SPESIFIKASI RECLOSER M1 - 44 - 156

RATINGS
RATED MAXIMUM VOLTAGE
RATED CONTINOUOUS CURRENT
EMERNGENCY CURRENT
FAULT MAKE CURRENT
FAULT MAKE CAPACITY
RATED FREQUENCY
POWER OPERATING TIME
MECHANICAL OPERATIONS
RATED FULL LOAD OPERATIONS
SHORT TIME CURRENT
BREAKING CAPACITY
MAINLY ACTIVE (0,7pF)
FALUT BREAK CAPACITY
CABLE CHARGING
LINE CHARGING
TRANSFORMER MAGNETISING
CAPACITOR BANK
LIGHTNING IMPULSE WITHSTAND LEVEL
PHASE TO EARTH
ACROSS INTERUPTER
OM LOSS OF SF6
POWER FREQUENCY WHITSTAND VOLTAGE
PHAE TO EARTH
ACROSS INTERUPTER
OPENING MECHANISM
CLOSING MECHANISM
TANK CONSTRUCTION
INSULTING MEDIUM
MAINTENANCE INTERVAL
SERVICE CONDITION
RADIATION(MAX)
HUMIDITY
ALTITUDE METERS(MAX)
ALTITUDE FEET(MAX)
NETWEIGHTS
CIRCUIT BREAKER WITH POLE MOUNT BRACKET
CONTROL CUBICLE WITH CONTROL CABLE
GROSS WEIGHT OF CRATE
EXTERNAL VT(N SERIES ONLY)
CRATE DIMENSIONS
WIDTH
DEPTH
HEIGHT

27 KV
800 A
850 A
12.5 KA
31.5 KA
50/60 HZ
0.1/0.05 S
10000
10000
12.5
800 A
12.5 KA
25 A
5A
22 A
250 A
150 KV
150 KV
70 KV
60 KV
60 KV
SPRING
SOLENOID
WELDED STAINLESS STEEL
SF6 GAS
5 YEARS
1.1 Kw/m2
0 to 100 %
3000 m
9840 Ft
249 Kg
41 Kg
404 Kg
60 Kg
1160 Mm
730 Mm
1640 Mm

APPLICABLE STANDARDS
N27

IEC 62271-100
ANSI C37.60