You are on page 1of 2

DriPak 2000

Initial Resistance (Pa)

Resistance Curves and Selection Chart Data


Rated
Face
Velocity1)
(m/s)

DriPak 2000 90%


225
200
175
150

Rated
Airflow
Capacity
(m3/h)

Rated
Initial2/3)
Resistance
(Pa)

9
592x592x700
4
287x592x700
7
490x592x700
8
592x592x635
2.5
4
287x592x635
6
490x592x635
6
592x592x508
1.25
3
287x592x508
5
490x592x508
80-85% Average Efficiency2) - F 7

8.0
3.6
6.2
6.7
3.3
5.0
4.1
2.0
3.4

4250
2125
3550
3400
1700
2850
1700
850
1400

160
160
160
135
135
135
90
90
90

9
4
7
8
4
6
6
3
5

8.0
3.6
6.2
6.7
3.3
5.0
4.1
2.0
3.4

4250
2125
3550
3400
1700
2850
1700
850
1400

105
105
105
80
80
80
60
60
60

9
4
7
8
4
6

8.0
3.6
6.2
6.7
3.3
5.0

4250
2125
3550
3400
1700
2850

75
75
75
65
65
65

6
3
5
6
3
5
6
3
5

5.0
2.5
4.3
4.1
2.0
3.4
2.5
1.2
2.0

3400
1700
2850
3400
1700
2850
3400
1700
2850

55
55
55
60
60
60
65
65
65

100

3.2

75

25
0
0

0.5

1.0

1.5

2.0

2.5

3.0

Face Velocity (m/s)

DriPak 2000 80%


225
200
175
150

3.2

125
100
75

2.5

50
25
0
0

0.5

1.0

1.5

2.0

2.5

3.0

Initial Resistance (Pa)

Face Velocity (m/s)


DriPak 2000 60%

1.25

592x592x700
287x592x700
490x592x700
592x592x635
287x592x635
490x592x635
592x592x508
287x592x508
490x592x508

60-65% Average Efficiency2) - F 6

120

3.2

90

2.5

60

30

592x592x700
287x592x700
490x592x700
592x592x635
287x592x635
490x592x635

50-55% Average Efficiency2) - F 5

0
0

0.5

1.0

1.5

2.0

2.5

3.0

Face Velocity (m/s)

Initial Resistance (Pa)

Number
of
Pockets

90-95% Average Efficiency2) - F 8

125

50

Initial Resistance (Pa)

Gross
Media
Area
(m2)

Actual
Size4/5)
(wxhxd)
(mm)

2.5
2.5

DriPak 2000 50%


120

2.5

90

60

30
0
0

0.5

1.0

1.5

2.0

2.5

3.0

Face Velocity (m/s)

AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98

592x592x635
287x592x635
490x592x635
592x592x508
287x592x508
490x592x508
592x592x305
287x592x305
490x592x305

Notes:
1) Filters can be operated at 67% to 133% of rated face velocity.
2) All performance data based on EN779 1993 standard (ASHRAE 52.1-1992 test method).
3) The recommended final resistance is 450 Pa.
4) The DriPak 2000 filter sizes fit into frame sizes 610 x 610, 305 x 610 and 508 x 610 mm.
5) Filters are also available in other sizes and with 25 and 20 mm headers.

International AAF Offices:


Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)

AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)

AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
RA-2-542-IN-2-0999

1999 AAF International

You might also like