4109

( Grounded resistance tester 4109)


Features

Appl
y to

measure equal potential bonding resistance of buildingsmetal and resistance between


electrical device and earth mat pole.And measure contacted resistance of switch or socket ,as
well
as low resistance
l
Measure range0.0201999, resolution0.001precision2%
l
Interference voltage USTrange050VAC 45400Hzprecision5%
l
Adopt DC voltage energize and change pole to measure automatically( 4pole or 2pole)
l
Maximal open circuit voltage 20Vshort circuit current< 250mA
l
Can dislodge surplus resistance of measuring wire
l
Can store 100( Group ) measured data
l
Employ instrument panel calibration technology

Specifications:
DC resistanceR measure
Range

Measuring
range

Resolution

Precision
2%+2

0.020
1.999

0.001

20

2.00
19.99

0.01

200

20.0
199.9

0.1

2000

2001999

Interference voltage(AC)UST
Measuring range
www.ttbvision.com

Resolution

Frequency range

Precision

0.0V50.0V

0.1V

45
400Hzsine

5%+5

Characteristic
l
Display84.8 59.8mm segment LCD dual display,White LED backlight

l
l
l
l
l

Operation environment: 0 to 40 C ( no condensation10 C), 85%RH


High voltage: AC3250V (50/60Hz ) / 5seconds(between the electrical
circuit and the outside box)
Electrical safety grade: CAT 600V pollution degree 2.
Power :1.5V AA alkaline batteries8, can shut power automatically
Dimensions and weight:
175x111x70 mm, about 680g

Annex:

1m testing wire x 4
40m wire
x2
Alkaline batteries (LR6)
Instruction manual x1
Portable bag
x1
Meet the standard
l
IEC/EN 61557-14
l
IEC/EN 61010-1
l
IEC/EN 61010-2-031
l
IEC/EN 61326

www.ttbvision.com