Project:

Intake Pumping Station


Calculations for Pump sizing and Generator Sizing
Item
1
2
3
4
5
6
7
8
9
10
11
12

Description
Pump Head
Flow Rate Per Pump
No. of Pumps on duty
No of Pumps on standby
Pumping Power
Motor Power
Installed Motor Power
Starting Power of Pump
1 Pump Running and The other pump Starting
Power Factor
Generator kVA
Next Standard Capacity

Formula

(rhoxgxQxH)/efficiency
Pump Power/ Motor Efficiency
Next Higher standard Value
2.5 x Nominal Power

item9/item10

Value
Unit
95
m
115
l/s
2
unit
1
unit
154
kW
171.1111
kW
180
kW
450
kW
630
kW
0.85
741.1765
kVA
750
kVA