Calculation Sheet for-6 UPS:1. No.

Of Batteries and Size Calculation for 6 kVA Online UPS with 30 min Backup:i. Known details (FYI mentioned on UPS Catalogue):
a. Load of UPS: 6 kVA
b. Power Factor: 0.9
c. Efficiency of UPS (in Eco Mode): 93 %
d. Total Cell Voltage (end cell voltage): 10.5 Volt
e. No. Of Battery: 20 No. (DC Voltage Requirement is 240 Volt)
The current rating (Idc) achieved is not
ii. Calculation and Formula Used:
a. I DC (Amp.) = (Load X 1000 X Power factor) /(efficiency X Total Cell Voltage
the final rating.ABB has to apply the
x No. of battery)
following factors to achieve the final
= (6 X 1000 X 0.9) / (.93 X 10.5 X 20)
current rating.For that current rating with
= 27.64Amp.
30 min back up AH rating shall be
b. For Ampere-Hour Calculation for your reference: -

selected.
> Aging factor
> Design margin
> Temperature correction factor

Above mentioned discharge current in point i.e. 27.64Amp, now as we require 30min. back up then from graph we
recommend 12V/26AH battery which can give around 30 min battery backup.
So we suggest to use 12 Volt 26Ah, SMF Grade Batteries for around 30min. backup for 6 kVA UPS.