3TI Comments & INV Response

KAP2-C2 Project (Najran&Aseer)


TRANSMITTAL n. K2C-36A-0401-IV-DS-TR-0003
Date: 23/04/2015
DOCUMENT n.
K2C-36A-0401-IV-DS-TR-003

Item
No.

3TI Comments

ETABS model
Into the Slab property Data the waffle slab HEB45
equivalent thickness is 210mm, but to be verified the
equivalent thickness has to be at least 240mm.

INV Response

The slab weight = two ribs/ 1.5m {2x(0.15X0.35)X25/1.5


+0.10X25 slab +1.0 bricks}= 5.25 KN/m2
slab Th = 5.25/25 = 0.21m

Project information has to be completed.

SAFE model
Into the Slab property Data the waffle slab HEB45
equivalent thickness is 360mm. Please use the correct
thickness for both the models.

Safe Model slab Thick is Due to Equivalent Inertia to


be modeled and distribute moments on slab correctly
in Safe,we need not that in ETABS to check
Vl Elements only

The loads on the floorings in the SAFE model and in the


It is already done, if you have comments on SAFE or
ETABS model, are not equal. Please use the correct loads ETABS highlight it and send capture screen from models
for both the models.
For the corridors, halls, stairs and assembly areas must
be used 5,00 kN/ sq m

The loads regarding the water tanks on the roof of the


building are not inserted neither into SAFE model nor into
ETABS model.

Into the Structural Report please avoid to mention the


design package received and then corrected. Use only the
final one.

Actually we checked the Architectural & Plumbing


disciplines and they stated that no Tanks in this Building

Noted and will be done