historical performance
In the past, Staff used a five year average plus one standard
deviation for setting targets (each utility had its own definition of
a major storm)
Currently, ten years of historical data are used for setting targets
(all utilities use the 2.5 Beta methodology for excluding major
events)
Staff expects all pertinent historical performance data to be
included in each electric utilitys application for new standards
(indices):
Exclusions
(Major Storms vs. Major Events)
The old rules required the exclusion of major storms from performance
data
The old rules allowed each utility to develop its own major storm
definition
As a result, there were variations among utilities on how their major storm
exclusions affected their respective performances
To address this problem, the IEEE developed the 2.5 Beta methodology
for establishing a standardized major event threshold
The new rules adopted a modified version of the IEEE methodology
10
11
Methodology Development
This methodology was developed by an IEEE working group
12
Purpose
The methodology is used to determine calendar days upon
13
Collect values of daily SAIDI for five sequential years ending on the last day of
the last complete reporting period.
If any day in the data set has a value of zero for SAIDI, do not include that day in
the analysis
Take the natural logarithm (ln) of each daily SAIDI value in the data set
Find (Alpha), the average of the logarithms of the data set
Find (Beta), the standard deviation of the logarithms of the data set
Compute the major event day threshold, TMED, using the equation:
TMED = e(+2.5)
Any day with a daily SAIDI greater than the threshold value, TMED ,that occurs
during the reporting period is classified as a major event day
14
15
performance standards
An objective major event definition for classifying
major events
Major event definition is the same for all electric
distribution utilities
16
17
Survey Use
Used as one of the Inputs in the Methodology Utilized to Determine the Electric Utilities
Minimum Performance Standards for the CAIDI and SAIFI Service Reliability Indices
Measurement of Customer Perception
Expectations of Service Reliability
Service Interruptions
o Frequency
o Duration
o Economic Impact
Minimum Frequency and Sample Size
Frequency
Every three years, an annual survey program is conducted using a quarterly
administered survey to smooth out or eliminate bias
Sample Size
Sample Size Meets a Standard of 95 Percent Confidence Level with a Plus/Minus 5
Percent Absolute Error Rate
Surveys Will Be Conducted Separately on Residential and Business Customers
18
Staff Oversight
Assess the Electric Utilities Submitted Survey Instruments
19
20
SCADA Supervisory Control and Data Acquisition used to remotely monitor and
SCADA and DA and extends the sensing and control functions to the customers meter.
21
22
Outage Reporting
Each electric utility must immediately report each outage to the commission
An outage means an interruption to service
An outage is reportable when involving 2500 customers or more for a projected
period of at least four hours or 100 customers for a projected period of 24 hours
or more
Outage notifications are circulated to PUCO Call Center and other PUCO Staff
23
Emergency Planning
Each electric utility shall maintain and implement an emergency plan and
24
Commission Enforcement
Rule 4901:1-10-30, O.A.C. states that if an electric utility fails to comply with
the rules in this Chapter (4901:1-10), the utility may be subject to:
Forfeitures of not more than ten thousand dollars for each offense, with
each days continuance being a separate offense
Corrective action to effectuate compliance
Restitution or damages to the customer/consumer
Any other remedies available under law
25
These programs are filed in a public docket and approved by the PUCO.
These programs shall establish preventative requirements for the electric utility to
maintain safe and reliable service.
Programs shall include: (a) Poles and towers, (b) Circuit and line inspections, (c)
Primary enclosures (e.g. pad-mounted transformers and switch gear) and
secondary enclosures (e.g. pedestals), (d) Line re-closers, (e) Line capacitors, (f)
Right-of-way vegetation control, and (g) Substations.
26
27
28
Contract Crews
29
Aerial Saw
30
Cleared Corridor
31
32
33
34
in
Informally contacts utility companies for facts about customers
concerns
35
36
Investigation
(mediate disputes)
37