Professional Documents
Culture Documents
Sheath Circulating Current Analysis of A Crossbonded Power Cable Systems
Sheath Circulating Current Analysis of A Crossbonded Power Cable Systems
320~328, 2007
1. Introduction
In the case of underground power cable systems, the
sheaths are crossbonded together at each end of the cable
to suppress the induced voltage in the sheaths. The details
of the various sheath bonding methods can be referred to in
the IEEE guide [1] and technical report of the CIGRE
Working group 07 [2]. Specially, the crossbonding of the
sheaths produces a returning path of the fault current and
also suppresses the overvoltage in a transient state. These
phenomena have been investigated by many researchers
[3-5]. The current induced from other phase cables is also
produced at the sheath of a crossbonded power cable
system in a steady state. This current is known as sheath
circulating current. According to IEC Std. 287 [6], the
high sheath circulating current has an influence on sheath
circulating loss, which increases the thermal resistance of
cable and then reduces the permissible current. It will also
cause danger to the cable maintenance engineer. Therefore,
its very important to analyse the reason why the sheath
current rises obviously.
In this paper, the characteristic of the sheath circulating
current is first analysed at the actual underground power
cable system that has some problems pertaining to the high
F ( jw ) =
f (t )e jwt d
(1)
f (t ) =
1
2
F ( jw ) e jwt d
(2)
X N ( k ) = x ( n )e
j(
2
) nk
N
(3)
n=0
Where, k = 0, 1, 2, 3, , N-1.
Equation (3) is the digital expression of Fourier transform
and this called DFT (Discrete Fourier Transform). IDFT
(Inverse Discrete Fourier Transform) is also defined by
Equation (4).
2
j(
) nk
1 N 1
X N ( k )e N
N n =0
Where, n = 0, 1, 2, 3, , N-1.
x(n) =
(4)
321
CT Sensor(9 Channels)
BPF
A/D
Sampling
DFT
Cos(nwt) look-up table
Convolution
RMS Calculation
Phase Angle
Calculation
No
Stop Key
Yes
Display
322
CT7
CT1
CT2
CT4
CT8
CT3
CT5
CT9
CT6
S S/S
Power cable
EBG
NJ : Normal joint
IJ : Insulted joint
5
7
Cross-bonding lead
Earth wire
8
351m
J/B #1
#2
345m
#3
378m
#4
340m
#5
385m
#6
552m
#7
363m
#8
391m
#9
374m
Trefoil
#10
370m
C T2
C T3
C T4
C T5
C T8
C T9
C T6
as u rem e n t e qu ipm e n t
Po wemr eCa
ble C u rre n t A nalys e r
#11
350m
#12
330m
#13
360m
#14
360m
#15
370m
J/B #16
316m
7
4
Duct Duct
Trefoil
Ground Level
0.5m
Trefoil
Ground Level
0.5m
Ground Level
1m
1m
C T7
Duct Duct
Trefoil
349m
Ground Level
C T1
R S/S
0.3m
0.33m
323
NJ
Phase A
IJ
is
IJ
NJ
Conductor
Ic
is
Sheath
Phase B
is
Phase C
i0
R1
(a) In phase A
R2
minor section1()
minor section2(m)
minor section3(n)
(6)
(c) In phase C
Fig. 7. Simulated and measured sheath current.
The increase of the sheath currents is supposedly caused
by the mixed burying formation of the cable and the
different length of the section. In Section 4, we are going
to study the characteristics of the sheath circulating
currents to find out which affect them the most. Also from
the comparison between test and simulation, it is validated
that both test and simulation methods are effective and
reliable in current sheath study.
(5)
(8)
De
r
[/km]
(9)
324
De
S
[/km]
(10)
Where,
'1 : loss caused by sheath circulating current
''1 : loss caused by eddy current
154 kV OF 2000[ ], single circuit of trefo il
De
S
[/km]
(12)
W d [0.5T1 + n(T 2 + T 3 + T 4)
RT1 + nR(1 + 1)T 2 + nR(1 + 1 + 2)(T 3 + T 4)
(13)
Temperature of sheath
Temperature of sheath [ C]
Permissib le current
[/km] (11)
Permissible current [A]
z ii = Rs + 0 .000989 f + j 0 .0029 f ln
(a) Trefoil
(14)
(b) Duct
Fig. 10. Trefoil and duct in unified burying formation.
325
IJ
IJ
NJ
Conductor
Ic
Phase A
Sheath
Phase B
Phase C
i0
R1
100m 1000m
Minor section1
i0
300m
Minor section2
300m
R2
Minor section3
100-500mm
2
C12
100-500mm C23
C13
1
100-500mm
NJ
330mm
IJ
330mm
IJ
NJ
Conductor
Ic
Phase A
Sheath
Phase B
Phase C
i0
R1
i0
300m
Minor section1
300m
Minor section2
300m
R2
Minor section3
326
B
A
B
A
C
C
B
A
A
B
C
100-500mm
2
C12
100-500mm C23
C13
1
100-500mm
NJ
IJ
IJ
NJ
Conductor
Ic
Phase A
Sheath
Phase B
Phase C
i0
R1
i0
280m
Minor section1
324m
Minor section2
203m
R2
Minor section3
#2
252m
CNCV 325
#3
229m
#4
303m
#5
307m
#7
#6
310m
305m
#8
135m
#9
341m
#10
310m
#11
476m
378m
Distribution cable
XLPE 2000
1[m]
258m
B S/S
A S/S
258m
327
252m
229m
303m
307m
310m
305m
135m
341m
310m
476m
378m
Load
0.5[m]
: NJ(Normal joint)
: IJ(Insulation joint)
5. Conclusions
Cable configuration
Resistance (R)
Reactance (X)
Average
Type 1
0%
0%
0%
Type 2
20 %
15 %
17.5 %
Type 3
27 %
30 %
28.5 %
Type 4
42 %
33 %
37.5 %
328
Chae-Kyun Jung
He received his B.Sc., M.Sc. and Ph.D.
degrees in Electrical Engineering from
Wonkwang University, Korea, in 1999,
2002 and 2006, respectively. He was a
Postdoctoral Researcher at the University
of Siegen, Germany in 2007. He is
currently working at the Korea Electric Power Research
Institute (KEPRI) since 2007 where is he is a researcher in
Transmission Technology Group. His research interests
include power systems operation, analysis of power cable
systems, fault location, protective relaying.
Reference
[1] IEEE, IEEE Guide for the Application of Sheath
Bonding Methods for Single-conductor Cables and
Calculation of induced Voltage and Current in Cable
Sheaths, ANSI/IEEE Std. 575-1998.
[2] Working Group 07 of Study Committer 21, Guide to
the Protection of Specially Bonded Cable Systems
against Sheath Overvoltage, Electra, No. 128.
[3] B. Gustavsen, J. Sletbak, T. Henrikson, Simulation of
Transient Sheath Overvoltage in the Presence of
Proximity Effects, IEEE Trans. On Power Delivery,
Vol. 10, No. 2, April 1995.
[4] B. Gustavsen, J. Sletbak, Transient Sheath Overvoltage
in Armoured Power Cables, IEEE Trans. On Power
Delivery, Vol. 11, No. 3, July 1996.
[5] Y. Itoh, N. Nagaoka, A. Ametani, Transient Analysis
of a Crossbonded Cable System Underneath a Bridge,
IEEE Trans. On Power Delivery, Vol. 5, No. 2, April
1990.
[6] IEC 287-1-1 Electric Cables Calculation of the Current
Rating, Part 1: Current rating Equations (100% Load
Factor) and Calculations of Losses, Section 1: General,
1995.
[7] M. G. Dwek, M. N. Eggleton, Electrical parameters of
400kV and 275kV cables used in England and Wales.
[8] J. A. Williams, P. L. Ostermann, R. W. Samm, Underground
Transmission System Reference Book, 1992 Edition.
Jong-Beom Lee
He received his B.Sc., M.Sc. and Ph.D.
degrees in Electrical Engineering from
Hanyang University, Korea, in 1981,
1983 and 1986, respectively. He worked
at the Korea Electrotechnology Research
Institute from 1987 to 1990. He was a
Visiting Scholar at Texas A&M University and the Swiss
Federal Institute of Technology (ETH), Switzerland. He is
currently a Professor in the Department of Electrical,
Electronic & Information Engineering, Wonkwang University,
Korea. His current research interests are power systems
operation, analysis of power cable systems, protective
relaying, and application of AI to power systems. He is a
member of KIEE and IEEE.
Ji-Won Kang
He received his B.Sc., M.Sc. and P.hD.
degrees in Electrical Engineering from
Hanyang University, Korea, in 1987,
1993 and 2003, respectively. He has
been working at the Korea Electric
Power Research Institute (KEPRI)
since 1993 where he is currently a Senior Technical Staff
Member in the Transmission Technology Group. His
current research interests are power systems operation and
the analysis and diagnosis of power cable systems.