You are on page 1of 15

DOTACION DE AGUA

Norma S.121,4
area de lotes tipo 240 m2
Dotacion

200

l/hab/dia en clima frio

VARIACIONES DE CONSUMO
Cosumo promedio =

dotacion =
Pf =
Qp = (Pf *Dot)/86400 l/seg
Qp =

200 l/hab/dia
942 Hab

2.1806 l/seg

Consumo maximo de la demanda diaria QMD =

QP*1,3

2.83

Consumo maximo Horario

QP*2,6

5.67

QMH =

DEMANDA CONTRA INCENDIOS


S.121.6

Para habilitaciones urbanas de poblaciones menores a 10000 hab


no se considerara demanda contra incendios

a) Volumen de regulacion
Variacion de consumos
Horas de Bonbeo:

total
HORAS
2
4
6
8
10
12
14
16
18
20
22
24

% PROMEDI CONSUMO PRODUCCION


20
0.2
0
30
0.3
0
60
0.6
1.5
126
1.26
3
132
1.32
1.5
180
1.8
0
147
1.47
0
137
1.37
0
122
1.22
3
96
0.96
3
90
0.9
0
60
0.6
0
1200
12
12

b) Volumen contra incendios

de 5 a 9

am

de 4 a 8

pm

8 horas diarias
CONSUMO
PRODUCION
ACUMULATICO
ACUMULADA
0.2
0
0.5
0
1.1
1.5
2.36
4.5
3.68
6
5.48
6
6.95
6
8.32
6
9.54
9
10.5
12
11.4
12
12
12

Vreg =

(2,32+2,32) K =

4.64

K=

QMD * 7,2

20.41

Vreg =

4,64 * K =

94.70

no se considera por tener menos de 10000 hab


c) volumen de reserva
Vres =

VOLUMEN DE ALMACENAMIENTO =

0,33 (Vreg+Vinc)=

31.25

Vreg+V inc+Vres=

125.95

l/seg
l/seg

DIFERENCIAS
-0.20
-0.50
0.40
2.14
2.32
0.52
-0.95
-2.32
-0.54
1.50
0.60
0.00

K
m3
m3

m3

m3

CAUDAL DE DISEO
Pf=
Dot=
QMD=
Qi=
QMH=
At=
cd=

poblacion futura

Area total

6681.00
200.00
20.10
0.00
40.21
196253.87
0.00020

hab
l/hab/d
l/s
l/s
m2

calculo de consumos (metodo del area)


tramo
A-B
B-C
C-D
D-E
E-F
F-A
D-A

cd
area tributaria Q
0.00020489
14170.73 2.9034
0.00020489
39162.06 8.0238
0.00020489
14794.66 3.0312
0.00020489
21727.85 4.4517
0.00020489
27367.18 5.6072
0.00020489
22116.85 4.5314
0.00020489
56914.54 11.661

4.53

40.21
F
A

4.45
E
5.61
3.03

D
11.66

B
2.9

C
8.02

METODO DE CROOS
CIRCUITO TRAMO

II

PRIMERA ITERACION

L (m)

Q (l/s)

D (pul)

S(m/m)

B-A
A-D
D-C
C-B

284.79
350.69
246.70
367.11

150
150
150
150

-1 8.2100
1 12.0000
1 5.7500
-1 5.3100

4
4
4
3

-10.6596
21.5277
5.5119
-19.3098

A-F
F-E
E-D
D-A

296.69
333.66
295.03
350.69

150
150
150
150

1 20.0000
1 15.4700
1 9.8600
-1 12.3175

6
6
4
4

7.6948
4.7824
14.9632
-22.5943

-3.0357
7.5495
1.3598
-7.0888
-1.2153
2.2830
1.5957
4.4146
-7.9236
0.3697

H/Q

0.3698
0.6291
0.2365
1.3350
2.5704
0.1141
0.1031
0.4477
0.6433
1.3083

Qo(Lt/Seg) V(m/s)

0.2556
0.4083
0.2556
0.2556

-7.95444 -0.981
12.4083 1.531
6.00556 0.741
-5.05444 -1.108

-0.1527
-0.1527
-0.1527
-0.4083

19.8473 1.088
15.3173 0.840
9.70727 1.197
-12.7258 -1.570

SEGUNDA ITERACION
CIRCUITO TRAMO

II

L (m)

Q (l/s)

D (pul)

S(m/km)

B-A
A-D
D-C
C-B

284.79
350.69
246.70
367.11

150
150
150
150

-1 7.9544
1 12.4083
1 6.0056
-1 5.0544

4
4
4
3

-10.0533
22.9037
5.9742
-17.6242

A-F
F-E
E-D
D-A

296.69
333.66
295.03
350.69

150
150
150
150

1 19.8473
1 15.3173
1 9.7073
-1 12.7258

6
6
4
4

7.5863
4.6953
14.5369
-24.0008

TERCERA ITERACION

Hf

-2.8631
8.0321
1.4738
-6.4700
0.1728
2.2508
1.5666
4.2888
-8.4168
-0.3106

H/Q

0.3599
0.6473
0.2454
1.2801
2.5327
0.1134
0.1023
0.4418
0.6614
1.3189

Qo(Lt/Seg) V(m/s)

-0.0369
-0.1642
-0.0369
-0.0369

-7.99133 -0.986
12.2441 1.510
5.96867 0.736
-5.09133 -1.116

0.1273
0.1273
0.1273
0.1642

19.9746 1.095
15.4446 0.847
9.83457 1.213
-12.5616 -1.549

CIRCUITO TRAMO

II

L (m)

Q (l/s)

D (pul)

S(m/m)

B-A
A-D
D-C
C-B

284.79
350.69
246.70
367.11

150
150
150
150

-1 7.9913
1 12.2441
1 5.9687
-1 5.0913

4
4
4
3

-10.1398
22.3456
5.9064
-17.8631

A-F
F-E
E-D
D-A

296.69
333.66
295.03
350.69

150
150
150
150

1 19.9746
1 15.4446
1 9.8346
-1 12.5616

6
6
4
4

7.6767
4.7678
14.8919
-23.4305

-2.8877
7.8364
1.4571
-6.5577
-0.1519
2.2776
1.5908
4.3935
-8.2168
0.0451

H/Q

0.3614
0.6400
0.2441
1.2880
2.5335
0.1140
0.1030
0.4467
0.6541
1.3179

Qo(Lt/Seg) V(m/s)

0.0324 -7.95891 -0.982


0.0509 12.295 1.517
0.0324 6.00109 0.740
0.0324 -5.05891 -1.109
-0.0185
-0.0185
-0.0185
-0.0509

19.9561 1.094
15.4261 0.846
9.81606 1.211
-12.6125 -1.556

CUARTA ITERACION
CIRCUITO TRAMO

II

L (m)

B-A
A-D
D-C
C-B

284.79
350.69
246.70
367.11

150
150
150
150

-1 7.9589
1 12.2950
1 6.0011
-1 5.0589

Q (l/s)

D (pul)

4
4
4
3

-10.0638
22.5181
5.9660
-17.6531

S(m/m)

A-F
F-E
E-D
D-A

296.69
333.66
295.03
350.69

150
150
150
150

1 19.9561
1 15.4261
1 9.8161
-1 12.6125

6
6
4
4

7.6635
4.7572
14.8400
-23.6067

-2.8661
7.8969
1.4718
-6.4806
0.0220
2.2737
1.5873
4.3782
-8.2786
-0.0394

H/Q

0.3601
0.6423
0.2453
1.2810
2.5287
0.1139
0.1029
0.4460
0.6564
1.3192

-0.0047
-0.0208
-0.0047
-0.0047

Qo(Lt/Seg) V(m/s)

-7.96361 -0.982
12.2742 1.514
5.99639 0.740
-5.06361 -1.110

0.0161 19.9722 1.095


0.0161 15.4422 0.847
0.0161 9.8322 1.213
0.0208 -12.5917 -1.553

DISEO DE LA LINES DE ADUCION


Hf =
L=
C=
Q=
D=

2
198
140
2.83

S=

10.1010101

USAMOS LA FORMULA DE HASSEN-WILLIANS


D=

2.69934194

D=

CALCULAMOS Hf
S=

6.02077524

Hf =

1.1921135
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0

PRESINES
FINALES
0.8078865
0.8078865
0.8078865
0.8078865
0.8078865
0.8078865
0.8078865
0.8078865

REDES SECUNDARIAS
asumimos las redes secundaris con un diametro menor a la de de la tuberias principales
HIDRANTES
no se colovan hidrantes porque no tenemos volumen contra incendios
no tenemos tuberias de diametro de 100 mm

You might also like