and again the heat
released will be insufficient for burning to continue beyond the ignition source.
In laboratory testing, various pure hydrocarbons are mixed with air to form mixtures with different hydrocarbon/air ratios. As
the hydrocarbon fraction is increased, the first point at which sustained burning is observed is noted as the Lower Explosive
Limit (LEL). As the hydrocarbon fraction is increased, eventually the fraction of oxygen is reduced enough that sustained
burning is no longer achieved. This point is the Upper Explosive Limit (UEL). Any hydrocarbon/air mixture between the LEL
and the UEL will burn, while any mixture outside of this range will not burn. Testing with methane, for instance, shows that 5%
(by volume) of methane in air is the LEL. Methanes UEL is 15%. Laboratory values for a few of the tested hydrocarbons is
listed below. Note that several of the compounds actually require no oxygen at all for combustion (UEL = 100), indicating that a
tank of the pure hydrocarbon will burn completely once ignited. The lowest LEL in this group is 1.05% for n-Heptane; if you
mix 1.05% of n-Heptane with 98.95% air, it will burn. This mixture of n-Hexane, however, would not burn:
Hydrocarbon
Formula
Ignition Temperature, oF
Methane
CH4
5.0
15.0
1202
Ethane
C2H6
3.0
12.4
959
Propane
C3H8
2.1
9.5
871
n-Butane
C4H10
1.8
8.4
896
n-Pentane
C5H12
1.4
7.8
878
n-Hexane
C6H14
1.2
7.4
527
n-Heptane
C7H16
1.05
6.7
491
Dimethyl ether
C2H6O
3.4
27
662
Hydrogen
H2
4.0
75
1062
Ethylene oxide
C2H4O
3.6
100
804
Acetylene
C2H2
2.5
100
581
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 2 of 8
Effect of temperature
Almost all published flammability values are measured using hydrocarbon/air mixtures at room temperature. If the mixture temperature is
higher, the LEL is reduced. Reference #3 reports that increasing the temperature 100oC = 180oF decreases the LEL value about 8%. The
equation to use is
Lt = 1.02 x L x (1-7.75 x10-4 x T), where L is the laboratory value of LEL, T is the elevated temperature and Lt is the LEL at T. The UEL value
increases with increase in mixture temperature, also by about 8% with 180oF increase in T.
Effect of pressure
Increasing the mixture pressure above atmospheric affects the LEL very little. The UEL, however, increases greatly. One source reports that for
several saturated hydrocarbons, the UEL increases in proportion to the logarithm of the pressure. Another source reports an opposite effect for
some hydrocarbons and warns that pressure effects vary according to the hydrocarbon considered.
Effect of inerts
Inert gases play no part in combustion reactions, but absorb heat when present in a hydrocarbon/air mixture. For that reason, adding inerts to a
mixture tends to reduce the spread between LEL and UEL until finally the mixture is no longer flammable. Reference 2 provides the graph
below showing specific effects for hydrogen, carbon monoxide and methane when inerted with nitrogen and carbon monoxide. For example,
methane in air with no inerts (Ratio = 0) has LEL = 5 and UEL = 15. But if 3.5 mols of CO2 are added to a mixture containing 1 mol of CH4
(in air), the mixture is no longer flammable.
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 3 of 8
Flammability of hydrocarbon mixtures The flammability limits of a mixture of various hydrocarbons can be calculated using Le Chateliers law, which states that a mixture at the
lower limit of flammability mixed with other mixtures which are also at the lower limits of flammability will yield a resulting mixture at the
lower limit of flammability. For example, to calculate the LEL of a hydrocarbon mixture which is 70% CH4, 20% C2H6 and 10% C3H8,
LEL = 100% / (70/5.0 + 20/3.0 + 10/2.1) = 3.9%
This mixture has a LEL of 3.9% hydrocarbons in air. The mixture UEL is calculated the same way.
Ignition Sources:
Hot refractory
If the refractory lining a burner or furnace is hot enough to bring the hydrocarbon/air mixture to the autoignition temperature, rapid combustion
will start. Heat transfer from the hot surface depends on gas velocity and turbulence, explaining why "swirl" type burners often seem more
stable than more linear types.
Flame
Flames from pilot burners are the typical means of initiating combustion of a hydrocarbon/air mixture. Nozzle mix burners (where the fuel
mixes with the combustion air within the furnace) have zones that are too lean or too rich for combustion, so the pilot flame must be positioned
to heat a volume of well mixed gas. Large pilot flames can overcome poor positioning of the pilot tip.
Sparks
Sparks are used to ignite pilot burners and also main burners in some cases. Occasionally small sparks (static electricity) are capable of
initiating combustion, but the extra energy in a large spark helps insure lightoff. Undesired sparks, such as those resulting from debris moving
through steel ducting or fans, can initiate combustion and require careful design to avoid.
Flashback Prevention Methods:
Enrichment
By adding natural gas or other hydrocarbon, the mixture can be brought above the UEL, preventing combustion.
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 4 of 8
Dilution
By adding inerts such as N2 or CO2, the mixture can be brought to a nonflammable state.
Velocity
Flames progress at a defined rate through a flammable mixture. Considerable lab testing with non-turbulent mixtures has been done data for
a few gases is listed below from Reference 7. For instance, the "maximum flame velocity" of a methane/air mixture is 1.48 ft/sec under lab
conditions. If this mixture flows through a pipe at 1.5 ft/sec, any flame will be unable to propagate against the flow. This fact is used in
designing flare tips, burner nozzle and some flame arrestors by designing for gas velocity above the flame velocity, the flame can be
prevented from moving upstream from the point of ignition. NOTE: as a flame front moves through a vessel or pipe, the flame velocity
increases. With long enough piping the velocity can increase to detonation levels, which are supersonic.
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 5 of 8
Many methods to stop flashbacks have been devised. "Active" methods require maintenance of certain parameters, such as liquid level or gas
velocity. "Passive" methods require only routine inspection and typically have no moving parts or instrument requirements.
Venturi type flame Arrestors (active)
Venturi flame arrestors simply create a restriction in the hydrocarbon/air mixture delivery pipe so that the gas velocity is faster than the flame
speed, preventing progression of a flashback upstream. Flashback in the direction of flow can still happen. Even a partly closed valve can
create a high velocity for flashback prevention, but a venturi shape creates much lower pressure drop. If gas flow stops, the venturi is no longer
effective, so methods to measure flow and add makeup gas (nitrogen, for instance) are often included. Note: initially flame velocity is limited
to the values in the literature, but extended pipe runs and fittings act to increase the velocity, eventually reaching detonation velocities. A
venturi arrestor must be located close to the point of ignition to avoid problems.
Inline flame arrestors (passive)
Mechanical flame arrestors are filled with metal or ceramic, which absorbs heat from a flashback, quenching it to a temperature below what is
needed for ignition. This stops the flame. With a low enough hydrocarbon/air mixture flow rate, if a flame travels to the face of the arrestor, it
can become stable at that point. Heating of the arrestor body and internals results. Once the arrestor temperatures increase enough, ignition
temperature can be reached on the upstream side of the arrestor and the flashback can proceed. For this reason, a temperature switch is often
installed on the flame side of each arrestor (adding an "active" element). If an elevated temperature is detected, an alarm sounds and steps can
be taken to stop flow completely. An Enardo flame arrestor is shown below (www.enardo.com).
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 6 of 8
arrestor must stop the flash back without damage to the arrestor itself, so it can be used repeatedly if necessary. Detonation arrestors can be
certified for various hydrocarbons, which have been divided into groups according to how difficult flash backs with them are to stop. A list
from Protectoseal (www.protectoseal.com) derived from National Electric Code (NEC) Article 500 is shown below:
- acetylene
Group B - butadiene, ethylene oxide, hydrogen, manufactured gases containing more than 30% hydrogen by volume and propylene oxide
Group C - acetaldehyde, cyclopropane, diethyl ether, ethylene, and unsymmetrical dimethyl hydrazine
Group D acetone, acrylonitrile, ammonia, benzene, butane, butyl alcohol, secondary butyl alcohol, n-butyl acetate, isobutyl acetate, ethane, ethyl alcohol, ethyl acetate,
ethylene dichloride, gasoline, heptanes, hexanes, isoprene, methane (natural gas), methanol, isobutyl alcohol, methyl isobutyl ketone, isobutyl alcohol, tertiary butyl alcohol,
petroleum naphtha, octanes, pentanes, amyl alcohol, propane, propyl alcohol, isopropyl alcohol, propylene, styrene, toluene, vinyl acetate, vinyl chloride, xylenes.
Note that a detonation arrestor certified for Group B hydrocarbons is also suitable for Group C and D hydrocarbons. There is some evidence
that methanol belongs in Group C or B, but recertification is not complete.
Currently the European Union is defining separate standards for testing and certification of detonation arrestors acceptable in that jurisdiction.
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 7 of 8
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
Page 8 of 8
References:
1. Perrys Chemical Engineers Handbook, 4th Edition
2. Bureau of Mines Bulletin 503 "Limits of Flammability of Gases and Vapors"
3. Flammability Properties of Hydrocarbon Fuels, Wilbur A Affens, Journal of Chemical and Engineering Data, Vol. 11, No. 2, April 1966.
4. Industrial Explosion Prevention and Protection
5. National Fire Protection Association, Standard on Explosion Prevention Systems, NFPA 69, Boston, 1973.
6. Flammability Calculations for Gas Mixtures, W.M. Heffington and Gaines, W.R., Oil & Gas Journal Nov. 16, 1981.
7. North American Combustion Handbook, Second Edition.
http://www.banksengineering.com/about_flame_arrestors_and_detona.htm
7/10/2013
CORROSION
Page 1 of 2
CORROSION / EROSION:
This problem is common when wastes being combusted contain acidic components or when burners / furnaces are designed
with swirling flow (for high intensity operation.)
Acid Dew Point: Waste containing acidic components form combustion products which are corrosive when combined with
water. Methyl Chloride contains chlorine, which forms HCl. When cooled to 120 - 150oF, the water vapor / HCl mixture in the flue
gas condenses. Corrosion of refractory or vessel shell material results. Sulfur compounds burn to form SO2 and SO3 (usually 3
to 10% ends up as SO3). The SO3 combines with water vapor when flue gas cools to the dew point temperature - often between
200 and 400o F, condensing to form H2SO4. Dewpoint problems often occur at the furnace shell when the refractory / rainshield
system allow a low shell temperature.
Refractory linings are relatively porous. Flue gas components penetrate to the steel shell. If the shell temperature is below the
acid dewpoint of the gas, condensation will occur.
Other problem areas are any heat recovery system (air preheater) or particle removal system (baghouse) where large surface
areas and reduced flue gas temperature are required. Adding heat tracing and/or external insulation may prevent the
condensation.
Source of problem: Acidic flue gas is inadvertently cooled below dewpoint temperature or the materials of construction were not
properly selected for the resulting acid contact.
http://www.banksengineering.com/corrosio.htm
7/10/2013
CORROSION
Page 2 of 2
Thermal Shock: Rapid temperature changes can cause localized stresses in refractory materials as the areas more easily
heated or cooled expand or contract faster than the rest of the material. The resulting stresses overcome the molecular bonds
holding the material together and pieces "spall" off. Commonly happens when a furnace is started or shutdown too quickly (see
refractory guidelines in this website). Thermal shock can also be caused by spraying liquid water directly on hot refractory usually caused by poor atomization of aqueous wastes or water quench streams. Corrosion or heat damage to water spray gun
tips is a common cause.
Source of problem: Heating or cooling refractory too fast relative to its strength.
Particulate "Scrubbing": Any material can be eroded by a harder material. If ash or refractory particles strike refractory or
vessel shell material, some "sanding" can take place. Excessive contact can remove enough of the base material to cause
equipment failure. This is most common where waste gas with entrained particulate enters a furnace or where burner / furnace
swirl is maintained using an exit choke ring.
Source of problem: Construction of the equipment of materials which are not sufficiently erosion resistant, given the waste
composition. Alternately, equipment design which traps particles and "recycles" them across a refractory surface.
http://www.banksengineering.com/corrosio.htm
7/10/2013
THERMAL DAMAGE:
Page 1 of 2
THERMAL DAMAGE: The environment near the incinerator burner flame can easily reach 3000o F or
higher. Loss of temperature control or selection of materials with poor high temperature properties
account for most thermal damage.
Metal Selection: Since incinerators operate at high temperatures, carbon steel can't be used in certain
areas. Burner parts are normally constructed of 304, 316 or 310 stainless steel in order to handle
normal flame temperatures. Operation with corrosive wastes may require use of Inconel, Hastelloy or
other specialty metal for both temperature and chemical resistance. The degree of air cooling and
radiation affect metal selection. Incinerating acid wastes usually requires flue gas scrubbing. A
scrubber circulating 15% HCl at 200o F may require Zirconium or nonmetallic construction - even
Hastelloy may prove inadequate at an acid temperature above 150o F. Trial-and-error or past
experience with similar waste may be required for a long lasting design.
Source of problem: Wrong metal selected for the waste or combustion products being handled.
Refractory Selection: An operating temperature above the service limit for a particular refractory can
weaken or melt the refractory. Operation under reducing conditions (starved air) in the furnace reduces
the service limit of most refractories by several hundred degrees (use 400oF as a rule of thumb).
Reducing operation can cause severe shrinkage in phosphate bonded refractories (causing large cracks
in castable refractory or collapse of large sections of brick linings). Waste containing certain ashes,
particularly sodium compounds, can create corrosive deposits which dissolve certain refractory
constituents, thinning the lining in a matter of months.
Source of problem: Improper refractory selection or placement.
Radiation / Convection: Waste gases must be transported to the incinerator and then injected into the
burner or furnace at the proper location and velocity for stable operation. Intermittent flow may allow hot
flue gases to circulate back into the waste delivery hardware, overheating carbon steel or nonmetallic
materials. Maintaining minimum flow or using a different material of construction can solve the problem.
Hot refractory radiates heat, and a straight view line into an exterior waste gas plenum or duct can allow
localized overheating some distance from the heat source. A change of sight line or use of high
temperature materials can be a solution.
Source of problem: Improper configuration, flow control or materials of construction.
http://www.banksengineering.com/rmal.htm
7/10/2013
THERMAL DAMAGE:
http://www.banksengineering.com/rmal.htm
Page 2 of 2
7/10/2013
THERMAL EXPANSION
Page 1 of 2
THERMAL EXPANSION: Of necessity parts of any incinerator system are hot while other parts may
be near ambient temperature. This temperature differential causes many problems.
Refractory Lining - Expansion Joints: A refractory lined metal vessel is constructed of several
layers - steel plus one or more layers of brick or hard castable refractory. During operation the layer
closest to the combustion area is hotter than the outer layer. Expansion differences require that soft
joints be built into the refractory layer to avoid pressure stresses, crushing and loss of refractory
material. Refractory linings constructed of ceramic fiber blanket or board don't usually have these
problems, but might have others!
Source of problem: Poorly designed or installed refractory lining.
Steel Shell - Expansion Joints: Metal vessel shells expand when hot. Incinerator shells are often
designed for operation as high as 400o F to guard against dewpoint problems. A furnace or duct
anchored at both ends can exert tremendous stresses when heated, causing deformation unless a
bellows or other expansion joint is included. A cold waste gas plenum or relatively cool boiler shell
expands less than the hot furnace shell it may be welded to, causing deformation or cracked welds.
A hot flue gas tubesheet may expand more than the associated tubes or shell in a waste gas
preheater, causing cracking at the welds.
Source of problem: Inadequate provision for unequal expansion.
http://www.banksengineering.com/rmalexp.htm
7/10/2013
THERMAL EXPANSION
Page 2 of 2
Stacks: Incinerator exhaust stacks expand when heated. Stack length can increase substantially,
depending on the shell temperature, which may range above 400o F. A stack supported by guy wires
can exert enough force to deform or break the wires unless provision is made when the guys are
tensioned during installation. A freestanding stack subject to rain or winter weather will experience
uneven cooling - result: "bowing" of the stack as one side becomes cooler than the other. External
insulation or a standoff "rainshield" with air gap will protect from uneven cooling.
Source of problem: Improper stack design.
http://www.banksengineering.com/rmalexp.htm
7/10/2013
About Refractory
Page 1 of 1
About Refractory:
Refractory Property Definitions from Harbison Walker
A 1953 Refractory Philosophy from A.P. Green
Refractory Selection Comments from A.P. Green
Color vs. Refractory Temperature Chart (General Refractories)
http://www.banksengineering.com/about_refractory.htm
7/10/2013
TYPE OF REFRACTORY
By "type of refractory" we mean the major classifications of refractories - such as silica, fire-clay, high-alumina, magnesite, chrome, etc. Chemical
characteristics of the furnace process usually determine the type of refractory required, although this is not universally true. We have the familiar and
greatly overworked example of silica brick, the most acid of refractories, being successfully used in the roofs of basic open hearth steel furnaces. In this
case the physical properties of the brick, particularly load bearing strength, are more important than the chemical characteristics. On the other hand,
susceptibility to spalling prevents the successful use of silica brick in the standpoint of slag resistance. Numerous examples could be given illustrating
the fact that for successful refractory practice the physical and chemical properties of the refractory must be compatible with the furnace operation and
nature of the process.
In order to judge the type of refractory material most likely to give satisfactory service in a certain furnace, one must have a knowledge of the limitations
as well as the strong points of the principal types of refractories. Very often it is desirable to use different types of refractories in various parts of the
same furnace to obtain uniformly good or balanced refractory service.
General statements, such as the above, are of little help to the person trying to explain why a refractory lining failed to give satisfactory service. The
following brief discussions of the outstanding characteristics of the various types of refractories is an attempt to be more specific.
Page 1 of 3
In addition to the properties of refractoriness and resistance to spalling, slagging, and load, mentioned above, there are other properties of fire-clay brick
which vary widely between different brands but which are often the controlling factor in determining their selection for a particular application. Some of
these properties are:
1.
2.
3.
4.
5.
OPERATING PRACTICE
"Our operating practice has not been changed in years."
"Your brick are just not as good as they used to be.",
These are statements frequently heard during the investigation of cases of premature failure of refractories, That they are entirely honest and sincere
expressions of opinion, there can be no doubt. The point that is sometimes overlooked, however, is that there can be unintentional changes in furnace
conditions long enough in duration to destroy a refractory lining but not long enough to be considered as a change in practice. We refer to such things
as a burner getting out of adjustment so that the furnace atmosphere becomes highly reducing for a short period of time; possibly the operating
temperature of the furnace may become abnormally high and damage the gridwork before it is corrected; or perhaps the chemical composition of raw
material charge or the fuel may have changed although purchased from the same sources.
Such variations in practice are usually extremely difficult to discover because they leave no record except for their effect on the lining. Another
complicating factor is that the failure of the refractory may not become apparent until weeks or even months after the actual damage was done.
Page 2 of 3
Therefore, in investigating cases of refractory failure, it is advisable not to jump to apparently obvious conclusions. It is much better to obtain all the
information possible and then, by a process of elimination strike out all the factors that are reasonably certain to have had thorough examination before
the field can be narrowed still further. In this way it is almost always possible to arrive at a conclusion as to which factor is the one most likely to have
caused the trouble. If you feel there are too many "weasel words" in that statement, the investigation of a few cases of refractory failure will go far toward
changing your mind
QUALITY OF REFRACTORY
All too frequently, from the refractory manufacturer's standpoint that is, it happens that by our process of elimination we find the finger of guilt pointing
directly at the refractory material itself. When this happens perhaps we should be relieved (although we rarely are) because it is the easiest to correct of
all causes of failure. It does not involve alterations in furnace design, modifications in the process to take care of raw material variations, better
instrumentation for closer burner control, or the selection of a different type of refractory. All that is required is the replacement of the lining with the same
brand of brick. It is almost certain that this replacement lining will be up to standard, normal quality and no further difficulty will be encountered
In any mass produced material, such as refractories, there are unavoidable variations in properties. This Is particularly true when the finished product is
made directly from raw materials without intermediate refining or beneficiation. It is the constant endeavor of the refractories industry to reduce the range
of these variations. The testing of raw materials, even before mining; the selection and blending of clays; and the inspection testing at all stages of the
manufacturing process contribute to this end, Finally, the inspection of the finished product before shipment is tremendously important to insure the
consumer of uniform and consistent quality.
WORKMANSHIP
It is easy to blame the brickmasons for every refractory failure because by the time failure occurs the evidence is pretty weII destroyed. Good brickwork
is extremely Important but we have tried to make the poi that there are other factors Involved, probably of more frequent occurrence than either poor
brickmasonry or brick that are not up to standard quality. Perhaps we should make it clear that we do not include the proper size and location of
expansion joints, the rise of an arch, or the thickness of a wall as properly coming under the head of masonry workmanship. These should be taken care
of in the furnace design. In practice we realize that many of these design details are left to the brickmason doing the work, and in most cases this is the
best. way to handle it. There are instances, however, of brickmasons being called on to do furnace work that have had no experience except in the
building trade. This is not likely to happen in large companies employing their own masons, but smaller companies will be well advised to keep this point
in mind and assure themselves that the person in charge of the masons understands high temperature furnace work.
At the beginning of this discussion we listed the five most important factors governing refractory service:
1.
2.
3.
4.
5.
Furnace Design
Type of Refractory
Operating Practice
Quality of Refractory
Workmanship
Arrange them in the order to suit the conditions existing in any particular furnace, and we believe they will help you analyze any refractory troubles.
Page 3 of 3
Page 1 of 1
http://www.banksengineering.com/Refrac_Temp_vs_Color_Chart.jpg
7/10/2013
SCRUBBER PROBLEMS:
Page 1 of 2
SCRUBBER PROBLEMS: Most scrubbers for incinerators handling vapor or liquid wastes are of
packed bed design. Variations include spray towers, trayed towers and venturi scrubbers. Acid
gases are usually the target of scrubber operation. Water chemistry is usually simple, but there are
always surprises.
Scale Deposition: Definite solubility limits exist for all minerals in water. The limits are composition
and temperature dependent. Scrubbers remove acidic components from incinerator exhaust gas
using absorption in water, and a neutralizing chemical such as NaOH or calcium carbonate are used
to convert the acid to its salt (NaCl, Na2SO4, etc.). These salts, combined with whatever minerals
(hardness) came with the fresh water feed stream, affect the scaling potential of the circulating
solution. Once the solubility limit is exceeded, the salts begin coming out of solution on any available
surfaces, such as the packing or other scrubber internals, eventually blocking flow. Deposition can
be avoided by keeping a low level of dissolved salts in the scrubber liquid (increase liquid blowdown
rate, use only caustic for neutralization or replace hard scrubber makeup water with deionized
water).
Source of problem: Operating with excessive dissolved solids.
Hypochlorite: Sodium hypochlorite (NaOCl) is a product of neutralizing Cl2 with NaOH. The
reaction is 2NaOH + Cl2 ==> NaCl + NaOCl + H2O. NaOCl attacks glass, so improperly designed
FRP shell construction or FRP circulating pipes can be ruined as the glass fibers are consumed. In
addition, if the scrubber blowdown liquid is later acidified (as in a waste water treatment plant) the
NaOCl breaks down, releasing chlorine gas!
Source of problem: Poor FRP fabrication; improper waste water treatment.
Thermal Damage: Most incinerator flue gas scrubbers are constructed of the least expensive acid
proof materials available. These are usually FRP, polypropylene or similar and are sensitive to high
temperatures. Prior to scrubbing, the hot flue gas must be cooled. Safety items include high
temperature switches in the quenched gas duct, quench liquid low-flow switches, etc. Should these
safeties be bypassed, a quench system failure (like a damaged pump or water spray tip) can result in
burned or melted scrubber internals.
Source of problem: Inadequate maintenance of flue gas quench system.
Salt Particles / SO3 aerosols: Scrubbers designed to remove acid gases typically are not very
good at removing small particles. Organic liquid wastes containing salts are fed directly to the flame
zone of an incinerator burner in order to achieve stable combustion. The high temperature in this
area can vaporize the salt compounds. When the salt vapor cools to furnace temperature it
http://www.banksengineering.com/scrubber.htm
7/10/2013
SCRUBBER PROBLEMS:
Page 2 of 2
condenses to droplets, which further cool in the gas quench section. Result: very small salt particles.
Similar particle size can be seen when burning any waste containing sulfur. The SO3 from the
furnace forms tiny droplets of H2SO4 when quenched with water prior to scrubbing. This "aerosol"
acts like a fine particulate and passes through the acid gas scrubber. A high energy scrubber,
electrostatic precipitator, or filter must be used in these cases.
Source of problem: Waste combustion forms small particles; additional equipment must be
specified.
Pump Cavitation: Most flue gas scrubbers recirculate the scrubbing liquid in order to reduce the
rate of blowdown to water treatment. Circulating pump cavitation can sharply reduce the rate of
scrubbing liquid available and damage the pump.
Source of problem: Incorrect pump specification, faulty pump suction piping design, poor scrubber
sump design or foreign matter clogging the pump suction.
Channeling and flooding: Incinerator flue gas scrubbers often incorporate beds of random packing.
If the scrubbing liquid is not well distributed across the bed, the incoming gas can flow preferentially
up one side of the scrubber, reducing acid gas removal efficiency. If gas flow is too high the
downward flow of liquid can be slowed, flooding parts of the bed, increasing gas pressure drop and
reducing scrubbing efficiency.
Source of problem: Improper scrubber design or possible fouling of the scrubber packing.
http://www.banksengineering.com/scrubber.htm
7/10/2013
BOILER PROBLEMS:
Page 1 of 1
Boiler Problems:
Since incinerators are usually installed only to satisfy emission requirements, heat recovery boilers sometimes offer the only positive
payback for the project. Designed correctly, they are one of the most trouble free components in any system. But:
Steam Blanketing: Firetube boilers are most often used for incinerator heat recovery for economic reasons. Carbon steel boiler
tubes are commonly used, and the tube metal temperatures are kept sufficiently low by the very rapid rate of heat removal as water
flashes to steam on the outer surface of the metal. As steam bubbles form they float upward away from the tube surface, allowing
fresh water to reach the tube. Excessive steam production in one area can "blanket" the area with steam, impeding water entry and
allowing tube metal to approach flue gas temperature, damaging the tube. A ceramic "ferrule" sleeve at the entrance to each tube
will prevent steam blanketing in this area of high gas velocity. Installation of ferrules to eliminate steam blanketing is possible, as long
as gas side pressure drop does not become excessive.
Source of problem: Improper boiler tube layout or construction.
Solids Fouling:
Some ash components in waste streams can have relatively low melting points. Should a molten salt droplet contact a cool boiler
tube, the salt will solidify. The effect is similar to painting the tube, and the accumulation of salt cuts boiler efficiency. To avoid this,
the flue gas should be cooled enough to solidify the salt droplets prior to boiler entry and soot blowers should be installed for removal
of the solid salt particles. Watertube boilers with unfinned (bare) tubes in the entry zone are preferred in this service, even though
the first cost of a firetube boiler might be less.
Source of problem: Improper system design.
For more about Boilers, click here.
http://www.banksengineering.com/boiler.htm
7/10/2013