Formula Used

Current (I) = Power (W) / Voltage (V)

LIGHTING
Ground Floor
Total Power

= (6 X 100W) + (3 X 60W)
= 600W + 180W
= 780W

Current

= 780W / 230V
= 3.39A (Therefore, 6A of fuse is used)

First Floor
Total Power

= (7 X 100W) + (3 X 60W)
= 700W + 180W
= 880W

Current

= 880W / 230V
= 3.83A (Therefore, 6A of fuse is used)

SPLIT UNIT AIR-CONDITIONER (MASTER BEDROOM)


Ground Floor & First Floor
Total Power

= (1.5 horsepower X 745.699872W)


= 1118.55W

Current

= 1118.5W / 230V
= 4.86A (Therefore, 6A of fuse is used)

WINDOW UNIT AIR-CONDITIONER (BEDROOM 2)


Ground Floor & First Floor
Total Power

= 1934W

Current

= 1934W / 230V
= 8.41A (Therefore, 10A of fuse is used)

POWER SOCKET RING MAIN


Ground Floor & First Floor
32A of fuse is used by follow the standard fuse rating.

SHOWER UNIT
Ground Floor & First Floor
Total Power

= 2 X 2000W
= 4000W

Current

= 4000W / 230V
= 17.39A (Therefore, 40A of fuse is used as the most of the shower is
using 40A)

COOKER
Ground Floor & First Floor
40A of fuse is used by follow the standard fuse rating of cooker.

BOILER
Ground Floor & First Floor
40A of fuse is used by follow the standard fuse rating of boiler.

DESIGN OF CONSUMER UNIT


Ground Floor & First Floor

10A Window Unit Air6A Split Unit Air40A


Shower
40A
Cooker
Ring
40A
Boiler
32A32A
Ring
6A Lighting

Live Bar
Neutral

2-pole
switch

Earth Bar

Eart
h

Neutr
al
Live