Bse Consumer Unit
LIGHTING
Ground Floor
Total Power
= (6 X 100W) + (3 X 60W)
= 600W + 180W
= 780W
Current
= 780W / 230V
= 3.39A (Therefore, 6A of fuse is used)
First Floor
Total Power
= (7 X 100W) + (3 X 60W)
= 700W + 180W
= 880W
Current
= 880W / 230V
= 3.83A (Therefore, 6A of fuse is used)
Current
= 1118.5W / 230V
= 4.86A (Therefore, 6A of fuse is used)
= 1934W
Current
= 1934W / 230V
= 8.41A (Therefore, 10A of fuse is used)
SHOWER UNIT
Ground Floor & First Floor
Total Power
= 2 X 2000W
= 4000W
Current
= 4000W / 230V
= 17.39A (Therefore, 40A of fuse is used as the most of the shower is
using 40A)
COOKER
Ground Floor & First Floor
40A of fuse is used by follow the standard fuse rating of cooker.
BOILER
Ground Floor & First Floor
40A of fuse is used by follow the standard fuse rating of boiler.
Live Bar
Neutral
2-pole
switch
Earth Bar
Eart
h
Neutr
al
Live