PEAK Case without Palatana Generation (NER DM = 1722 MW, GEN = 1130 MW)

Line Flows (MW)


400 kV Silchar - Byrnihat

400 kV Silchar - Azara

220 kV BTPS - Agia

220 kV BTPS - Salakati D/C

220 kV Azara - Sarusajai D/C

220 kV Azara-Boko

220 kV Azara - Agia

BaseCase

-121

193

147x2

57x2

-54

-62

With 400/220 kV Azara

-71

-68

231

167x2

41x2

-72

-80

Tripping of 400kV Silchar - Byrnihat

-111

257

180x2

31x2

-68

-76

Tripping of 220 kV BTPS - Agia S/C

-155

-47

153x2

2 x -15

41

34

Tripping of 220 kV BTPS - Salakati D/C

-194

101

-104

2 x -41

95

87

Tripping of 220 kV Azara - Agia S/C

-81

-54

204

153x2

35 x 2

-124

Tripping of 220 kV Azara - Boko S/C

-80

-56

207

155x2

35x2

-129

Tripping of 220 kV Azara - Sarusajai D/C

-41

-110

188

145x2

-52

-59

Contingency

Remarks

OFFPEAK Case without Palatana Generation (NER DM = 1280 MW, GEN = 1031 MW)
Line Flows (MW)
400 kV Silchar - Byrnihat

400 kV Silchar - Azara

220 kV BTPS - Agia

220 kV BTPS - Salakati D/C

220 kV Azara - Sarusajai D/C

220 kV Azara-Boko

220 kV Azara - Agia

BaseCase

-46

108

87x2

26x2

-24

-29

With 400/220 kV Azara

-47

109

87x2

26x2

-24

-29

Tripping of 400kV Silchar - Byrnihat

-28

124

95x2

19x2

-31

-36

Tripping of 220 kV BTPS - Agia S/C

-86

53

33x2

2 x -1

30

25

Tripping of 220 kV BTPS - Salakati D/C

-110

87

-66

2 x -18

63

58

Tripping of 220 kV Azara - Agia S/C

-50

101

83x2

24x2

-45

Tripping of 220 kV Azara - Boko S/C

-50

103

84x2

24x2

-47

Tripping of 220 kV Azara - Sarusajai D/C

-28

-29

84

75x2

-12

-17