sts 35128 Gonerator Set 66WO00001-UP(SEBPZ772.- 8) -Documertacion CATERPILLAR’ < Producto: GENERATOR SET Modelo: 35128 GENERATOR SET 6GW Service Information System Configuracién: 35128 Generator Set 6GWO0001-UP Localizacién y Solucién de Problemas Electronic Modular Control Panel I+ (EMCP I+) Nimero de medio -RENR2484-06 AL Fault Code SMCS - 4490-035 Fecha de publicacién -01/04/2009 Fecha de actualizacién -01/04/2009 101367572 Table 1 AL Fault Code Troubleshooting AL Description Fault Code Troubleshooting ALI | High Water Temperature Alam Coolant temperature increases to within 6°C (11°F) of setpoint POIs. See the Troubleshooting, "Troubleshooting Dedicated Shutdown Indicators", AL2_ | Low Engine Coolant ‘Temperature Alarm Coolant temperature decreases to setpoint PO16. See the Troubleshooting, "Troubleshooting Dedicated Shutdown Indicators". AL3__ | Low Engine Oil Pressure Alarm Oilpressure drops to within 34 kPa (5 or PO14 setpoint See the Troubleshooting, "Troubleshooting Dedi Indicators". AL4_ | Fault Detected By Engine 2CM The engine ECM detects an hpesiss cat comsiewebiesvebtechdoctechdoc_ grin page jep?rturs Refer to the appropriate engine troubleshooting service manual sts 35128 Gonerator Set 66WO00001-UP(SEBPZ772.- $6) -Documeetacion alarm faut or a shutdown fant. ALS | Low Engine Coolant Level | Check level of engine coolant, The level of engine coolant must be Fault above the probe of the sensor. Check for CID 111 faults. Perform the Coolant level drops below |} electrical connector inspection test. Refér to the Testing and Adjusting, the probe of the coolant | "Electrical Connector - Inspect". Joss sensor. AL6_ | High Engine Oil Temp Fault | Check level of engine coolant, The level of engine coolant must be Oil temperature increases _ |] above the probe of sensor. Check fan bett, ete. Check P026 setpoint. to within 6°C (11°F) of setpoint P026. ALT | Generator Overvotage —_| Refer to the service manual for the voltage regulator that is being used. Fault Check P101 through P106 setpoints, Line to line voltages rises above the P102 or PLOS setpoints. AL8 | Generator Undervottage || Refer to the service manual for the voltage regulator that is being used. Fault Check P107 through P112 setpoints, Refer to the engine service Line to line voltage drops |] manual for the cause of low engine speed. If engine speed is reduced below the P108 or the and the engine control switch (ECS) is NOT in STOP, the GSC+ will P11 setpoints issue this fault AL9 | Generator Overfiequency || See the Troubleshooting, "Indicator For Engine Overspeed”. Check Fault setpoints P113 through P18, Frequency rises above the P114 or P117 setpoints AL10 | Generator Underffequency |) Refer to the engine service manual for a cause of low engine speed. If Fault engine speed is reduced and the ECS is NOT in STOP, the GSC+ will Frequency drops below the |} issue this fault. Check setpoints P119 through P124. P120 or P123 setpoints AL11 | Generator Reverse Power || Refer to the engine service manual for a cause of lost engine power. Fault Check setpoints P125 through P127. Reverse power rises above the P126 setpoint. AL12 | Generator Phase Check for a cause of the overcurrent. Overcurrent Fault Check setpoint P029 and setpoints P128 through P135, Phase current rises above the P129 or P134 setpoints. pers s cat comsiswebissvebtechdoctechdoc._ prin page jep?reurn=siswebissvehimedasearchinediahnadecefltaresel jspicalledpage=Isswmbss, 28 sts 35128 Gonerator Set 66WO0001-UP(SEBPZ772- 8) - Documeetacion AL13 | Generator Total Check for a cause of the overcurrent. Check setpoint P029 and Overcurrent Fault setpoints P128 through P137. Total current rises above the P131 or P136 setpoints. ALI4 || Phase A No Voltage Input || Check for an open circuit on the wire that is connected to the GSC+ Fault connector contact 10. Check for a short on the wire that is connected Phase A voltage not being | to the GSC+ connector contact 10. See the Testing And Adjusting, received at GSC* input, |] "Schematics and Wiring Diagrams", ALIS | GSC+ Configuration Error | Check setpoints P09 and PO33. Setpoint PO09 represents the Frequency of generator || number of ring gear teeth, Setpoint PO33 represents the number of output voltage does not | generator poles. Correct the setpoint value, ifnecessary. mateh engine speed. Additional AL Fault Codes (for GSC+P) ALIG6 | Incorrect Phase Seque! Check for the cause of the phase sequence mismatch. Check wiring to ‘The generator and the bus | the bus transformer box (BTB +) and the AC transformer box (ATB have a phase mismatch. | +), ALI7 | Improper generator or bus || 1. The generator voltage and the bus voltage must be above 10% of voltage the nameplate voltage in PO28 when setpoint PO20 is set to 700. The generator voltage or |] Generator voltage and bus voltage must be above 50% of the the bus voltage are either _ |] nameplate voltage in PO28 when setpoint PO20 is set to any other too low or the vollages do value than 700. not match, 2. Check Setpoints P303 and P304 in order to determine whether the generator voltage and the bus voltage match within the tolerance that is specified. ALI8 | Synchronizer Time-Out || Check for cause of synchronization time-out, Ensure that the engine is ‘The GSC+P is unable to | responding properly to the GSC+P Speed Adjust 1 Output signal complete automatic Check for wiring errors. Check setpoints P313 and P314 for proper synchronization or dead bus |] values. Increase the values, ifnecessary. paralleling within the time allowed in P314. pers s cat comsiswebiesvebitechdoctochdoc._ prin page jep?reurn=siswebiesveimedasearchinediahnadecnfltaresetjspcalledpage=Isswmbss, 3 sts 35128 Gonerator Set 66WO00001-UP(SEBPZ772.- 8) -Documertacion Illustration 1 20044; Upper Display With AL Fault Code AL3 Showing, AL Fault Codes are shown as "ALI" through "ALIS" on the upper display. The fault codes include specific engine fault conditions. An example of a specific engine fault condition is the low engine oil pressure alarm. An example of a protective relaying fiction is the underffequency fault. AL fault codes depend on certain setpoints. For more information on setpoints, see the Systems Operation, "Service Mode" AL fault codes are not diagnosed by the GSC+. These codes are not stored in the fault log. Many of the AL fault codes are programmabk: as fault alarm or as a fault shutdown, The AL fault codes are accompanied by either the fault alarm indicator or the fault shutdown indicator on the GSC+ in order to show the severity of the fault Copyright 1993 - 2013 Caterpillar Inc. Fe ota 4:14:17 GMT-0: ora estandar de Argentina) fonsucht iaas— atti cate May 31 2013 14:14:17 GMT-0300 (Hora estandar de Argentina) Red privada pare licenciados del SIs. hipesiss cat comsisnebiesvebtechdoctechdoc_ grin page jep?returs

You might also like