You are on page 1of 68

EMUA

V100R001

User Guide

Issue

10

Date

2010-03-30

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Huawei Technologies Co., Ltd. provides customers with comprehensive technical support and service. For any
assistance, please contact our local office or company headquarters.

Huawei Technologies Co., Ltd.


Address:

Huawei Industrial Base


Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website:

http://www.huawei.com

Email:

support@huawei.com

Copyright Huawei Technologies Co., Ltd. 2010. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior written
consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the
customer. All or part of the products, services and features described in this document may not be within the
purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,
and recommendations in this document are provided "AS IS" without warranties, guarantees or representations
of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

EMUA
User Guide

Contents

Contents
About This Document.....................................................................................................................1
1 Changes in EMUA User Guide................................................................................................1-1
2 Overview of the EMUA.............................................................................................................2-1
2.1 Functions of the EMUA..................................................................................................................................2-2
2.2 Exterior of the EMUA.....................................................................................................................................2-3
2.3 Internal Structure of the EMUA......................................................................................................................2-6
2.4 Communication Ports on the EMUA..............................................................................................................2-9
2.4.1 RS485 Serial Port.................................................................................................................................2-10
2.4.2 RS232 Serial Port.................................................................................................................................2-11
2.4.3 Commissioning Serial Port...................................................................................................................2-12
2.5 Monitoring Ports of the EMUA....................................................................................................................2-12
2.5.1 Monitoring Port for the Water Sensor..................................................................................................2-13
2.5.2 Monitoring Port for the Smoke Sensor................................................................................................2-14
2.5.3 Monitoring Port for the Infrared Sensor...............................................................................................2-15
2.5.4 Monitoring Port for the Door Status Sensor.........................................................................................2-16
2.5.5 Monitoring Port for the Humidity/Temperature Sensor.......................................................................2-17
2.5.6 Monitoring Port for Boolean Signals...................................................................................................2-18
2.5.7 Monitoring Port for Analog Signals.....................................................................................................2-19
2.5.8 Monitoring Port for the Relay Node Boolean Signals.........................................................................2-21
2.6 Technical Specifications of the EMUA.........................................................................................................2-23

3 Introduction to the Sensors......................................................................................................3-1


3.1 Water Sensor...................................................................................................................................................3-2
3.2 Smoke Sensor..................................................................................................................................................3-2
3.3 Infrared Sensor................................................................................................................................................3-4
3.4 Door Status Sensor..........................................................................................................................................3-5
3.5 Humidity/Temperature Sensor........................................................................................................................3-7
3.6 Self-Selected Sensors......................................................................................................................................3-8

4 Installing the EMUA..................................................................................................................4-1


5 Installing the Sensors................................................................................................................5-1
5.1 Installing the Water Sensor.............................................................................................................................5-2
5.2 Installing the Smoke Sensor............................................................................................................................5-3
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

EMUA
User Guide

Contents

5.3 Installing the Infrared Sensor..........................................................................................................................5-6


5.4 Installing the Door Status Sensor....................................................................................................................5-7
5.5 Installing the Humidity/Temperature Sensor..................................................................................................5-9

6 Commissioning the EMUA......................................................................................................6-1


7 Handling Common Faults........................................................................................................7-1

ii

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

Figures

Figures
Figure 2-1 Exterior of the EMUA of type A........................................................................................................2-4
Figure 2-2 Front panel of the EMUA of type A...................................................................................................2-4
Figure 2-3 Exterior of the EMUA of type B........................................................................................................2-5
Figure 2-4 Front panel of the EMUA of type B...................................................................................................2-5
Figure 2-5 Exterior of the EMUA of type C........................................................................................................2-6
Figure 2-6 Front panel of the EMUA of type C...................................................................................................2-6
Figure 2-7 Board layout inside the EMUA of type A or B..................................................................................2-7
Figure 2-8 Board layout inside the EMUA of type C..........................................................................................2-7
Figure 2-9 Pins of the RS485 serial port socket.................................................................................................2-10
Figure 2-10 Pins of the RS232 serial port socket...............................................................................................2-11
Figure 2-11 Pins of the commissioning serial port socket.................................................................................2-12
Figure 2-12 Monitoring port for the water sensor..............................................................................................2-14
Figure 2-13 Monitoring port for the smoke sensor............................................................................................2-15
Figure 2-14 Monitoring port for the infrared sensor..........................................................................................2-16
Figure 2-15 Monitoring port for the door status sensor.....................................................................................2-17
Figure 2-16 Monitoring port for the humidity/temperature sensor....................................................................2-18
Figure 2-17 Monitoring port for Boolean signals..............................................................................................2-19
Figure 2-18 Monitoring port for analog signals.................................................................................................2-20
Figure 2-19 Connecting the analog sensor of the voltage type..........................................................................2-21
Figure 2-20 Connecting the analog sensor of the current type...........................................................................2-21
Figure 2-21 Monitoring Port for relay node Boolean signals............................................................................2-22
Figure 2-22 Cable connection of the relay node................................................................................................2-22
Figure 3-1 Exterior of the YW517B water sensor................................................................................................3-2
Figure 3-2 Exterior of the JTY-GD-01K smoke sensor.......................................................................................3-3
Figure 3-3 Exterior of the MC-760T infrared sensor...........................................................................................3-4
Figure 3-4 Exterior of the AGX105F door status sensor.....................................................................................3-5
Figure 3-5 Exterior of the HO-03A door status sensor........................................................................................3-6
Figure 3-6 Working principle of the AGX105F door status sensor.....................................................................3-6
Figure 3-7 Exterior of the WS302A1T4 humidity/temperature sensor................................................................3-7
Figure 3-8 Relations between the humidity and output current...........................................................................3-9
Figure 3-9 Relations between the temperature and output current.......................................................................3-9
Figure 4-1 Installing the EMUA inside the cabinet.............................................................................................4-2
Figure 4-2 Installing the EMUA inside the rack..................................................................................................4-2
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

iii

EMUA
User Guide

Figures

Figure 5-1 Installing the water sensor..................................................................................................................5-2


Figure 5-2 Connecting the water sensor...............................................................................................................5-3
Figure 5-3 Installation of the smoke sensor......................................................................................................... 5-5
Figure 5-4 Connecting the smoke sensor.............................................................................................................5-6
Figure 5-5 Connecting the infrared sensor...........................................................................................................5-7
Figure 5-6 Connecting the AGX105F door status sensor.................................................................................... 5-8
Figure 5-7 Connecting the HO-03A door status sensor.......................................................................................5-8
Figure 5-8 Connecting the humidity/temperature sensor...................................................................................5-10

iv

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

Tables

Tables
Table 2-1 Functions of the three EMUA models.................................................................................................2-3
Table 2-2 Functions and settings of the DIP switches on the panel of the EMUA..............................................2-8
Table 2-3 Meanings of the pins of the RS485 serial port socket........................................................................2-10
Table 2-4 Meanings of the pins of the RS232 serial port socket........................................................................2-11
Table 2-5 Meanings of the pins of the commissioning serial port socket..........................................................2-12
Table 2-6 Meanings of the terminals of the monitoring port for the water sensor.............................................2-14
Table 2-7 Meanings of the terminals of the monitoring port for the smoke sensor...........................................2-15
Table 2-8 Meanings of the terminals of the monitoring port for the infrared sensor.........................................2-16
Table 2-9 Meanings of the terminals of the monitoring port for the door status sensor....................................2-17
Table 2-10 Meanings of the terminals of the monitoring port for the humidity/temperature sensor.................2-18
Table 2-11 Valid values of Boolean signals of the voltage type........................................................................2-19
Table 2-12 Meanings of the terminals of the monitoring port for Boolean signals...........................................2-19
Table 2-13 Meanings of the terminals of the monitoring port for analog signals..............................................2-20
Table 2-14 Meanings of the terminals of the monitoring port for relay node Boolean signals..........................2-22
Table 2-15 Alarms corresponding to the relay switch........................................................................................2-23
Table 2-16 Technical specifications of the EMUA............................................................................................2-23
Table 2-17 Performance specifications of the EMUA.......................................................................................2-24
Table 3-1 Technical specifications of the YW517B water sensor.......................................................................3-2
Table 3-2 Indicator on the smoke sensor..............................................................................................................3-3
Table 3-3 Technical specifications of the JTY-GD-01K smoke sensor...............................................................3-3
Table 3-4 Technical specifications of the MC-760T infrared sensor...................................................................3-5
Table 3-5 Technical specifications of the AGX105F door status sensor.............................................................3-7
Table 3-6 Technical specifications of the HO-03A door status sensor................................................................3-7
Table 3-7 Technical specifications of the WS302A1T4 humidity/temperature sensor........................................3-8
Table 5-1 3-core leading cable of the water sensor..............................................................................................5-3
Table 7-1 Solutions to common faults in the EMUA...........................................................................................7-1

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

EMUA
User Guide

About This Document

About This Document


Purpose
This document describes the exterior, interfaces, functions, and sensors of the Outdoor
Environment Monitoring Extension Unit (EMUA). In addition, this document describes how to
install the EMUA and the sensors.

Product Version
The following table lists the product version related to this document.
Product Name

Product Version

EMUA2416

V100R001

EMUA2432

V100R001

EMUA4832

V100R001

Intended Audience
This document is intended for:
l

NodeB/BTS Installer

System Engineer

Site Maintainer

Change History
For changes made in this document, refer to 1 Changes in EMUA User Guide.

Organization
1 Changes in EMUA User Guide
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

EMUA
User Guide

About This Document

This describes the changes in the EMUA User Guide.


2 Overview of the EMUA
Applicable to all types of BTSs/NodeBs manufactured by Huawei, the outdoor environment
monitoring unit (EMUA) is used to monitor the environment in the equipment room and the
cabinet.
3 Introduction to the Sensors
The sensors provided by Huawei can be used directly. The sensors not provided by Huawei can
be used only if their specifications meet the requirements.
4 Installing the EMUA
This describes how to install the EMUA. The EMUA can be installed in different ways.
5 Installing the Sensors
The installation methods of the sensors provided by Huawei are described here. For the sensors
not provided by Huawei, see their respective instructions during installation.
6 Commissioning the EMUA
This describes how to commission the EMUA.
7 Handling Common Faults
This describes the solutions to common faults in the EMUA.

Conventions
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol

Description
Indicates a hazard with a high level of risk, which if not
avoided,will result in death or serious injury.
Indicates a hazard with a medium or low level of risk, which
if not avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation, which if not
avoided,could result in equipment damage, data loss,
performance degradation, or unexpected results.
Indicates a tip that may help you solve a problem or save
time.
Provides additional information to emphasize or supplement
important points of the main text.

General Conventions
The general conventions that may be found in this document are defined as follows.
2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

About This Document

Convention

Description

Times New Roman

Normal paragraphs are in Times New Roman.

Boldface

Names of files, directories, folders, and users are in


boldface. For example, log in as user root.

Italic

Book titles are in italics.

Courier New

Examples of information displayed on the screen are in


Courier New.

Command Conventions
The command conventions that may be found in this document are defined as follows.
Convention

Description

Boldface

The keywords of a command line are in boldface.

Italic

Command arguments are in italics.

[]

Items (keywords or arguments) in brackets [ ] are optional.

{ x | y | ... }

Optional items are grouped in braces and separated by


vertical bars. One item is selected.

[ x | y | ... ]

Optional items are grouped in brackets and separated by


vertical bars. One item is selected or no item is selected.

{ x | y | ... }*

Optional items are grouped in braces and separated by


vertical bars. A minimum of one item or a maximum of all
items can be selected.

[ x | y | ... ]*

Optional items are grouped in brackets and separated by


vertical bars. Several items or no item can be selected.

GUI Conventions
The GUI conventions that may be found in this document are defined as follows.
Convention

Description

Boldface

Buttons, menus, parameters, tabs, window, and dialog titles


are in boldface. For example, click OK.

>

Multi-level menus are in boldface and separated by the ">"


signs. For example, choose File > Create > Folder.

Keyboard Operations
The keyboard operations that may be found in this document are defined as follows.
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

EMUA
User Guide

About This Document

Format

Description

Key

Press the key. For example, press Enter and press Tab.

Key 1+Key 2

Press the keys concurrently. For example, pressing Ctrl+Alt


+A means the three keys should be pressed concurrently.

Key 1, Key 2

Press the keys in turn. For example, pressing Alt, A means


the two keys should be pressed in turn.

Mouse Operations
The mouse operations that may be found in this document are defined as follows.

Action

Description

Click

Select and release the primary mouse button without moving


the pointer.

Double-click

Press the primary mouse button twice continuously and


quickly without moving the pointer.

Drag

Press and hold the primary mouse button and move the
pointer to a certain position.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

1 Changes in EMUA User Guide

Changes in EMUA User Guide

This describes the changes in the EMUA User Guide.

10(2010-03-30)
Tenth release. The document is modified according to the comments by the testers.

09(2009-12-30)
Ninth release. The document is modified according to the comments by the testers.

08 (2008-09-10)
Eighth release. The wall-mounted installation mode is deleted.

07 (2008-08-20)
Seventh release. The description of SW-ADDR is Modified, and the appearance description the
EMUA is modified.

06 (2008-05-20)
Sixth release. The pin mapping description of the data cable is added.

05 (2008-04-25)
Fifth release. The illustration of how to connect the infrared sensor is modified.

04 (2008-01-15)
Fourth release. The title of the preface is changed, the document structure is adjusted, and the
procedure for installing the EMUA on a wall is added.

03 (2007-04-20)
Third release. Indexes are added, parameter description of the self-selected sensors is added.
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

1-1

EMUA
User Guide

1 Changes in EMUA User Guide

02 (2007-02-02)
Second release. Testing problems are solved.

01 (2007-01-15)
First release.

1-2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Overview of the EMUA

About This Chapter


Applicable to all types of BTSs/NodeBs manufactured by Huawei, the outdoor environment
monitoring unit (EMUA) is used to monitor the environment in the equipment room and the
cabinet.
2.1 Functions of the EMUA
This describes the functions of the EMUA. Providing a variety of input ports for monitoring
signals, the EMUA supports real-time monitoring and remote monitoring. In addition, the
EMUA is highly reliable and can be flexibly configured. It supports a large area for temperature
monitoring.
2.2 Exterior of the EMUA
Each Module of EMUA has three types of exterior A, B, and C.
2.3 Internal Structure of the EMUA
This describes the internal structure of the EMUA.
2.4 Communication Ports on the EMUA
The EMUA provides the RS485 and RS232 ports for the communication between the EMUA
and the BTS/NodeB. Specifically, the EMUA4832 provides an independent commissioning
port.
2.5 Monitoring Ports of the EMUA
The EMUA provides monitoring ports for the humidity/temperature sensor, smoke sensor, water
sensor, infrared sensor, and door status sensor. In addition, the EMUA provides monitoring ports
for the Boolean signal sensor, analog signal sensor, and output control sensor, which are extended
sensors.
2.6 Technical Specifications of the EMUA
This describes the technical specifications of the EMUA.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-1

EMUA
User Guide

2 Overview of the EMUA

2.1 Functions of the EMUA


This describes the functions of the EMUA. Providing a variety of input ports for monitoring
signals, the EMUA supports real-time monitoring and remote monitoring. In addition, the
EMUA is highly reliable and can be flexibly configured. It supports a large area for temperature
monitoring.

Functions of the EMUA


Power Input
The EMUA supports input voltage detection. The alarm threshold for the input voltage can be
configured on the BTS/NodeB and delivered to the EMUA.
The EMUA provides two power input ports, which are protected from inverse connections.
l

The EMUA2416 and EMUA2432 support +24 V DC power input, and the voltage can
range from +18 V DC to +36 V DC.

The EMUA4832 supports -48 V DC power input, and the voltage can range from -36 V
DC to -72 V DC.

Environment Monitoring
l

The EMUA provides an independent port for +12 V/+24 V DC current-type (4 mA - 20


mA) humidity/temperature sensors. The temperature monitoring range is -20oC [-4oF] to
80oC [176oF].

The EMUA provides four ports for monitoring analog signals. Voltage-type (0 V - 5 V)
sensors and current-type (4 mA - 20 mA) sensors can be used. The types of monitored
analog signals can be configured through the DIP switch settings according to the BTS/
NodeB configuration.

Boolean Signal Monitoring


The EMUA provides ports for monitoring Boolean signals. Dry contact point signals and OC
signals are supported.
l

The EMUA2416 supports 16 ports for Boolean signal monitoring.

The EMUA2432 or EMUA4832 supports 32 ports for Boolean signal monitoring.

Relay Node Control


The EMUA provides six output control ports for external Boolean signals of the relay node type.
Communication Ports
The EMUA provides two RS-485 ports, which are used for the communication between the
EMUA and the BTS/NodeB.

Comparison Between the Functions of the Three EMUA Models


Table 2-1 lists the functions of the three EMUA models for you to make a comparison.

2-2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Table 2-1 Functions of the three EMUA models


EMUA2416

EMUA2432

EMUA4832

Input voltage

+24 V DC power
input

+24 V DC power
input

-48V DC power input

Range of voltage
input

+18 V DC to +36 V
DC

+18 V DC to +36 V
DC

-36 V DC to -72 V DC

Boolean signal

16 ports

32 ports

32 ports

(S1+/S1- to S16+/
S16-)

(S1+/S1- to S32+/
S32-)

(S1+/S1- to S32+/
S32-)

Boolean signal
port

32 ports

32 ports

32 ports

DIP switch
settings

By default, the DIP


switches SW24A
and SW24B are set
to OFF. Do not
change their default
settings.

You can set the DIP


switches SW24A and
SW24B.

You can set the DIP


switches SW24A and
SW24B.

Serial port
protection

Maximum current in
differential mode: 3
kA; maximum
current in common
mode: 5 kA

Maximum current in
differential mode: 3
kA; maximum
current in common
mode: 5 kA

Maximum current in
differential mode: 3
kA; maximum current
in common mode: 5 kA

(Ports 17 to 32 are
invalid)

2.2 Exterior of the EMUA


Each Module of EMUA has three types of exterior A, B, and C.

Exterior of the EMUA of Type A


Figure 2-1 and Figure 2-2 show the exterior of the EMUA of type A and its front panel
respectively.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-3

EMUA
User Guide

2 Overview of the EMUA

Figure 2-1 Exterior of the EMUA of type A

Figure 2-2 Front panel of the EMUA of type A


1

EMUA

RS-485

6
RE5+ RE5- RE6+ RE6- NC

24V3 12V3 ANA3 GND3 24V4 12V4 ANA4 GND4

24VI 12VI OPTI GND 24VS Smoke 12VG GATE

NC

NC

NC

24V1 12V1 ANA1 GND1 24V2 12V2ANA2 GND2

24VT TEMP 24VH HUMI 24VW 12VW Water GND RE1+ RE1- RE2+ RE2- RE3+ RE3- RE4+ RE4-

S29+ S29- S30+ S30- S31+ S31- S32+ S32-

S21+ S21- S22+ S22- S23+ S23- S24+ S24-

S13+ S13- S14+ S14- S15+ S15- S16+ S16-

S5+ S5-

S17+ S17- S18+ S18- S19+ S19- S20+ S20-

S9+ S9- S10+ S10- S11+ S11- S12+ S12-

S1+

S6+ S6-

S7+

S7

S8+ S8-

RUN ALM

+ - + PWR1 PWR2

10

S25+ S25- S26+ S26- S27+ S27-

S28+ S28-

S1-

S2+ S2-

S3+ S3-

11

S4+ S4-

RS-232

12

13

(1) Indicator

(2) Four ports for analog signal


sensors

(3) Port for infrared sensors

(4) Port for smoke sensors

(5) Port for door status sensors

(6) Six ports for Boolean signal


output

(7) 16/32 ports for the detection of


Boolean signals

(8) Two RS-485 ports

(9) Wiring terminal for the power


supply

(10) Port for humidity/temperature


sensors

(11) Port for water sensors

(12) RS-232 port

(13) Grounding screw

Exterior of the EMUA of Type B


Figure 2-3 and Figure 2-4 show the exterior of the EMUA of type B and its front panel
respectively.

2-4

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Figure 2-3 Exterior of the EMUA of type B

Figure 2-4 Front panel of the EMUA of type B


2

1
RUN ALM

6
RE5+ RE5- RE6+ RE6- NC

24VI 12VI OPTI GND 24VS Smoke 12VG GATE

NC

NC

NC

24V1 12V1 ANA1 GND1 24V2 12V2ANA2 GND2

24VT TEMP 24VH HUMI 24VW 12VW Water GND RE1+ RE1- RE2+ RE2- RE3+ RE3- RE4+ RE4-

S29+ S29- S30+ S30- S31+ S31- S32+ S32-

S21+ S21- S22+ S22- S23+ S23- S24+ S24-

S13+ S13- S14+ S14- S15+ S15- S16+ S16-

S5+ S5-

S17+ S17- S18+ S18- S19+ S19- S20+ S20-

S9+ S9- S10+ S10- S11+ S11- S12+ S12-

S1+

S6+ S6-

S7+

S7

S8+ S8-

EMUA

24V3 12V3 ANA3 GND3 24V4 12V4 ANA4 GND4

RS-485

PWR1+ PWR1-PWR2+ PWR2-

10

S25+ S25- S26+ S26- S27+ S27-

S28+ S28-

S1-

S2+ S2-

S3+ S3-

S4+ S4-

RS-232

11

12

(1) Indicator

(2) Four ports for analog signal


sensors

(3) Port for infrared sensors

(4) Port for smoke sensors

(5) Port for door status sensors

(6) Six ports for Boolean signal


output

(7) 16/32 ports for Boolean signal


monitoring

(8) Two RS-485 ports

(9) Wiring terminal for the power


supply

(10) Port for humidity/temperature


sensors

(11) Port for water sensors

(12) RS-232 port

NOTE

The grounding screw of the EMUA of type B is on the rear panel.

Exterior of the EMUA of Type C


Figure 2-5 and Figure 2-6 show the exterior of the EMUA of type C and its front panel
respectively.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-5

EMUA
User Guide

2 Overview of the EMUA

Figure 2-5 Exterior of the EMUA of type C

Figure 2-6 Front panel of the EMUA of type C


8

1
RUN ALM

6
RE5+ RE5- RE6+ RE6- NC

24V3 12V3 ANA3 GND3 24V4 12V4 ANA4 GND4

24VI 12VI OPTI GND 24VS Smoke 12VG GATE

NC

NC

NC

24V1 12V1 ANA1 GND1 24V2 12V2ANA2 GND2

24VT TEMP 24VH HUMI 24VW 12VW Water GND RE1+ RE1- RE2+ RE2- RE3+ RE3- RE4+ RE4-

S29+ S29- S30+ S30- S31+ S31- S32+ S32-

S21+ S21- S22+ S22- S23+ S23- S24+ S24-

S13+ S13- S14+ S14- S15+ S15- S16+ S16-

S5+ S5-

S17+ S17- S18+ S18- S19+ S19- S20+ S20-

S9+ S9- S10+ S10- S11+ S11- S12+ S12-

S1+

S6+ S6-

S7+

S7

S8+ S8-

EMUA

RS-485

+ - + PWR1 PWR2

RS-232

12

10

S25+ S25- S26+ S26- S27+ S27-

S28+ S28-

S1-

S2+ S2-

S3+ S3-

11

S4+ S4-

TX+

TX-

RX+

RX-

14

13

(1) Indicator

(2) Four ports for analog signal sensors (3) Port for infrared sensors

(4) Port for smoke sensors

(5) Port for door status sensors

(6) Six ports for Boolean signal


output

(7) 16/32 ports for the detection of (8) Two RS-485 ports
Boolean signals

(9) Wiring terminal for the


power supply

(10) Port for humidity/temperature (11) Port for water sensors


sensors

(12) RS-232 port

(13) Grounding screw

(14) Commissioning serial port

2.3 Internal Structure of the EMUA


This describes the internal structure of the EMUA.

Board Layout
Figure 2-7 shows the board layout inside the EMUA of type A or B.

2-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Figure 2-7 Board layout inside the EMUA of type A or B


SW24B SW24A SW12B SW12A
12345678

12345678

ON

ON

12345678

12345678

ON

ON

SW_THE SW_AV
1234

1234

12
1234

ON

ON
ON

SW_ADDR

Ligntning protection
board

SW_AE

1234

DC/DC
pouwer module

Lattice

ON

ON

SW_BKE

CPU

Figure 2-8 shows the board layout inside the EMUA of type C.
Figure 2-8 Board layout inside the EMUA of type C

SW_THE

SW_AE

4321

ON

87654321
87654321

ON

87654321

ON

87654321

SW12A

SW12B

ON

4321

SW24A

SW24B

SW_AV

ON

CPU

SW_BKE

ON

ON

4321

SW_ADDR

4321

ON

21

DC/DC power
module

IDC connector

Lightning protection and


interface board for Boolean
signals

ON

IDC connector

DIP Switches
Table 2-2 lists the functions and settings of the DIP switches on the panel of the EMUA.
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-7

EMUA
User Guide

2 Overview of the EMUA

Table 2-2 Functions and settings of the DIP switches on the panel of the EMUA
Silkscreen

Function

Setting

SW_ADDR

Selection of the
communication protocol

If a DIP switch bit is set to ON, it


represents 0. If a DIP switch bit is set to
OFF, it represents 1.

The settings of the DIP switch


SW_ADDR (1234) are as follows:

Outdoor CDMA BTS: 0000

Indoor CDMA BTS or non-doubledensity GSM BTS: 0001

Double-density GSM BTS, WCDMA


NodeB or LTE eNodeB or WiMAX
BTS (the EMUA does not support
alarm association): 0010

Double-density GSM BTS, WCDMA


NodeB or LTE eNodeB or WiMAX
BTS (the EMUA supports alarm
association)1110

NOTE
l If an EMUA is delivered along with the BTS/

NodeB, the communication protocol is


already configured according to the BTS/
NodeB type.
l If an EMUA is delivered independently, the

default setting of the DIP switch SW_ADDR


(1234) is 0010.
l If an EMUA must support alarm association,

the DIP switches must be set on site.

SW_BKE

Bit 1: water sensor setting

2-8

This bit is set to ON if a sensor is not


used.

This bit is set to OFF if a sensor is used.

Bit 2: smoke sensor setting

This bit is set to ON no matter whether a


sensor is used.

Bit 3: infrared sensor setting

This bit is set to ON if a sensor is not


used.

This bit is set to OFF if a sensor is used.

This bit is set to ON if a sensor is used.

This bit is set to OFF if a sensor is not


used.

This bit is set to ON if a sensor is used.

This bit is set to OFF if a sensor is not


used.

Bit 4: door status sensor setting

SW_THE

Bit 1: temperature sensor


setting

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Silkscreen

SW_AE

SW_AV

SW12A,
SW12B,
SW24A,
SW24B

Function

Setting

Bit 2: humidity sensor setting

This bit is set to ON if a sensor is used.

This bit is set to OFF if a sensor is not


used.

Four bits for analog signal


sensor settings

Four bits for analog signal


sensor settings

Thirty-two bits for Boolean


signal input

Each bit corresponds to an analog sensor.


l

This bit is set to ON if a sensor is used.

This bit is set to OFF if a sensor is not


used.

Each bit corresponds to an analog sensor.


l

This bit is set to ON if a current-type


sensor is used.

This bit is set to OFF if a voltage-type


sensor is used.

Bits 1-8 of the DIP switch SW12A


correspond to input signals 1-8.

Bits 1-8 of the DIP switch SW12B


correspond to input signals 9-16.

Bits 1-8 of the DIP switch SW24A


correspond to input signals 17-24.

Bits 1-8 of the DIP switch SW24B


correspond to input signals 25-32.

When a bit is set to ON, it represents


high-level alarms.

When a bit is set to OFF, it represents


low-level alarms or is not used.

2.4 Communication Ports on the EMUA


The EMUA provides the RS485 and RS232 ports for the communication between the EMUA
and the BTS/NodeB. Specifically, the EMUA4832 provides an independent commissioning
port.
2.4.1 RS485 Serial Port
This describes the RS485 serial port on the EMUA. The RS485 serial port supports two ports
(active/standby mode) for the communication between the EMUA and the BTS/NodeB. The
RS485 serial port is suitable for a dedicated serial port that has a DB-9 male connector.
2.4.2 RS232 Serial Port
This describes the RS232 serial port on the EMUA. An RS232 serial port is an RJ-45 socket and
suitable for a dedicated serial port cable that has an RJ-45 plug.
2.4.3 Commissioning Serial Port
This describes the commission serial port of the EMUA4832. Of all the EMUA models, only
the EMUA4832 provides a commissioning serial port. The commissioning serial port is used
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-9

EMUA
User Guide

2 Overview of the EMUA

only for commissioning during the manufacture of the EMUA4832. When the EMUA works
properly, this port is not used.

2.4.1 RS485 Serial Port


This describes the RS485 serial port on the EMUA. The RS485 serial port supports two ports
(active/standby mode) for the communication between the EMUA and the BTS/NodeB. The
RS485 serial port is suitable for a dedicated serial port that has a DB-9 male connector.
For the position of the RS485 serial port on the EMUA, see 2.2 Exterior of the EMUA.
Figure 2-9 shows the pins of the RS485 serial port socket.
Figure 2-9 Pins of the RS485 serial port socket

Table 2-3 lists the meanings of the pins of the RS485 serial port socket.
Table 2-3 Meanings of the pins of the RS485 serial port socket

2-10

Pin

Meaning

NULL

RX1+: positive reception terminal of serial


port 1

TX1+: positive transmission terminal of


serial port 1

RX2+: positive reception terminal of serial


port 2

TX2+: positive transmission terminal of


serial port 2

RX1-: negative reception terminal of serial


port 1

TX1-: negative transmission terminal of


serial port 1

RX2-: negative reception terminal of serial


port 2

TX2-: negative transmission terminal of


serial port 2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA


NOTE

The signals shown in this table are defined in terms of transmission and reception by the EMUA.

When the TXD+ pin is connected to the RXD+ pin and the TXD- pin is connected to the RXD- pin ,
the RS485 serial port can be used for two-wire connection.

The EMUA works properly even if only one RS485 serial port is connected. It is recommended that
you use two RS-485 serial ports in active/standby mode. In this case, set serial port 1 to the active port.

2.4.2 RS232 Serial Port


This describes the RS232 serial port on the EMUA. An RS232 serial port is an RJ-45 socket and
suitable for a dedicated serial port cable that has an RJ-45 plug.
For the position of the RS232 serial port on the EMUA, see 2.2 Exterior of the EMUA.
Figure 2-10 shows the pins of the RS232 serial port socket.
Figure 2-10 Pins of the RS232 serial port socket

Table 2-4 lists the meanings of the pins of the RS232 serial port socket.
Table 2-4 Meanings of the pins of the RS232 serial port socket
PIN

Meaning

NULL

NULL

TX: transmit terminal

GND: signal grounding terminal

GND: signal grounding terminal

RX: receive terminal

NULL

NULL

NOTE

Issue 10 (2010-03-30)

The signals shown in this table are defined in terms of transmission and reception by the EMUA.

The RS232 serial port is a standby commissioning port. When the EMUA works properly, this port is
not used.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-11

EMUA
User Guide

2 Overview of the EMUA

2.4.3 Commissioning Serial Port


This describes the commission serial port of the EMUA4832. Of all the EMUA models, only
the EMUA4832 provides a commissioning serial port. The commissioning serial port is used
only for commissioning during the manufacture of the EMUA4832. When the EMUA works
properly, this port is not used.

CAUTION
Do not connect the power supply cable to this port. Otherwise, the boards inside the EMUA4832
may get damaged.
For the position of the commissioning serial port on the EMUA4832, see 2.2 Exterior of the
EMUA.
Figure 2-11 shows the pins of the commissioning serial port socket.
Figure 2-11 Pins of the commissioning serial port socket

Table 2-5 lists the meanings of the pins of the commissioning serial port socket.
Table 2-5 Meanings of the pins of the commissioning serial port socket
Silkscreen

Meaning

Connection Mode

TX+

Positive transmit terminal

Connected to the positive receive terminal


on the BTS/NodeB side

TX-

Negative transmit terminal

Connected to the negative receive


terminal on the BTS/NodeB side

RX+

Positive receive terminal

Connected to the positive transmit


terminal on the BTS/NodeB side

RX-

Negative receive terminal

Connected to the negative transmit


terminal on the BTS/NodeB side

2.5 Monitoring Ports of the EMUA


The EMUA provides monitoring ports for the humidity/temperature sensor, smoke sensor, water
sensor, infrared sensor, and door status sensor. In addition, the EMUA provides monitoring ports
2-12

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

for the Boolean signal sensor, analog signal sensor, and output control sensor, which are extended
sensors.
2.5.1 Monitoring Port for the Water Sensor
This describes the monitoring port for the water sensor. This port is a voltage-type Boolean
signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
2.5.2 Monitoring Port for the Smoke Sensor
This describes the monitoring port for the smoke sensor. This port is a current-type Boolean
signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
2.5.3 Monitoring Port for the Infrared Sensor
This describes the monitoring port for the infrared sensor. This port is a voltage-type Boolean
signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
2.5.4 Monitoring Port for the Door Status Sensor
This describes the monitoring port for the door status sensor. This port is a dry contact point
Boolean signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
2.5.5 Monitoring Port for the Humidity/Temperature Sensor
This describes the monitoring port for the humidity/temperature sensor. This port is a currenttype analog signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12
AWG).
2.5.6 Monitoring Port for Boolean Signals
This describes the monitoring port for Boolean signals. The EMUA supports 32 monitoring ports
for Boolean signals, and the monitoring port for Boolean signals is suitable for a bare terminal
of a cable (24 AWG - 12 AWG).
2.5.7 Monitoring Port for Analog Signals
This describes the monitoring port for analog signals. This port is a voltage-type analog signal
monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
2.5.8 Monitoring Port for the Relay Node Boolean Signals
This describes the monitoring port for the Boolean Sensor. The EMUA supports six monitoring
ports for relay node Boolean signals, and the monitoring port for relay node Boolean signals is
suitable for a bare terminal of a cable (24 AWG - 12 AWG).

2.5.1 Monitoring Port for the Water Sensor


This describes the monitoring port for the water sensor. This port is a voltage-type Boolean
signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
For the position of the monitoring port for the water sensor, see 2.2 Exterior of the EMUA.
Figure 2-12 shows this port.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-13

EMUA
User Guide

2 Overview of the EMUA

Figure 2-12 Monitoring port for the water sensor

NOTE

The EMUA supports +24V/+12 V DC water sensors.

Table 2-6 lists the meanings of the terminals of the monitoring port for the water sensor.
Table 2-6 Meanings of the terminals of the monitoring port for the water sensor
Silkscreen

Meaning

24VW

+24 V DC power output

12VW

+12 V DC power output

Water

Input of water damage monitoring signals

GND

Signal grounding terminal

NOTE

You can set bit 1 of the DIP switch SW_BKE to choose whether to use the monitoring port for the water
sensor. For details, see 2.3 Internal Structure of the EMUA.

2.5.2 Monitoring Port for the Smoke Sensor


This describes the monitoring port for the smoke sensor. This port is a current-type Boolean
signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
For the position of the monitoring port for the smoke sensor, see 2.2 Exterior of the EMUA.
Figure 2-13 shows this port.

2-14

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Figure 2-13 Monitoring port for the smoke sensor

NOTE

The EMUA supports 24 V DC smoke sensors.

Table 2-7 lists the meanings of the terminals of the monitoring port for the smoke sensor.
Table 2-7 Meanings of the terminals of the monitoring port for the smoke sensor
Silkscreen

Meaning

24VS

24 V DC power output

Smoke

Input of smoke monitoring signals

NOTE

You can set bit 2 of the DIP switch SW_BKE to choose whether to use the monitoring port for the smoke
sensor. For details, see 2.3 Internal Structure of the EMUA.

2.5.3 Monitoring Port for the Infrared Sensor


This describes the monitoring port for the infrared sensor. This port is a voltage-type Boolean
signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
For the position of the monitoring port for the infrared sensor, see 2.2 Exterior of the EMUA.
Figure 2-14 shows this port.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-15

EMUA
User Guide

2 Overview of the EMUA

Figure 2-14 Monitoring port for the infrared sensor

NOTE

The EMUA supports 24V/12 V DC infrared sensors.

Table 2-8 lists the meanings of the terminals of the monitoring port for the infrared sensor.
Table 2-8 Meanings of the terminals of the monitoring port for the infrared sensor
Silkscreen

Meaning

24VI

24 V DC power output

12VI

12 V DC power output

OPTI

Input of infrared monitoring signals

GND

Signal grounding terminal

NOTE

You can set bit 3 of the DIP switch SW_BKE to choose whether to use the monitoring port for the infrared
sensor. For details, see 2.3 Internal Structure of the EMUA.

2.5.4 Monitoring Port for the Door Status Sensor


This describes the monitoring port for the door status sensor. This port is a dry contact point
Boolean signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
For the position of the monitoring port for the door status sensor, see 2.2 Exterior of the
EMUA. Figure 2-15 shows this port.

2-16

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Figure 2-15 Monitoring port for the door status sensor

Table 2-9 lists the meanings of the terminals of the monitoring port for the door status sensor.
Table 2-9 Meanings of the terminals of the monitoring port for the door status sensor
Silkscreen

Meaning

12VG

Positive input terminal for door status


monitoring signals

GATE

Negative input terminal for door status


monitoring signals

NOTE

You can set bit 4 of the DIP switch SW_BKE to choose whether to use the monitoring port for the door
status sensor. For details, see 2.3 Internal Structure of the EMUA.

2.5.5 Monitoring Port for the Humidity/Temperature Sensor


This describes the monitoring port for the humidity/temperature sensor. This port is a currenttype analog signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12
AWG).
For the position of the monitoring port for the humidity/temperature sensor, see 2.2 Exterior of
the EMUA. Figure 2-16 shows this port.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-17

EMUA
User Guide

2 Overview of the EMUA

Figure 2-16 Monitoring port for the humidity/temperature sensor

NOTE

The EMUA supports 24 V DC humidity/temperature sensors.

Table 2-10 lists the meanings of the terminals of the monitoring port for the humidity/
temperature sensor.
Table 2-10 Meanings of the terminals of the monitoring port for the humidity/temperature sensor
Silkscreen

Meaning

24VT

24 V DC power output

TEMP

Temperature monitoring signal input

24VH

24 V DC power output

HUMI

Humidity monitoring signal input

NOTE

You can set the DIP switch SW_BKE to choose whether to use the monitoring port for the humidity/
temperature sensor. For details, see 2.3 Internal Structure of the EMUA.

2.5.6 Monitoring Port for Boolean Signals


This describes the monitoring port for Boolean signals. The EMUA supports 32 monitoring ports
for Boolean signals, and the monitoring port for Boolean signals is suitable for a bare terminal
of a cable (24 AWG - 12 AWG).
For the position of the monitoring port for Boolean signals, see 2.2 Exterior of the EMUA.
Figure 2-17 shows this port.

2-18

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Figure 2-17 Monitoring port for Boolean signals


S29+ S29- S30+ S30- S31+ S31- S32+ S32- S21+ S21- S22+ S22- S23+ S23- S24+ S24- S13+ S13- S14+ S14- S15+ S15- S16+ S16- S5+ S5- S6+ S6- S7+ S7

S8+ S8-

S25+ S25- S26+ S26- S27+ S27- S28+ S28- S17+ S17- S18+ S18- S19+ S19- S20+S20- S9+ S9- S10+ S10- S11+ S11- S12+ S12- S1+ S1- S2+ S2- S3+ S3- S4+ S4-

NOTE

The common types of Boolean signals are the dry contact point type, OC type, voltage type, and current
type.

All the monitoring ports for Boolean signals support Boolean signals of the dry contact point type and
OC type.

Ports S13 - S16 and S29 - S32 support Boolean signals of the voltage type.

Table 2-11 lists the valid values of Boolean signals of the voltage type.
Table 2-11 Valid values of Boolean signals of the voltage type
Value Range of the Input Voltage
Signal (x)

Definition

x 3 V DC

Low level

x 5 V DC

High level

3 V DC < x < 5 V DC

Unspecified

Table 2-12 lists the meanings of the terminals of the monitoring port for Boolean signals.
Table 2-12 Meanings of the terminals of the monitoring port for Boolean signals
Silkscreen

Meaning

Si+ (i ranges from 1 to 32)

Positive Boolean input of port i

Si- (i ranges from 1 to 32)

Negative Boolean input of port i

NOTE

You can set the DIP switches SW12A, SW12B, SW24A, and SW24B to choose whether to use the
monitoring port for Boolean signals. For details, see 2.3 Internal Structure of the EMUA.

2.5.7 Monitoring Port for Analog Signals


This describes the monitoring port for analog signals. This port is a voltage-type analog signal
monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG).
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-19

EMUA
User Guide

2 Overview of the EMUA

Description
For the position of the monitoring port for analog signals, see 2.2 Exterior of the EMUA.
Figure 2-18 shows this port.
Figure 2-18 Monitoring port for analog signals

Table 2-13 lists the meanings of the terminals of the monitoring port for analog signals.
Table 2-13 Meanings of the terminals of the monitoring port for analog signals
Silkscreen

Meaning

24Vi (i ranges from 1 to 4)

24 V DC power output of port i

12Vi (i ranges from 1 to 4)

12 V DC power output of port i

ANAi (i ranges from 1 to 4)

Analog input of port i

GNDi (i ranges from 1 to 4)

Signal grounding of port i

NOTE

You can set the DIP switches SW_AE and SW_AV to choose whether to use the monitoring port for Analog
signals. For details, see 2.3 Internal Structure of the EMUA.

Cable Connection
Analog Sensor of the Voltage Type
The voltage-type analog sensor has two power input terminals (marked "POWER+" and
"POWER-") and one analog signal output terminal (marked "Sout"), as shown in Figure 2-19.

2-20

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

Figure 2-19 Connecting the analog sensor of the voltage type


24V i
Analog
signal
sensor

POWER +

12V i

Sout

ANA i

POWER -

GND

i = 1, 2, 3, 4

Analog Sensor of the Current Type


The analog sensor of the current type has two power input ends (marked "POWER+" and
"POWER-"), as shown in Figure 2-20.
Figure 2-20 Connecting the analog sensor of the current type
24V i
Analog
signal
sensor

POWER +
POWER -

12V i
ANA i

i = 1, 2, 3, 4

2.5.8 Monitoring Port for the Relay Node Boolean Signals


This describes the monitoring port for the Boolean Sensor. The EMUA supports six monitoring
ports for relay node Boolean signals, and the monitoring port for relay node Boolean signals is
suitable for a bare terminal of a cable (24 AWG - 12 AWG).

Description
For the position of the monitoring port for relay node Boolean signals, see 2.2 Exterior of the
EMUA. Figure 2-21 shows this port.
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-21

EMUA
User Guide

2 Overview of the EMUA

Figure 2-21 Monitoring Port for relay node Boolean signals

Table 2-14 lists the meanings of the terminals of the monitoring port for relay node Boolean
signals.
Table 2-14 Meanings of the terminals of the monitoring port for relay node Boolean signals
Silkscreen

Meaning

REi+ (i ranges from 1 to 6)

Positive relay node output port i

REi- (i ranges from 1 to 6)

Negative relay node output port i

Cable Connection
Figure 2-22 shows the cable connection of the relay node.
Figure 2-22 Cable connection of the relay node
CTR_OUT+

REi +

CTR_OUT-

REi -

i=1-6

2-22

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

2 Overview of the EMUA

The relay node has two pins. The settings of the two pins are as follows:
l

If relay node output is enabled, the two pins are connected.

If relay node output is disabled, the two pins are disconnected.

If the relay needs to output 60 V DC or higher, use a 24 V intermediate relay to convert the
output voltage.

Alarm Association
Alarm association is a process in which the corresponding relay switch is automatically turned
on after the EMUA detects an environmental alarm. Table 2-15 describes the alarms
corresponding to the relay switch.
Table 2-15 Alarms corresponding to the relay switch
Relay
Switch (i = 1
to 6)

Alarm

Overtemperature alarm

Undertemperature alarm

High humidity alarm

Low humidity alarm

Water damage alarm

Smoke alarm

NOTE

When no alarm is generated, the relay switch is turned off.

When an alarm is generated, the relay switch is turned on.

If an EMUA must support alarm association, the DIP switches must be set on site.

2.6 Technical Specifications of the EMUA


This describes the technical specifications of the EMUA.

Technical Specifications of the EMUA


Table 2-16 lists the technical specifications of the EMUA.
Table 2-16 Technical specifications of the EMUA

Issue 10 (2010-03-30)

Item

Measured Object

Specification

System voltage

Measurement range

0 V DC to 100 V DC

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-23

EMUA
User Guide

2 Overview of the EMUA

Item

Temperature

Humidity

Boolean signal

Analog signal

Relay output control

Communication rate

Measured Object

Specification

Measurement precision

1 V

Measurement range

-20oC [-4oF] to 80oC [176oF]

Measurement precision

2oC

Measurement range

0% RH to 100% RH

Measurement precision

5%

Measurement range

Smoke, door status, water damage, and


infrared signal

Alarm response time

< 10s

Measurement range

4 mA to 20 mA or 0 V to 5 V

Measurement precision

1%

Control response time

< 1s

Dry contact output


capacity

Withstood voltage: 110 V DC, 125 V


AC; maximum load current: 1 A (30 V
DC)

RS232, RS485

9600 bit/s

Performance Specifications for the EMUA


Table 2-17 lists the performance specifications for the EMUA.
Table 2-17 Performance specifications of the EMUA
Item

Specification

Storage temperature

-40oC [-40oF] to +70oC [158oF] (no condensing)

Working temperature

-5oC [23oF] to 55oC [131oF]

Storage humidity

5%RH to 95%RH

Working humidity

10%RH to 90%RH

Working voltage type

DC

Rated working voltage

24 V for the EMUA2416 and EMUA2432


-48 V for the EMUA4832

Rated working current

0.4 A for the EMUA2416 and EMUA2432


0.2 A for the EMUA4832

Dimensions

2-24

483 mm [19.02 in.] x 284 mm [11.18 in.] x 44 mm [1.73


in.]
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

Issue 10 (2010-03-30)

2 Overview of the EMUA

Item

Specification

Weight

Approximately 3.5 kg [7.72 lb]

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-25

EMUA
User Guide

3 Introduction to the Sensors

Introduction to the Sensors

About This Chapter


The sensors provided by Huawei can be used directly. The sensors not provided by Huawei can
be used only if their specifications meet the requirements.
3.1 Water Sensor
This describes the water sensor. The model of the configured water sensor is YW517B. This
water sensor is of the current type.
3.2 Smoke Sensor
This describes the smoke sensor. The model of the configured smoke sensor is JTY-GD-01K.
This smoke sensor features a photoelectric sensing design and is of the voltage type.
3.3 Infrared Sensor
This describes the infrared sensor. The model of the configured infrared sensor is MC-760T.
3.4 Door Status Sensor
This describes the doors status sensor. The model of the configured door status sensor is
AGX105F (outdoor) or HO-03A (indoor).
3.5 Humidity/Temperature Sensor
This describes the humidity/temperature sensor. The model of the configured humidity/
temperature sensor is WS302A1T4.
3.6 Self-Selected Sensors
This describes the requirements for the specifications of the self-selected sensors.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-1

EMUA
User Guide

3 Introduction to the Sensors

3.1 Water Sensor


This describes the water sensor. The model of the configured water sensor is YW517B. This
water sensor is of the current type.

Exterior of the Water Sensor


Figure 3-1 shows the exterior of the YW517B water sensor.
Figure 3-1 Exterior of the YW517B water sensor

NOTE

The cable provided along with the YW517B water sensor is 2.7 m [8.86 ft] long.

Technical Specifications of the Water Sensor


Table 3-1 lists the technical specifications of the YW517B water sensor.
Table 3-1 Technical specifications of the YW517B water sensor
Item

Specification

Power supply voltage

12 V DC 5%

Current output when liquid is not detected

< 80 uA

Current output when liquid is detected

10 mA to 15 mA

Output signal type

Current

Working temperature

-20oC [-4oF] to +70oC [158oF]

3.2 Smoke Sensor


This describes the smoke sensor. The model of the configured smoke sensor is JTY-GD-01K.
This smoke sensor features a photoelectric sensing design and is of the voltage type.

Exterior of the Smoke Sensor


Figure 3-2 shows the exterior of the JTY-GD-01K smoke sensor.
3-2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

3 Introduction to the Sensors

Figure 3-2 Exterior of the JTY-GD-01K smoke sensor

NOTE

The cable distributed for the JTY-GD-01K smoke sensor is 10 m [32.81 ft] long.

Working Principle of the Smoke Sensor


When the smoke sensor is in the alarm state, the red indictor is on. After the system is powered
on immediately after being powered off or after the system is reset, the indicator shifts to the
ON state, indicating that the smoke sensor returns to the normal state. Table 3-2 describes the
indicator on the smoke sensor.
Table 3-2 Indicator on the smoke sensor
Indicator

Meaning

Status

Red indicator

Alarm

On

No alarm

Blinking

Technical Specifications of the Smoke Sensor


Table 3-3 lists the technical specifications of the JTY-GD-01K smoke sensor.
Table 3-3 Technical specifications of the JTY-GD-01K smoke sensor

Issue 10 (2010-03-30)

Item

Specification

Power supply voltage

24 V DC 5%

Working current

< 50 uA

Power-on time

30s

Power-on current

< 150 uA

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-3

EMUA
User Guide

3 Introduction to the Sensors

Item

Specification

Working temperature

-10oC [14oF] to +55oC [131oF]

Working humidity

95% (40oC [104oF] 2oC [35.6oF], no


condensing)

Output type

Dry contact point

3.3 Infrared Sensor


This describes the infrared sensor. The model of the configured infrared sensor is MC-760T.

Exterior of the Infrared Sensor


Figure 3-3 shows the exterior of the MC-760T infrared sensor.
Figure 3-3 Exterior of the MC-760T infrared sensor

NOTE

The cable provided along with the MC-760T infrared sensor is 10 m [32.81 ft] long.

Working Principle of the Infrared Sensor


The MC-760T infrared sensor is based on the pyroelectric effect and performs dual monitoring
(microwave and infrared).
The sensitivity of the infrared sensor can be adjusted through its DIP switches. For details, refer
to the instructions of the infrared sensor. The infrared sensor enters the monitoring state three
minutes after it is powered on. It generates an alarm whenever someone moves in the equipment
room.

Technical Specifications of the Infrared Sensor


Table 3-4 lists the technical specifications of the MC-760T infrared sensor.
3-4

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

3 Introduction to the Sensors

Table 3-4 Technical specifications of the MC-760T infrared sensor


Item

Specification

Power supply voltage

12 V DC 5%

Working current

30 mA

Monitoring range

Front: 18 m [59.06 ft]


45oC range: 25 m [82.02 ft]

Output type

Dry contact point

Working temperature

-10oC [14oF] to 55oC [131oF]

3.4 Door Status Sensor


This describes the doors status sensor. The model of the configured door status sensor is
AGX105F (outdoor) or HO-03A (indoor).

Exterior of the Door Status Sensor


Figure 3-4 shows the exterior of the AGX105F door status sensor.
Figure 3-4 Exterior of the AGX105F door status sensor

Surface
A

Side

Surface B

Bottom
sectional view

Figure 3-5 shows the exterior of the HO-03A door status sensor.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-5

EMUA
User Guide

3 Introduction to the Sensors

Figure 3-5 Exterior of the HO-03A door status sensor

NOTE

The cable provided along with the HO-03A door status sensor is 10 m [32.81 ft] long.

Working Principle of the Door Status Sensor


When the button at the top of the AGX105F door status sensor is pressed, the spring is
compressed, and the reed touches pins A and B, as shown in Figure 3-6.
Figure 3-6 Working principle of the AGX105F door status sensor

The HO-03A door status sensor consists of a dry finger pipe and a magnetic ferrite. The dry
finger pipe consists of two soft magnetic metal fingers that are close to each other. When the
magnetic ferrite is close to the dry finger pipe, the fingers are magnetized and attracted to each
other. When the magnetic field no longer covers the fingers, the fingers spring apart.

Technical Specifications of the Door Status Sensor


Table 3-5 lists the technical specifications of the AGX105F door status sensor.
3-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

3 Introduction to the Sensors

Table 3-5 Technical specifications of the AGX105F door status sensor


Item

Specification

Working voltage

250 V AC

Rated current

10.0 A

Pin length

10.60 mm [0.42 in.]

Table 3-6 lists the technical specifications of the HO-03A door status sensor.
Table 3-6 Technical specifications of the HO-03A door status sensor
Item

Specification

Effect distance

25 mm [0.98 in.]

Contact capacity

Maximum voltage: 150 V DC

Maximum current: 0.5 A

Impedance

0.3 ohm

Power

10 W

Output type

Dry contact point

3.5 Humidity/Temperature Sensor


This describes the humidity/temperature sensor. The model of the configured humidity/
temperature sensor is WS302A1T4.

Exterior of the Humidity/Temperature Sensor


Figure 3-7 shows the exterior of the WS302A1T4 humidity/temperature sensor.
Figure 3-7 Exterior of the WS302A1T4 humidity/temperature sensor

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-7

EMUA
User Guide

3 Introduction to the Sensors

NOTE

The cable provided along with the WS302A1T4 humidity/temperature sensor is 3 m [9.84 ft] long.

Working Principle of the Humidity/Temperature Sensor


The WS302A1T4 humidity/temperature sensor uses a Pt100 thermistor as the temperature
sensing component and an S108 macromolecular humidity-sensitive capacitor as the humidity
sensing component. The WS302A1T4 humidity/temperature sensor uses the SMT
craftsmanship, and it is installed on the wall.

Technical Specifications of the Humidity/Temperature Sensor


Table 3-7 lists the technical specifications of the WS302A1T4 humidity/temperature sensor.
Table 3-7 Technical specifications of the WS302A1T4 humidity/temperature sensor
Item

Specification
Temperature Sensor

Humidity Sensor

Measurement
range

-20oC [-4oF] to +80oC [176oF]

0% RH to 100% RH

Precision

0.3oC [32.54oF] (ambient


temperature: 25oC [77oF])

2% RH (ambient temperature:
25oC [77oF], ambient humidity:
30% RH to 80% RH)

Power supply
voltage

12 V DC to 24 V DC

Signal output

4 mA to 20 mA (in linear response to the measurement range)

Sample
resistance

500 ohms

Sensitive
components

Pt100 thermistor

Working
temperature

-20oC [-4oF] to +80oC [176oF]

Storage
temperature

-40oC [-40oF] to +60oC [+140oF] (no condensing)

Covering
material

ABS engineering plastic

S108 macromolecular humiditysensitive capacitor

3.6 Self-Selected Sensors


This describes the requirements for the specifications of the self-selected sensors.
3-8

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

3 Introduction to the Sensors

Requirements for the specifications of the self-selected sensors


l

Working voltage: 24 V

Type of output temperature signals: current type (4 mA to 20 mA)

Type of output humidity signals: current type (4 mA to 20 mA)

Temperature monitoring range: -20oC [-4oF] to +80oC [176oF]

Humidity monitoring range: 0%RH to 100%RH

The relations between the humidity and output current must meet the requirements shown in
Figure 3-8.
Figure 3-8 Relations between the humidity and output current
100% RH

0% RH

4 mA

20 mA

The relations between the temperature and output current must meet the requirements shown in
Figure 3-9.
Figure 3-9 Relations between the temperature and output current
80

4 mA

20 mA

-20

Requirements for the Specifications of Self-Selected Water Sensors


Working voltage: 24 V or 12 V
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-9

EMUA
User Guide

3 Introduction to the Sensors

The output signals must meet the following requirements:


l

Current type

When liquid is not detected, the output current should be less than 200 uA.

When liquid is detected, the output current should be greater than 1 mA.

Voltage type

When liquid is not detected, the output voltage should be less than 3.3 V.

When liquid is detected, the output voltage should be greater than 5 V.

Dry contact point type

When liquid is not detected, the sensor should be disconnected.

When liquid is detected, the sensor should be connected.

Requirements for the Specifications of Self-Selected Door Status Sensors


Working voltage: 12 V
The output signals must meet the following requirements:
l

Current type

When the door is closed, the output current should be less than 200 uA.

When the door is open, the output current should be greater than 1 mA.

Voltage type

When the door is closed, the output voltage should be less than 3.3 V.

When the door is open, the output voltage should be greater than 5 V.

Dry contact point type

When the door is closed, the sensor should be connected.

When the door is open, the sensor should be disconnected.

Requirements for the Specifications of Self-Selected Smoke Sensors


Working voltage: 24 V
The output signals must meet the following requirements:
l

Current type

When smoke is not detected, the output current should be less than 200 uA.

When smoke is detected, the output current should be greater than 3 mA.

Voltage type

When smoke is not detected, the output voltage should be less than 3.3 V.

When smoke is detected, the output voltage should be greater than 5 V.

Dry contact point type

When smoke is not detected, the sensor should be disconnected.

When smoke is detected, the sensor should be connected.

Requirements for the Specifications of Self-Selected Infrared Status Sensors


Working voltage: 24 V or 12 V
3-10

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

3 Introduction to the Sensors

The output signals must meet the following requirements:


l

Issue 10 (2010-03-30)

Current type

When moving objects are not detected, the output current should be less than 200 uA.

When moving objects are detected, the output current should be greater than 1 mA.

Voltage type

When moving objects are not detected, the output voltage should be less than 3.3 V.

When moving objects are detected, the output voltage should be greater than 5 V.

Dry contact point type

When moving objects are detected, the sensor should be disconnected.

When moving objects are detected, the sensor should be connected.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-11

EMUA
User Guide

4 Installing the EMUA

Installing the EMUA

This describes how to install the EMUA. The EMUA can be installed in different ways.

Prerequisite
The following items are ready:
l

Screwdriver

EMUA

Context
The EMUA can be installed in the reserved 19-inch space inside any 19-inch cabinet or rack
whose depth exceeds 300 mm [11.81 in.].

Procedure
l

Issue 10 (2010-03-30)

Install the EMUA in the reserved 19-inch space inside the cabinet, as shown in Figure
4-1.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-1

EMUA
User Guide

4 Installing the EMUA

Figure 4-1 Installing the EMUA inside the cabinet

Install the EMUA in the reserved 19-inch space inside the rack, as shown in Figure 4-2
Figure 4-2 Installing the EMUA inside the rack

----End

4-2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

5 Installing the Sensors

Installing the Sensors

About This Chapter


The installation methods of the sensors provided by Huawei are described here. For the sensors
not provided by Huawei, see their respective instructions during installation.

Context
By default, the outdoor cabinet is configured with some sensors. Therefore, only the methods
of installing the sensors indoors are described here.
5.1 Installing the Water Sensor
This describes how to install the water sensor.
5.2 Installing the Smoke Sensor
This describes how to install the smoke sensor.
5.3 Installing the Infrared Sensor
This describes how to install the infrared sensor.
5.4 Installing the Door Status Sensor
This describes how to install the door status sensor.
5.5 Installing the Humidity/Temperature Sensor
This describes how to install the humidity/temperature sensor.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-1

EMUA
User Guide

5 Installing the Sensors

5.1 Installing the Water Sensor


This describes how to install the water sensor.

Context

CAUTION
l

The sensor probe must be protected from liquid chloride.

The monitored plane must not be reflective.

The water sensor can be connected only to the terminals marked "Water", "12VW", and
"GND".

Procedure
Step 1 Erect the water sensor in the selected installation position, as shown in Figure 5-1.
Figure 5-1 Installing the water sensor

Placing
surface

Step 2 Install the leading cable of the sensor.


5-2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

5 Installing the Sensors

Table 5-1 describes the 3-core leading cable of the water sensor, and Figure 5-2 shows the
connection of the cable.
Table 5-1 3-core leading cable of the water sensor
Color

Core Wire

Function

Red

Core wire for the


external power
supply

Connected to the terminal marked "12VW"

White

Grounding core
wire

Connected to the terminal marked "GND"

Blue

Signal core wire

Connected to the terminal marked "Water"

Figure 5-2 Connecting the water sensor

(1) GND (white)

(2) Water (blue)

(3) 12VW (red)

----End

5.2 Installing the Smoke Sensor


This describes how to install the smoke sensor.
Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-3

EMUA
User Guide

5 Installing the Sensors

Context
The requirements for the installation of the smoke sensor are as follows:
l

If the smoke sensor is to be installed in the center of the ceiling, ensure that:

There is no obstacle within a 0.5 m [1.64 ft] radius of the smoke sensor.

The horizontal distance between the smoke sensor and the blast vent of the airconditioner is greater than 1.5 m [4.92 ft].

The horizontal distance between the smoke sensor and the air vent in the ceiling is
greater than 0.5 m [1.64 ft].

The horizontal distance between the smoke sensor and the air vent of the air-conditioner
is greater than 1.5 m [4.92 ft].

The smoke sensor is suitable for detecting fires that have smolder during the initial stage
and emit large amounts of smoke. Do not install the smoke sensor at locations where:

Black smoke is emitted during fires.

No smoke or little smoke is edited during fires.

The relative humidity is constantly greater than 95%.

The airflow rate is greater than 5 m/s.

Large amounts of dust or water smoke is suspended.

Corrosive gas may be emitted.

Smoke is suspended under normal circumstances.

Organic substances, such as alcohol, ether, and ketone are generated.

Before powering on the smoke sensor, ensure that the smoke sensor is correctly connected.
Thirty seconds after the smoke sensor is powered on, the red indicator will start to blink
once every 9 to 15 seconds.

Dust easily accumulates on the smoke sensor. Therefore, clear the dust periodically to avoid
false alarms.

To protect the smoke sensor from dirt, do not remove the dust cover before using the sensor.

CAUTION
l

The smoke sensor cannot work without the power supply. Therefore, the smoke sensor does
not work if the power supply is interrupted.

To avoid damage to the smoke sensor, do not directly use +24 V DC input voltage for the
smoke sensor.
NOTE

The smoke sensor can be connected only to the terminals marked "Smoke&24VS".

The smoke sensor generates alarms when there is smoke or fire. You have to run an associated command
to clear the alarms.

Procedure
Step 1 Install the smoke sensor in the selected position.
5-4

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

5 Installing the Sensors

Use a PVC terminal to bridge the seam between the cable duct and the base.
Figure 5-3 shows the installation of the smoke sensor.
Figure 5-3 Installation of the smoke sensor
65 mm
7

2
4
1

(1) Cable duct

(2) PVC terminal

(3) Alarm indicator

(4) Base

(5) Tapping screw

(6) Plastic expansion tube

(7) Percussion drill hole

Step 2 Connect the smoke sensor.


Open the base of the smoke sensor. On the base, there are four wiring bars labeled 1 - 4, a plus
sign, and a minus sign, as shown in Figure 5-4.
1.

Connect wiring bar 3 to the terminal marked "24VS".

2.

Connect wiring bar 1 to the terminal marked "Smoke".

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-5

EMUA
User Guide

5 Installing the Sensors

Figure 5-4 Connecting the smoke sensor

----End

5.3 Installing the Infrared Sensor


This describes how to install the infrared sensor.

Context
The requirements for the installation of the infrared sensor are as follows:
l

The infrared sensor should not be exposed to sunlight or other strong light.

The infrared sensor should not directly face heat sources such as air-conditioners or
caliducts.

The infrared sensor should directly face positions prone to unauthorized entry.

The infrared sensor should not be installed on the wall beside the door.

The monitoring range should be clear of obstacles so that the infrared sensor can be directly
seen in the monitoring range.

The Fresnel lens of the infrared sensor should be kept clean.

The pyroelectric components of the infrared sensor should not be touched.


NOTE

The infrared sensor can be connected only to the terminals marked "OPTI&12VI&GND".

5-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

5 Installing the Sensors

Procedure
Step 1 Remove the installation sheet of the infrared sensor, and then mark on the wall the positions of
the two installation holes of the installation sheet.
Step 2 Use the percussion drill to drill holes according to the marks.
Step 3 Insert the expansion tubes into the installation holes.
Step 4 Use the tapping screws to fix the installation sheet to the wall.
Step 5 Fix the infrared sensor to the installation sheet.
Step 6 Connect the infrared sensor, as shown in Figure 5-5.
Figure 5-5 Connecting the infrared sensor

----End

5.4 Installing the Door Status Sensor


This describes how to install the door status sensor.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-7

EMUA
User Guide

5 Installing the Sensors

Context
NOTE

The distance between the two fingers should be less than 5 mm [0.20 in.] when the door is closed.

The door status sensor can be connected only to the terminals marked "GATE&12VG".

The alarms reported by the door status sensor can be cleared only through human intervention.

Procedure
Step 1 Mark the installation position of the door status sensor.
Step 2 Use the percussion drill to drill holes according to the marks.
Step 3 Install and fasten the door status sensor.
Step 4 Connect the door status sensor, as shown in Figure 5-6 and Figure 5-7.
Figure 5-6 Connecting the AGX105F door status sensor

Figure 5-7 Connecting the HO-03A door status sensor

5-8

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

5 Installing the Sensors

----End

5.5 Installing the Humidity/Temperature Sensor


This describes how to install the humidity/temperature sensor.

Context
The requirements for the installation of the humidity/temperature sensor are as follows:
l

Generally, the humidity/temperature sensor should be installed on a wall and about 1.5 m
[4.92 ft] above the ground.

Around the humidity/temperature sensor, ventilation should be good, and the airflow rate
is 0.1 m/s to 1 m/s.
NOTE

The humidity/temperature sensor cannot be installed in a position with no or little airflow.

The humidity/temperature sensor cannot be installed in a position with too rapid airflow, for
example, the air vent in the ceiling or the blast vent of an air-conditioner.

Do not install the humidity/temperature sensor in a position where:

There is no air conditioning.

The relative humidity is constantly higher than 90%.

The temperature is constantly below -20oC [-4oF].

The wind of an air cooling machine or air heating machine can directly blows the
humidity/temperature sensor.

The air is polluted by substances such as sour gas and oily gas.

The humidity/temperature sensor should be kept away from the ends of the cabling trough.

The installation plane should be clean.

The humidity/temperature sensor should be powered off before the sensor is installed or
replaced.

Holes should not be drilled around the humidity/temperature sensor after the sensor is
installed. If you have to do so, take appropriate measures to protect the sensor from dust.

The humidity-sensitive components of the humidity/temperature sensor should not be


touched.

CAUTION
l

To avoid mechanical and electrostatic damage to the humidity/temperature sensor, be


cautious when moving the box cover and the circuit board and when connecting the wires.
When moving the circuit board, hold its edges and take care not to touch its components.
Place the circuit board in a clean position.

You need to calibrate the humidity/temperature sensor annually. Replace it if its precision is
too low.

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-9

EMUA
User Guide

5 Installing the Sensors


NOTE

The humidity/temperature sensor can be connected only to the terminals marked


"TEMP&24VT&HUMI&24VH".

Procedure
Step 1 Remove the backplane of the humidity/temperature sensor, and then mark on the wall the
positions of the three installation holes in the backplane.
Step 2 Use the percussion drill to drill holes according to the marks.
Step 3 Insert the plastic expansion tubes into the installation holes.
Step 4 Use the tapping screws to fix the backplane to the wall.
Step 5 Fix the humidity/temperature sensor to the backplane.
Step 6 Connect the humidity/temperature sensor, as shown in Figure 5-8.
Figure 5-8 Connecting the humidity/temperature sensor

----End

5-10

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 10 (2010-03-30)

EMUA
User Guide

6 Commissioning the EMUA

Commissioning the EMUA

This describes how to commission the EMUA.

Procedure
Step 1 Perform a power-on check for the EMUA.
1.

Check the DIP switch settings.


For the correct DIP switch settings, see 2.3 Internal Structure of the EMUA.

2.

Power on the EMUA.

3.

Check the status of the indicators.


After power-on, both the red and green indicators should blink for about 0.5 second. Then,
the red indicator should be off, and the green indicator should continue blinking.

Step 2 Check the communication between the EMUA and the BTS/NodeB.
1.

Ensure that the EMUA has passed the power-on check.

2.

On the Service Maintenance System of the BTS/NodeB, establish the communication


between the BTS/NodeB and the EMUA.

3.

Check the status of the indicators on the EMUA.


Check that the green indicator on the EMUA blinks once every two seconds.

Step 3 Check the running status of the EMUA.


1.

Ensure that the EMUA has passed the communication check.

2.

Read the data of the sensors and the voltage on the Service Maintenance System of the
BTS/NodeB.
Check that the data is correct.

----End

Issue 10 (2010-03-30)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

6-1

EMUA
User Guide

7 Handling Common Faults

Handling Common Faults

This describes the solutions to common faults in the EMUA.


Table 7-1 lists the solutions to common faults in the EMUA.
Table 7-1 Solutions to common faults in the EMUA
Symptom

Solution

The power indicator is OFF.

Check whether the power cable is inversely connected.


Check whether the protection tubes F1, F2, F3, and F4 are
burned out.

The EMUA fails to


communicate with the BTS/
NodeB.

Check whether the communication cables are intact.

The relay malfunctions.

Check whether the output cabling of the relay is correct.

Boolean value input fails.

Check whether the alarming states are correctly set.

Check whether the communication protocol is correctly


configured.

Check whether the cabling is correct.


The humidity/temperature
sensor generates an alarm at
normal temperatures.

Check whether the humidity/temperature sensor is


correctly connected.

The humidity/temperature
query results are invalid values.

Check whether the humidity/temperature sensor is


correctly connected.

Check whether the alarming threshold is correctly set.

Check whether the DIP switch SW_THE is correctly set.


Check whether the sensor fails, for example, by comparing
it with another sensor.
The water sensor generates a
false alarm.

Issue 10 (2010-03-30)

Check whether the water sensor is correctly connected.


Check whether the first bit of the DIP switch SW_BKE is
correctly set.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

7-1

EMUA
User Guide

7 Handling Common Faults

Symptom

Solution

The smoke sensor generates a


false alarm.

Check whether the smoke sensor is correctly connected.

The infrared sensor generates a


false alarm.

Check whether the infrared sensor is correctly connected.

The door status sensor generates


a false alarm.

Check whether the button on the door status sensor is


pressed into the correct position.

Check whether the second bit of the DIP switch SW_BKE


is correctly set.

Check whether the third bit of the DIP switch SW_BKE is


correctly set.

Check whether the door status sensor is correctly


connected.
Check whether the fourth bit of the DIP switch SW_BKE
is correctly set.
Analog value measurement
fails.

Check whether associated DIP switches are correctly set.

NOTE

When the EMUA2416 generates an alarm, check whether the factory settings of the DIP switches SW24A
and SW24B are changed. If they are changed, restore them to their original states (OFF).