Load the EMTDC/PSCAD simulation tool and open C:\ Program files / PSCAD / examples /
Sync_machines / sync_SCtest (synchronous generator short circuit test model) file and save
it in your personal directory.
IF
Tm
TM
0.001 [ohm]
100 [ohm]
#1
A
V
#2
SHORT
Te
w Tm
0.0
W
120 MVA 13.8 kV
HYDRO GENERATOR
IF
3 Phase
RMS
Vt
B
Tm
TM
w Tm
0.0
W
120 MVA 13.8 kV
HYDRO GENERATOR
0.001 [ohm]
Ib
0.001 [ohm]
Ic
13.8 [kV]
C
230.0 [kV]
120.0 [MVA]
#1
#2
Te
0.001 [ohm]
Ia
Ef If
SHORT
1.0
- Lab 1 Assignment 1
Simulation 3: Change your model to include the high reactance (0.1 H/phase) circuit.
Simulate the three-phase balanced fault and comment on the result.
Simulation 4: Change your model to include the high impedance circuit (100 Ohms and 0.1
H in series/phase). Simulate the three-phase balanced fault and comment on the result.
Simulation 5: Change your model to include the resistive load (100 Ohms/phase). Simulate
the three-phase balanced fault and comment on the result. Change the field voltage E f (2.0)
to boost the terminal voltage back to 230kV and simulate the three-phase balanced fault and
comment on the result.
Simulation model data
To get a detailed explanation of the data click the right mouse-button on the
component and select Properties.
Table 1: Generator and Transformer Data
Generator
Ts
= 0.02 [sec]
Vbase = 7.967 [kV]
Ibase = 5.02 [kA]
Ang.Fre = 314.159 [rad/s]
H
= 3.117 [sec]
D
= 0.04 [p.u.]
RNeut = 1.0E5 [p.u.]
XNeut = 0 [p.u.]
Ra
= 0.0030592 [p.u.]
Ta
= .278 [sec]
Xp
= 0.163 [p.u.]
Xd
= 1.014 [p.u.]
Xd'
= 0.314 [p.u.]
Tdo'
= 6.55 [sec]
Xd'' = 0.280 [p.u.]
Tdo'' = 0.039 [sec]
Xq
= 0.770 [p.u.]
Xq'
= 0.228 [p.u.]
Tqo' = 0.85 [sec]
Xq'' = 0.375 [p.u.]
Tqo'' = 0.071 [sec]
Assessment
Class attendance
Assignment
Total
Tmva
f
YD1
YD2
Lead
Xl
Ideal
NLL
Tap
V1
Im1
V2
Im2
Transformer
= 120.0 [MVA]
= 50.0 [Hz]
=1
=0
=1
= 0.005 [p.u.]
=1
= 0.0 [p.u.]
=0
= 13.8 [kV]
= 1.0 [%]
= 230.0 [kV]
= 1.0 [%]
50%
50%
100%