CAPACITY CHECK FOR PIPE BRACING MEMBER

BASED ON ACTUAL VALUES OF YIELD STRENGTH


AND
TENSILE STRENGTH AS PER DESIGN
CALCULATION

Location

Mezzanine at 7.5 M level

Member Designation

CHS 139.7 x 8.0

DesignSpecification for
pipe material

Grade of Steel:

BSEN 10210:2006 GRADE 355J2H

Strength Limits
BSEN 10025-2:2004
N/mm2
Yield Strength (Fy)
Tensile Strength (Fu)

Length of section : 8.115 M


Area of section : 3310 mm2
Radious of Gravity of Section , r=4.66 cm
Consider, K=1
=KL/r=1*8.115*100/4.66=174.14180 (ok)
Compresive Strength of Section ,
=175, from BS 5950-2000, Table 24, Pc=62 N/mm2
The maximum Capacity of section A*Pc=3310*62/1000=205.22 KN

355
470---630

CAPACITY CHECK FOR Available Section in the Market


Location

Mezzanine at 7.5 M level

Member Designation

CHS 141.3 x 9.3

DesignSpecification for
pipe material

Grade of Steel:

BSEN 10210:2006 GRADE 275JOH

Strength Limits
BSEN 10025-2:2004
N/mm2
275

Yield Strength (Fy)


Tensile Strength (Fu)

410---560

Length of section : 8.115 M


Area of section : 3940 mm2
Radious of Gravity of Section , r=4.66 cm
Consider, K=1
=KL/r=1*8.115*100/4.66=174.14180 (ok)
Compresive Strength of Section ,
=175, from BS 5950-2000, Table 24, Pc=60 N/mm2
The maximum Capacity of section A*Pc=3940*60/1000=236.4 KN 205

The Capacity of available section is bigger than


the designated Section