ees
d(C]
OY Cea ure ems a LCs
Currents produced from 2,000 MW power plants require protective solutions ensuring fast and effective
power plant protection that guarantees the connection from the generator terminals to the grid.
With 4o years of field experience and 200 references in nuclear power plants in 20
countries, Alstom Grid offers you a complete and integrated solution: the PKG
Generator Circuit Breaker.
‘The PKG offers flexible operation and efficent protection for all types of power
plants up to 2,000 MWY, ensuring switching security for the connection between
the plant and the transformers.
Proven technology - extreme performance
Te interrupt an electric arc, the PKG air blast generator circuit breakers use the proven
technology of compressed air, provided by an external compression station. In order to
withstand the very igh rated curren, added fans, radiators an a cooling turbine placed on
the top ofthe pole cool the contacts
Rigorous tests in the factory, test laboratories and in large public utility power stations show
thatthe PKG is perfectly reliable and capable of extremely high performance such as:
> 275 kA breaking of short circuit
> 50,000 A rated curents
+ Unrivalled experience in the nuclear
PKG Generator Circuit Breakers ae tested and manufactured in accordance with the applications field
International Standard IEEE C37.013, |
cro | ALSTOM | ae ane ataping he ftCIRCUIT BREAKER | PKG
Simplified design
‘The general design ofthe PKG circuit
breaker i simple, with one main chamber
per pole. The limited number of working
pars further contributes to reliability, A
Proven pneumatic system synchronises
‘contac separation and compressed air
blowing. In the main chamber, the diferent
contact rings are used to cutoff fault
currents and to pass normal load currents
Around the tungsten contacts, used to cut
off faut currents, one or more finger rings in
silver-plated copper with individual cooling
flanges ensure the passage of nominal load
currents. In parallel the auxiliary chamber
has contacts in series with alow value
resistance. Ths resistance damps the high
transient recovery voltages, which appear on
‘contact separation wien the circuit breaker
interrupts large current faults.
Principle of arc interruption
In closed position
‘The contacts ofthe main and auxiliary
‘chambers are closed, The two chambers are
ful of compressed air.
Sophisticated Modelling
1 Main chamber
2 Auilary chamber
3 - Moving contact
14 Fed contact
5 Silencer 9 - Blower
6 - Resistor 10- Fan
7-Insulated support 32 - Radiator
a Enclosure
On opening
The mobile contact of the main chamber is The contacts ofthe aliary chamber open
‘activated and the blow valves open and afew milseconds after those of the main
allow air to escape from the chamber, thus chamber, a single or a double axial blowing
prottucing a double axial blowing between ‘between the fied and the mobile contact of
the contacts and suppressing the arc and the chamber interrupt the resistive curent
interrupting the short-circuit current.
yl
Soaaa eG ad
Flexible Installation
‘Alstom Grd compression stations supaly dry
airto the PKG. They are sized to meet
‘operating cycle and sequence requrernents
and ensure completely self-contained
operation.
“The flexibly of component integration means
thata compression station can ft any internal
corexternal configuration. Depending on the
type of station, the complete compressed a
supply ystem comprises:
For an individual station supplying 2
single CB
+ ahigh-pressure production and storage
receiver
+ low-pressure distribution network tthe
Circuit breaker service pressure
+ a circuit breaker actuated pressure reducing
unit inking the two networks and providing
compressor contol
For a central station supplying several CB
+ ahigh-pressure production and storage
network
+ a medium pressure distribution and storage
network
+ alow-pressure distribution network tthe
iret breaker service pressure
two pressure reducing units, actuated by
the circuit breakers, ink up the different
networks
Proactive maintenance
‘Thanks to the inspection window ofthe PKG, an optional pyrometer can be installed in order to
‘monitor the main contact temperatures in real time. An integrated infrared camera ensures
Drecse measurements which ate transmitted by remote acces. This option aso allows pro
active maintenance concerning the electrical wear ofthe PKG interrupting contacts
‘Safe maintenance
During maintenance of either the generator er grounded transformer, the PKG circuit breaker
canactas a disconnecting switch between grounded items and those under voltage. With its
principal contacts ope, it satisfies IEC standard requirements, giving it the advantage over other
iteut breakers equipped with independent disconnecting swites.
‘When the PKG circuit breakers used as a disconnecting switch without compressed air, the
‘pen contacts resist peak shocks up to 365 kV (peak value) and industrial frequency voltages up
10-60 KV (RMS value). When the circuit breaker has been emptied of compressed ai, friction
between the sliding contact is sufficient to prevent accidental movement and closing,
Inspection windows enable visual verification that the main and auxliary contacts ae in the
‘pen postion. For further protection, locking bars can be inserted inthe main and auxiliary
chambers,
PL Load break switch
In order to make or break normal load currents on generator start-up and shut-down, without
cut-off of current faults, Alstom Grid offers the PG switch, a variation ofthe PKG circuit breaker.
‘The PG switch is identical tothe PKG circuit breaker, minus the auliary chamber, in its design,
fabrication and operation. Ii ui and tested forthe same values asthe load curent of the
PKG circuit breakers
Mitre besmmceae ™ltocacse shesaaa Cw}
Air cooling - the safe and cost-effective solution
This air system eliminates the rsks found with water cooling (water quality, permanent risks of corrosion, vaporsation freezing or leakages) and
‘eliminates costly auxiliary equipment. As the cut-off contacts are separated from the contacts which pass load currents, high conductiblity is
‘maintained, avoiding temperature increases above those set inthe prescribed standards,
The cooling device can consist of
«Radiator fins in which the circuit breaker's compressed air circulates for cooling by convection and natural radiation
+ External fans blowing against the radiators
Blowers or turbines pushing the compressed air through the radiator tubes
‘The design is based on a fully redundant philosophy, thus radiators, fans and turbines are duplicated assuring avery high system availabilty.
‘These devices allow a withstand of normal lead currents up to 50,000 A without excessive heating,
!
|
3
i
i
z
i
'
i
I
i
In case of a breakdown in the fans, blowers or turbines, the PKG circuit breakers allow the passage of current produced by the generator during the i
normal time require for load reduction operations. j
‘ype description
pe sar ue Lou !
asic versions: Hit ee 4
PKG Arblast cuit breaker i
Ac blast ad teaksiteh (2nd generation) i
Optional equipment available: i
> Rwith radiators i
> V with aiators and external fans i
> Cwith radiators, eerral fans and blowers TWP R Trev Type Cort nid
2a cera fansand lowers nrintrs «== Wiheatintos ond == Wihradatsandetaral FEE
external fans fans, biowers and rbines EEE
He
a
it
Device type PAG Creuitbreaker Plead break switch i :
ated vokape w 38 3 a
Fated Feary a a wre i
Rated normal curent A Tp 10 50,000" Tate 50,000" Hu
Rated shor-creuit brealing capacly ia
> Symmetrical (cm.s. value) ian Up to 275 er Hy
> Asymmetrical mA 340 NA He
Rates sorte raking ere Gah 780 780 i i
Rated short-time ie
> Withstand current cy 275 275 dey
~peakwe ‘a ‘000 to00 Hy
ated insulation level (to ground) iat
> At power Frequency wv 10 To Bee
> At ightrng impulse (2/50 us wave) AV (peoe) 180 150 gh
Rated insulation evel (accross terminals) ie
> at power frequency w 80 80 Hu
> Atlighting impulse (12/50 ys wave) 0 (peo 165 165 u
Maximum intrupting tine me 30 20 a
Rated opeangsequece atin C03 ninco wannto OTE
* higher ratings on request ; i : '
un
‘Alstom Grid Worldwide Contact Centre
Toucgim soe cro | ALSTOM
vrnvgatsomcam