Medium voltage products

VD4
Medium voltage vacuum circuit-breakers
12...36 kV - 630...3150 A - 16...50 kA

Index

1. Description

1 2

2. Selection and ordering

6 4

3. Specific product characteristics

6 8

4. Overall dimensions

9 5

5. Electric circuit diagram

1. Description

The new VD4 are a synthesis of renowned technology


in designing and constructing vacuum interrupters
embedded in poles, and excellency in design, engineering
and production of circuit-breakers.
The VD4 medium voltage circuit-breakers use vacuum
interrupters embedded in the poles. This construction
technique makes the circuit-breaker poles particularly
sturdy and protects the interrupter from impacts, dust
deposits and humidity. The vacuum interrupter houses the
contacts and makes up the interrupting chamber.

1
2
3
4

5
6
7

8
9
10

1
2
3
4
5
6
7
8

Upper terminal
Vacuum interrupter
Housing/pole
Stem of moving contact
Lower terminal
Flexible connection
Tie-rod spring fork
Tie-rod

9 Pole fixing
10 Connection to operating
mechanism

Vacuum interrupter embedded in the pole

Current interruption in vacuum


The vacuum circuit-breaker does not require an interrupting
and insulating medium. In fact, the interrupters do not contain
ionisable material.
In any case, on separation of the contacts an electric arc
is generated made up exclusively of melted and vaporised
contact material.
The electric arc remains supported by the external energy
until the current is cancelled in the vicinity of natural zero. At
that instant, the rapid reduction in the load density carried
and the rapid condensation of the metallic vapour, leads to
extremely rapid recovery of the dielectric characteristics.
The vacuum interrupter therefore recovers the insulating
capacity and the capacity to withstand the transient recovery
voltage, definitively extinguishing the arc.
Since high dielectric strength can be reached in the vacuum,

Vacuum interruption technique


Vacuum contacts protected against oxidation and
contamination
Vacuum interrupter embedded in the pole
Interrupter protected against shocks, dust and humidity
Operation under different climatic conditions
Limited switching energy
Stored energy operating mechanism with anti-pumping
device supplied as standard
Simple customisation with a complete range of
accessories
Fixed and withdrawable version
Compact dimensions
Sealed-for-life poles
Sturdiness and reliability
Limited maintenance
Circuit-breaker racking in and racking out with door
closed
Incorrect and hazardous operations are prevented
thanks to special locks in the operating mechanism and
in the truck
High environmental compatibility

even with minimum distances, interruption of the circuit is


also guaranteed when separation of the contacts takes place
a few milliseconds before passage of the current through
natural zero.
The special geometry of the contacts and the material used,
as well as the limited duration and low voltage of the arc,
guarantee minimum contact wear and long life. Furthermore,
the vacuum prevents their oxidation and contamination.
Operating mechanism
The low speed of the contacts, together with the reduced run
and low mass, limit the energy required for the operation and
therefore guarantee extremely limited wear of the system.
The circuit-breaker therefore only requires limited
maintenance.
The VD4 circuit-breakers use a mechanical operating

mechanism, with stored energy and free trip.


These characteristics allow opening and closing operations
independent of the operator. The operating mechanism is of
simple conception and use and can be customised with a
wide range of accessories which are easy and rapid to install.
This simplicity converts into greater reliability of the apparatus.
The structure
The operating mechanism and the poles are fixed to a metal
frame which is also the support for the fixed version of the
circuit-breaker. The compact structure ensures sturdiness and
mechanical reliability.
Apart from the isolating contacts and the cord with plug for
connection of the auxiliary circuits, the withdrawable version
is completed with the truck for racking it into and out of the
switchgear or enclosure with the door closed.

1. Description

Quenching principle of ABB interrupters


In a vacuum interrupter, the electric arc starts at the moment
of contact separation and is maintained until zero current and
can be influenced by magnetic fields.
Vacuum arc diffuse or contracted
Following contact separation, single melting points form over
the entire surface of the cathode, producing metal vapours
which support the arc.
The diffuse vacuum arc is characterised by expansion over
the contact surface and by an even distribution of thermal
stress on the contact surfaces.

At the rated current of the vacuum interrupter, the electric arc


is always of the diffuse type. Contact erosion is very limited
and the number of current interruptions very high.
As the interrupted current value increases (above the rated
value), the electric arc tends to be transformed from the
diffuse into the contracted type, due to the Hall effect.
Starting at the anode, the arc contracts and as the current
rises further it tends to become sharply defined. Near the area
involved there is an increase in temperature with consequent
thermal stress on the contact.
To prevent overheating and erosion of the contacts, the arc is
kept rotating. With arc rotation it becomes similar to a moving
conductor which the current passes through.

1
2
3
4
5
6
7
8
9
10

1 Stem/terminal
2 Twist protection
3 Bellows
4 Interrupter housing
5 Shield
6 Ceramic insulator

Vacuum interrupter

7 Shield
8 Contacts
9 Terminal
10 Interrupter housing

Diffuse arc.

Contraction
over anode.

Contraction over
anode and cathode.

Schematic diagram of the transition from a diffuse arc to a contracted arc


in a vacuum interrupter.

The spiral geometry of ABB vacuum interrupter contacts


The special geometry of the spiral contacts generates a radial
magnetic field in all areas of the arc column, concentrated
over the contact circumferences.
An electromagnetic force is self-generated and this acts
tangentially, causing rapid arc rotation around the contact
axis.
This means the arc is forced to rotate and to involve a wider
surface than that of a fixed contracted arc.

Apart from minimising thermal stress on the contacts, all


this makes contact erosion negligible and, above all, allows
the interruption process to be controlled even with very high
short-circuits.
ABB vacuum interrupters are zero-current interrupters and are
free of any re-striking.
Rapid reduction in the current charge and rapid condensation
of the metal vapours simultaneously with the zero current,
allows maximum dielectric strength to be restored between
the interrupter contacts within microseconds.

Corrent, Voltage

Short-circuit
current
Arc voltage
System
voltage

Short-circuit current
interruption

Time
Contact
separation
Recovery voltage
(system frequency)
Transient recovery voltage (TRV)
(high frequency)

Radial magnetic field contact


arrangement with a rotating
vacuum arc.

Development of current and voltage trends during a single phase vacuum interruption process.

1. Description

Versions available
The VD4 circuit-breakers are available in the fixed and
withdrawable version with front operating mechanism.
The withdrawable version is available for UniGear ZS1, ZS8.2
and UniSec switchgear and for PowerCube and Powerbloc
enclosures.

Fields of application
The VD4 circuit-breakers are used in power distribution for
control and protection of cables, overhead lines, transformer
and distribution substations, motors, transformers, generators
and capacitor banks.

Standards
The VD4 circuit-breakers comply with the IEC 62271-100,
VDE 0671-part. 100, CEI EN 62271-100 file 7642 (20055) Standards and with those of the major industrialised
countries.
The VD4 circuit-breakers have undergone the tests indicated
below and guarantee the safety and reliability of the apparatus
in service in any installation.
Type tests: heating, withstand insulation at power frequency,
withstand insulation at lightning impulse, short-time and peak
withstand current, mechanical life, short-circuit current making
and breaking capacity.
Individual tests: insulation of the main circuits with
voltage at power frequency, auxiliary circuit and operating
mechanism insulation, measurement of the main circuit
resistance, mechanical and electrical operation.

Service safety
Thanks to the complete range of mechanical and electrical
locks (available on request), it is possible to construct safe
distribution switchgear with the VD4 circuit-breakers.
The locking devices have been studied to prevent incorrect
operations and to inspect the installations whilst guaranteeing
maximum operator safety.
Key locks or padlock devices enable opening and closing
operations and/or racking in and racking out.
The racking-out device with the door closed allows the circuitbreaker to be racked into or out of the switchgear only with
the door closed.
Anti-racking-in locks prevent circuit-breakers with different
rated currents from being racked in, and the racking-in and
racking out operation with the circuit-breaker closed.

Highly reliable operating mechanisms thanks to a low


number of components which are manufactured using
production systems for large quantities
Extremely limited and simple maintenance
Accessories common to the entire range
Electrical accessories that can be easily and quickly
installed or replaced thanks to wiring pre-engineered
with plug-socket connectors
Mechanical anti-pumping device is supplied as
standard
Built-in closing spring charging lever
Key lock with circuit-breaker open
Protective covering over the opening and closing
pushbuttons to be operated using a special tool
Padlock device on the operating pushbuttons

Accessories
The VD4 circuit-breakers have a complete range of
accessories to satisfy all installation requirements.
The operating mechanism has a standardised range of
accessories and spare parts which are easy to identify and
order.
The accessories are installed conveniently from the front of
the circuit-breaker. Electrical connection is carried out with
plug-socket connectors.
Use, maintenance and service of the apparatus are simple
and require limited use of resources.

M
L
I
H
G

Circuit-breaker operating mechanism


A Open/closed auxiliary contacts
B Geared motor for closing spring charging
C Built-in closing spring charging lever
D Mechanical signalling device for circuit-breaker
open/closed
E Mechanical operation counter
F Plug-socket connectors of electrical accessories
in the truck

G Signalling device for closing springs charged/discharged


H Service releases
I Closing pushbutton
L Opening pushbutton
M Operating mechanism locking electromagnet
N Additional shunt opening release
O Transient contact
P Contacts for signalling spring charged/discharged

1. Description

General characteristics of the complete VD4 series (*)


The VD4 series of vacuum circuit-breakers conform to the
specifications of the following standards:
VDE 00670, part 1000
IEC 62271-1
VDE 00671, part 100
IEC 62271-100
CEI EN 62271-100 File 7642 (2005-5)
(*) For information about the 12 kV 1250 ... 4000 A 50/63 kA and 36/40.5 kV
630 ... 2500 A 16 ... 40 kA circuit-breakers, please see technical catalogue
GCBA520PO102.

Rated voltage

(1)

Rated frequency
Rated normal current

kV

12

Hz

50 - 60

630 . . . 4000 (2)

Short-time withstand current and breaking capacity

kA

16 ... 31.5

40

50

Making capacity

kA

40 ... 80

100

125

Short-time withstand current

63
(3)

158

d (mm)

150 - 275

210 - 275

210 - 275

275

H (mm)

205 - 310

310

310

310

a (mm)

450 - 700

570 - 700

600 - 750

750

b (mm)

424

424

459

459

c (mm)

461 - 599

kg

73 - 105

94 - 180

147 - 260

Embedded poles

Assembled poles

Fixed / withdrawable version

Maximum overall
dimensions
(fixed version)

H
c

d
a

Weight

Technical documentation

10

599

(5)

608

(7)

677
260

To go into technical and application aspects of the VD4 circuitbreakers in depth, please ask us for the following publications:
PowerCube modules
code 1VCP000091
Powerbloc modules
code BA441/03E
UniGear ZS1 switchgear
code 1VCP000138
ZS8.4 switchgear
code L2288
REF542plus unit
code 1VTA100001
PR512 protection unit
code 1VCP000055

17.5

24

36

40,5

50 - 60

50 - 60

50-60

50-60

630 3150

630 3150

630 . . . 4000

630 . . . 3150

(2)

(2)

16 ... 31.5

40 ... 50

16 ... 31.5

16 ... 31.5

16 40

40 ... 80

100 ... 125

40 ... 80

40 ... 80

40 100

150 - 275

210 - 275

210 - 275

275

205 - 310

310

310

328 / 280

(6)

450 - 700

570 - 700

570 - 700

786 / 853

(6)

424

424

424

492 / 789

(6)

631 - 661

876 / 973

(6)

461 - 599

(5)

599

(5) (7)

280 - 360

(4)

328
895

(6)

- 1000

555 - 686

(6)

1575

73 - 105

94 - 180

100 - 110

170 / 210

290 - 350

Test voltage according to IEC 622711 Standards table 1a, VDE 0670, - part
1000, list 2
(2)
With forced ventilation
(3)
Higher values on request
(4)
360 mm for fixed version, 280 mm for
withdrawable version
(5)
Circuit-breaker with eat sink 616 mm
(2500 A)
(6)
Withdrawable version
(7)
Circuit-breaker with eat sink 634 mm
(3150 A)
(1)

Quality System
Complies with ISO 9001 Standards, certified by an
independent organisation.

Environmental Management System


Complies with ISO 14001 Standards, certified by an
independent organisation.

Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025 Standards,
accredited by an independent organisation.

Health and Safety Management System


Complies with OHSAS 18001 Standards, certified by an
independent organisation.

11

2. Selection and ordering



Withdrawable circuit-breakers

Fixed VD4 circuit-breaker (12 kV)

Circuit-breaker

VD4 12 (1)
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 12

Rated insulation voltage

Us [kV] 12

Withstand voltage at 50 Hz

Ud (1 min) [kV] 28

Impulse withstand voltage

Up [kV] 75

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

Rated breaking capacity


(rated short-circuit breaking current
symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

630

630

1250

1250

1250

1250

1250

1250

1250

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

40

40

50

50

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

40

40

50

50

40

40

40

40

40

40

50

50

50

50

50

50

63

63

63

63

63

63

80

80

80

80

80

80

100

100

125

125

610

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

461

461

461

589

589

610

700

450

570

700

570

700

600

750

D [mm] 424

424

424

424

424

424

424

424

459

459

TN 7405
1VCD

Operating temperature

210

275

150

210

275

210

275

210

275

75

79

73

75

79

84

84

146

158

7406

7405

7406

000051

000051 003282 003285 003440 003441

[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(1) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

12

461

570

[kg] 73

Standardised table of dimensions

Electromagnetic compatibility

461

W [mm] 450
Pole distance P [mm] 150

Weight

Tropicalization

H [mm] 461

12
12
28
75
50-60
1600

1600

1600

1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

2500

3150

3150

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31,5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

63

80

80

80

80

80

80

80

80

100

100

100

100

100

100

125

125

125

125

125

125

599

599

599

589

589

610

610

599

599

610

610

599

599

610

635

636

450

570

700

570

700

600

750

570

700

600

750

570

700

750

700

750

424

424

424

424

424

459

459

424

424

459

459

424

424

459

424

459

150

210

275

210

275

210

275

210

275

210

275

210

275

275

275

275

93

98

105

84

84

146

158

98

105

146

158

98

105

163

140

177

7407

7408

7407

7408

7407

7408

003282 003285 003440 003441

003440 003441

003441 000149 003443

33 ... 60
10 ... 15
43 ... 75
60 ... 80

000050
- 5 ... + 40

13

2. Selection and ordering



Withdrawable circuit-breakers

Fixed VD4 circuit-breaker (17.5 kV)

Circuit-breaker

VD4 17 (1)
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 17.5

Rated insulation voltage

Us [kV] 17.5

Withstand voltage at 50 Hz

Ud (1 min) [kV] 38

Impulse withstand voltage

Up [kV] 95

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

Rated breaking capacity


(rated short-circuit breaking
current symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

630

630

1250

1250

1250

1250

1250

1250

1250

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

40

40

50

50

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

40

40

50

50

40

40

40

40

40

40

50

50

50

50

50

50

63

63

63

63

63

63

80

80

80

80

80

80

100

100

125

125

610

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

461

461

461

589

589

610

700

450

570

700

570

700

600

750

D [mm] 424

424

424

424

424

424

424

424

459

459

TN 7405
1VCD

Operating temperature

210

275

150

210

275

210

275

210

275

75

79

73

75

79

84

84

146

158

7406

7405

7406

000051

000051 003282 003285 003440 003441

[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(1) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

14

461

570

[kg] 73

Standardised table of dimensions

Tropicalization

461

W [mm] 450
Pole distance P [mm] 150

Weight

Electromagnetic compatibility

H [mm] 461

17.5
17.5
38
95
50-60
1600

1600

1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

2500

3150

3150

20

20

20

20

20

20

20

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

20

20

20

20

20

20

20

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

80

80

80

80

80

80

80

100

100

100

100

100

100

125

125

125

125

125

125

599

599

589

589

610

610

599

599

610

610

599

599

610

635

636

570

700

570

700

600

750

570

700

600

750

570

700

750

700

750

424

424

424

424

459

459

424

424

459

459

424

424

459

424

459

210

275

210

275

210

275

210

275

210

275

210

275

275

275

275

98

105

84

84

146

158

98

105

146

158

98

105

163

140

177

7407

7408

7407

7408

7407

7408

003282

003285

003440

003441

003440

003441

003441

000149

003443

33 ... 60
10 ... 15
43 ... 75
60 ... 80

- 5 ... + 40

15

2. Selection and ordering



Withdrawable circuit-breakers

Fixed VD4 circuit-breaker (24 kV)

Circuit-breaker

VD4 24
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 24

Rated insulation voltage

Us [kV] 24

Withstand voltage at 50 Hz

Ud (1 min) [kV] 50

Impulse withstand voltage

Up [kV] 125

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

630

1250

1250

1600

2000

2500

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

63

63

63

63

63

63

63

80

80

80

80

[O - 0.3 s - CO - 15 s - CO]

H [mm] 631

631

631

631

642

642

642

W [mm] 570

700

570

700

700

700

700

D [mm] 424

424

424

424

424

424

424

Pole distance P [mm] 210

275

210

275

275

275

275

[kg] 100

104

110

110

110

7410

7411

7411

7411

Rated breaking capacity


(rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity

Isc [kA]

Ik [kA]

Ip [kA]

Operation sequence
Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1) 31.5 kA version.

16

TN 7409
1VCD
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

104

100/106

7410

7409

000172

(1)

(1)

Fixed VD4 circuit-breaker (36 kV)

Circuit-breaker

VD4 36
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 36

Rated insulation voltage

Us [kV] 36

Withstand voltage at 50 Hz

Ud (1 min) [kV] 70

Impulse withstand voltage

Up [kV] 170

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 1250

Rated breaking capacity


(rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity
Operation sequence

1600

2000

2500 (*)

31,5

31,5

31,5

Isc [kA] 31,5

Ik [kA] 31,5

31,5

31,5

31,5

Ip [kA] 80

80

80

80

H [mm] 564

564

564

W [mm] 778

778

778

D [mm] 468

468

468

Pole distance P [mm] 275

275

275

[kg] 150

150

170

1VYN300901-LT

1VYN300901-LT

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 35 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 45 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

TN 1VYN300901-LT
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(*) Contact ABB.

17

2. Selection and ordering



Withdrawable circuit-breakers

Types of fixed version circuit-breakers available


Complete the circuit-breaker selected with the optional accessories indicated on the following pages.

VD4 fixed circuit-breaker without bottom and top terminals (12 kV)
Ur

kV

Isc

kA

Rated uninterrupted current (40C) [A]


H=461

H=589

H=599

H=610

H=636

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 12.06.16 p150

20

630

VD4 12.06.20 p150

25

630

VD4 12.06.25 p150

31.5

630

VD4 12.06.32 p150

16

1250

VD4 12.12.16 p150

20

1250

VD4 12.12.20 p150

25

1250

VD4 12.12.25 p150

31.5

1250

VD4 12.12.32 p150

20

1600

VD4 12.16.20 p150

25

1600

VD4 12.16.25 p150

31.5
16

12

1600

VD4 12.16.32 p150

630

VD4 12.06.16 p210

20

630

VD4 12.06.20 p210

25

630

VD4 12.06.25 p210

31.5

630

VD4 12.06.32 p210

16

1250

VD4 12.12.16 p210

20

1250

VD4 12.12.20 p210

25

1250

VD4 12.12.25 p210

31.5

1250

40

VD4 12.12.32 p210


1250

VD4 12.12.40 p210

50

1250

VD4 12.12.50 p210

20

1600

VD4 12.16.20 p210

25

1600

VD4 12.16.25 p210

31.5

1600

VD4 12.16.32 p210

40

1600

VD4 12.16.40 p210

50

1600

VD4 12.16.50 p210

20

2000

VD4 12.20.20 p210

25

2000

VD4 12.20.25 p210

31.5

2000

VD4 12.20.32 p210

40

2000

50

VD4 12.20.40 p210


2000

VD4 12.20.50 p210

20

2500

VD4 12.25.20 p210

25

2500

VD4 12.25.25 p210

31.5

2500

VD4 12.25.32 p210

= Height of the circuit-breaker.

= Width of the circuit-breaker.

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

= Pole horizontal centre distance.

18

Circuit-breaker type

VD4 fixed circuit-breaker without bottom and top terminals (12 kV)
Ur

kV

Isc

kA

Rated uninterrupted current (40C) [A]


H=461

H=589

H=599

H=610

H=636

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 12.06.16 p275

20

630

VD4 12.06.20 p275

25

630

VD4 12.06.25 p275

31.5

630

VD4 12.06.32 p275

16

1250

VD4 12.12.16 p275

20

1250

VD4 12.12.20 p275

25

1250

VD4 12.12.25 p275

31.5

1250

40

VD4 12.12.32 p275


1250

VD4 12.12.40 p275

50

1250

VD4 12.12.50 p275

20

1600

VD4 12.16.20 p275

25

1600

VD4 12.16.25 p275

31.5

1600

VD4 12.16.32 p275

40

12

Circuit-breaker type

1600

VD4 12.16.40 p275

50

1600

VD4 12.16.50 p275

20

2000

VD4 12.20.20 p275

25

2000

VD4 12.20.25 p275

31.5

2000

VD4 12.20.32 p275

40

2000

50

VD4 12.20.40 p275


2000

VD4 12.20.50 p275

20

2500

VD4 12.25.20 p275

25

2500

VD4 12.25.25 p275

31.5

2500

VD4 12.25.32 p275

40

2500

50

VD4 12.25.40 p275


2500

VD4 12.25.50 p275

20

3150

VD4 12.32.20 p275

25

3150

VD4 12.32.25 p275

31.5

3150

VD4 12.32.32 p275

40

3150

VD4 12.32.40 p275

50

3150

VD4 12.32.50 p275

= Height of the circuit-breaker.

= Width of the circuit-breaker.

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

= Pole horizontal centre distance.

19

2. Selection and ordering



Withdrawable circuit-breakers

VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV)
Ur

Isc

kV

kA

17.5

Rated uninterrupted current (40 C) [A]


H=461

H=589

H=599

H=610

H=635

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237.5

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 17.06.16 p150

20

630

VD4 17.06.20 p150

25

630

VD4 17.06.25 p150

31.5

630

VD4 17.06.32 p150

16

1250

VD4 17.12.16 p150

20

1250

VD4 17.12.20 p150

25

1250

VD4 17.12.25 p150

31.5

1250

VD4 17.12.32 p150

16

630

VD4 17.06.16 p210

20

630

VD4 17.06.20 p210

25

630

VD4 17.06.25 p210

31.5

630

VD4 17.06.32 p210

16

1250

VD4 17.12.16 p210

20

1250

VD4 17.12.20 p210

25

1250

VD4 17.12.25 p210

31.5

1250

40

VD4 17.12.32 p210


1250

VD4 17.12.40 p210

50

1250

VD4 17.12.50 p210

20

1600

VD4 17.16.20 p210

25

1600

VD4 17.16.25 p210

31.5

1600

VD4 17.16.32 p210

40

1600

VD4 17.16.40 p210

50

1600

VD4 17.16.50 p210

20

2000

VD4 17.20.20 p210

25

2000

VD4 17.20.25 p210

31.5

2000

VD4 17.20.32 p210

40

2000

50

VD4 17.20.40 p210


2000

VD4 17.20.50 p210

20

2500

VD4 17.25.20 p210

25

2500

VD4 17.25.25 p210

31.5

2500

VD4 17.25.32 p210

= Height of the circuit-breaker.

= Width of the circuit-breaker.

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

= Pole horizontal centre distance.

20

Circuit-breaker type

VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV)
Ur

Isc

kV

kA

Rated uninterrupted current (40 C) [A]


H=461

H=589

H=599

H=610

H=635

D=424

D=424

D=424

D=459

D=459

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

l/g=217.5

l/g=238

l/g=237.5

l/g=237

l/g=237.5

P=150

P=210

P=275

P=210

P=275

P=150

P=210

P=275

P=210

P=275

P=275

W=450

W=570

W=700

W=570

W=700

W=450

W=570

W=700

W=600

W=750

W=750

16

630

VD4 17.06.16 p275

20

630

VD4 17.06.20 p275

25

630

VD4 17.06.25 p275

31.5

630

VD4 17.06.32 p275

16

1250

VD4 17.12.16 p275

20

1250

VD4 17.12.20 p275

25

1250

VD4 17.12.25 p275

31.5

1250

40

VD4 17.12.32 p275


1250

VD4 17.12.40 p275

50

1250

VD4 17.12.50 p275

20

1600

VD4 17.16.20 p275

25

1600

VD4 17.16.25 p275

31.5

1600

VD4 17.16.32 p275

40

17.5

Circuit-breaker type

1600

VD4 17.16.40 p275

50

1600

VD4 17.16.50 p275

20

2000

VD4 17.20.20 p275

25

2000

VD4 17.20.25 p275

31.5

2000

VD4 17.20.32 p275

40

2000

50

VD4 17.20.40 p275


2000

VD4 17.20.50 p275

20

2500

VD4 17.25.20 p275

25

2500

VD4 17.25.25 p275

31.5

2500

VD4 17.25.32 p275

40

2500

50

VD4 17.25.40 p275


2500

VD4 17.25.50 p275

20

3150

VD4 17.32.20 p275

25

3150

VD4 17.32.25 p275

31.5

3150

VD4 17.32.32 p275

40

3150

VD4 17.32.40 p275

50

3150

VD4 17.32.50 p275

= Height of the circuit-breaker.

= Width of the circuit-breaker.

= Depth of the circuit-breaker.

u/l

= Distance between bottom and top terminal.

l/g

= Distance between the bottom terminal and the resting surface of the circuit-breaker.

= Pole horizontal centre distance.

21

2. Selection and ordering



Withdrawable circuit-breakers

VD4 fixed circuit-breaker without bottom and top terminals (24 kV)
Ur

Isc

kV

kA

24

H
W
D
u/l
l/g
P

22

=
=
=
=
=
=

Rated uninterrupted current (40 C) [A]


H=631

H=642

D=424

D=424

u/l=310

u/l=310

l/g=282.5

Circuit-breaker type

l/g=282.5

P=210

P=275

P=275

W=570

W=700

W=700

16

630

VD4 24.06.16 p210

20

630

VD4 24.06.20 p210

25

630

VD4 24.06.25 p210

16

1250

VD4 24.12.16 p210

20

1250

VD4 24.12.20 p210

25

1250

VD4 24.12.25 p210

31.5

1250

VD4 24.12.32 p210

16

630

VD4 24.06.16 p275

20

630

VD4 24.06.20 p275

25

630

VD4 24.06.25 p275

16

1250

VD4 24.12.16 p275

20

1250

VD4 24.12.20 p275

25

1250

VD4 24.12.25 p275

16

1600

VD4 24.16.16 p275

20

1600

VD4 24.16.20 p275

25

1600

VD4 24.16.25 p275

31.5

1600

VD4 24.16.32 p275

16

2000

VD4 24.20.16 p275

20

2000

VD4 24.20.20 p275

25

2000

VD4 24.20.25 p275

31.5

2000

VD4 24.20.32 p275

25

2500

VD4 24.25.25 p275

31.5

2500

VD4 24.25.32 p275

Height of the circuit-breaker.


Width of the circuit-breaker.
Depth of the circuit-breaker.
Distance between bottom and top terminal.
Distance between the bottom terminal and the resting surface of the circuit-breaker.
Pole horizontal centre distance.

VD4 fixed circuit-breaker without bottom and top terminals (36 kV)
Ur

Isc

Rated uninterrupted current (40 C) [A]


H=876
D=478.5

kV

kA

u/l=328
l/g=428.5

Circuit-breaker type

P=275
W=786

36

H
W
D
u/l
l/g
P
(*)

31.5

=
=
=
=
=
=
=

1250 A

VD4 36.12.32 p275

1600 A

VD4 36.16.32 p275

2000 A

VD4 36.20.32 p275

2500 A (* )

VD4 36.25.32 p275

Height of the circuit-breaker.


Width of the circuit-breaker.
Depth of the circuit-breaker.
Distance between bottom and top terminal.
Distance between the bottom terminal and the resting surface of the circuit-breaker.
Pole horizontal centre distance.
Contact ABB.

Standard fittings of fixed circuit-breakers


The basic versions of the fixed circuit-breakers are three-pole
and fitted with:
EL type manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton, opening pushbutton and operation
counter
set of ten auxiliary circuit-breaker break/make contacts
Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and five make contacts (signalling circuit-breaker
closed) are available.

lever for manually charging the closing springs


auxiliary circuit support terminal board.
VD4 - up to 24 kV

VD4 - 36 kV

23

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable version circuit-breakers


for UniGear ZS1 switchgear (12 kV)

Circuit-breaker

VD4/P 12 (3)
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 12

Rated insulation voltage

Us [kV] 12

Withstand voltage at 50 Hz

Ud (1 min) [kV] 28

Impulse withstand voltage

Up [kV] 75

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

(1)

Rated breaking capacity


(rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity

Isc [kA]

Ik [kA]

Ip [kA]

Operation sequence

1250

1250

1250

1250

1600

1600

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

50

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

50

40

40

50

50

50

50

63

63

63

63

80

80

80

80

100

100

125

628

691

691

691

691

691

[ O - 0.3 s - CO - 15 s - CO ]

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H [mm] 628

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

W [mm] 503

503

653

853

681

653

853

D [mm] 662

662

641

642

643

642

642

Pole distance P [mm] 150

150

210

275

210

210

275

[kg] 116

116

174

176

180

160

166

7412

7415

7416

003284

003286

003444

TN 7412
1VCD
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
(2) Up to 4000 A with forced ventilation.
(3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

24

12
12
28
75
50-60
1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

3150

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

40

50

50

50

50

50

50

50

50

50

50

63

63

63

63

80

80

80

80

100

100

100

100

100

100

125

125

125

125

125

125

691

691

691

691

691

691

691

691

691

691

730

742

653

853

681

853

653

853

681

853

853

853

853

853

641

642

643

643

642

642

643

643

640

643

640

643

210

275

210

275

210

275

210

275

275

275

275

275

174

176

180

193

160

166

190

205

186

225

221

240

7415

7416

7417

003284

003286

003444

003445

003444

003445

003446

000153

003447

(2)

3150

(2)

33 ... 60
10 ... 15
43 ... 75
60 ... 80

- 5 ... + 40

25

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable version circuit-breakers


for UniGear ZS1 switchgear (17.5 kV)

Circuit-breaker

VD4/P 17 (3)
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 17.5

Rated insulation voltage

Us [kV] 17.5

Withstand voltage at 50 Hz

Ud (1 min) [kV] 38

Impulse withstand voltage

Up [kV] 95

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

(1)

Rated breaking capacity


(rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity

Isc [kA]

Ik [kA]

Ip [kA]

Operation sequence

1250

1250

1250

1250

1600

1600

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

50

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

50

40

40

50

50

50

50

63

63

63

63

80

80

80

80

100

100

125

632

691

691

691

691

691

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H [mm] 632

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

W [mm] 503

503

653

853

681

653

853

D [mm] 664

664

641

642

643

642

642

Pole distance P [mm] 150

150

210

275

210

210

275

[kg] 116

116

174

176

180

160

166

7412

7415

7416

003284

003286

003444

TN 7412
1VCD
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
(2) Up to 4000 A with forced ventilation.
(3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

26

17,5
17,5
38
95
50-60
1600

1600

1600

1600

2000

2000

2000

2000

2500

2500

3150

20

20

20

20

25

25

25

25

31,5

31,5

31,5

31,5

40

40

40

40

40

40

50

50

50

50

50

50

20

20

20

20

25

25

25

25

31,5

31,5

31,5

31,5

40

40

40

40

40

40

50

50

50

50

50

50

50

50

50

50

63

63

63

63

80

80

80

80

100

100

100

100

100

100

125

125

125

125

125

125

691

691

691

691

691

691

691

691

691

691

730

742

653

853

681

853

653

853

681

853

853

853

853

853

641

642

643

643

642

642

643

643

640

643

640

643

210

275

210

275

210

275

210

275

275

275

275

275

174

176

180

193

160

166

190

205

186

225

221

240

7415

7416

7417

003284

003286

003444

003445

003444

003445

003446

000153

003447

(2)

3150

(2)

33 ... 60
10 ... 15
43 ... 75
60 ... 80

- 5 ... + 40

27

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable version circuit-breakers


for UniGear ZS1 switchgear (24 kV)

Circuit-breaker
Standards

VD4/P 24
IEC 62271-100
VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 24

Rated insulation voltage

Us [kV] 24

Withstand voltage at 50 Hz

Ud (1 min) [kV] 50

Impulse withstand voltage

Up [kV] 125

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

(1)

Rated breaking capacity


(rated short-circuit breaking current
symmetrical)

Isc [kA]

Rated short-time withstand current (3s)

Making capacity

Ik [kA]

Ip [kA]

Operation sequence

1600

2000

2500

(2)

3150

16

16

16

16

16

16

20

20

20

20

20

20

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

16

16

16

16

16

16

16

20

20

20

20

20

20

20

25

25

25

25

25

25

25

31.5

31.5

31.5

31.5

31.5

40

40

40

40

40

40

40

50

50

50

50

50

50

50

63

63

63

63

63

63

63

80

80

80

80

80

[O - 0.3 s - CO - 15 s - CO]

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

(3)

[ms] 60 ... 80
P P

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

28

1250

16

[ms] 33 ... 60

(1)
(2)
(3)
(4)

1250

20

Opening time

Maximum
overall
dimensions

630

H [mm] 794

794

794

794

838

838

838

838

W [mm] 653

853

653

853

853

853

853

853

D [mm] 802

802

802

802

790

790

790

790

Pole distance P [mm] 210

275

210

275

275

275

275

275

[kg] 140

148

140/146

7414

7413

000173

TN 7413
1VCD

(4)

(4)

148

228

228

228

277

7414

7418

7418

7418

000177

[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
2300 A rated current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
2700 A rated current guaranteed with natural ventilation; 3150 A rated current guaranteed with forced ventilation.
31.5 kA version.

General characteristics of withdrawable circuit-breakers


for UniGear ZS2 and PowerCube modules (36 kV)

Circuit-breaker

VD4/W 36
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 36

Rated insulation voltage

Us [kV] 36

Withstand voltage at 50 Hz

Ud (1 min) [kV] 70

Impulse withstand voltage

Up [kV] 170

Rated frequency

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 1250

(1)

Rated breaking capacity


(rated short-circuit breaking current symmetrical)

Rated short-time withstand current (3s)

Making capacity
Operation sequence

1600

2000

2500 (*)

31,5

31,5

31,5

31,5

31,5

31,5

Ip [kA] 80

80

80

80

Isc [kA] 31,5

Ik [kA] 31,5

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 45 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

H [mm] 973

973

973

973

W [mm] 842

842

842

842

D [mm] 788

788

788

788

Pole distance P [mm] 275

275

275

275

[kg] 230

230

230

1VYN300901-KG

1VYN300901-KG

TN 1VYN300901-KG
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(*) Ask ABB

29

2. Selection and ordering



Withdrawable circuit-breakers

Types of withdrawable version circuit-breakers available for UniGear ZS1 switchgear


Complete the circuit-breaker selected with the optional accessories indicated on the following pages.

VD4 (12 kV) withdrawable circuit-breaker


Ur

kV

12

W =
P =
u/l =
=

30

Isc

kA

Rated uninterrupted current (40 C) [A]


W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

=35

=79

=79

=109

=109

Circuit-breaker type

16

630

VD4/P 12.06.16 p150

20

630

VD4/P 12.06.20 p150

25

630

VD4/P 12.06.25 p150

31.5

630

VD4/P 12.06.32 p150

16

1250

VD4/P 12.12.16 p150

20

1250

VD4/P 12.12.20 p150

25

1250

VD4/P 12.12.25 p150

31.5

1250

VD4/P 12.12.32 p150

40

1250

VD4/P 12.12.40 p210

50

1250

VD4/P 12.12.50 p210

20

1600

VD4/P 12.16.20 p210

25

1600

VD4/P 12.16.25 p210

31.5

1600

VD4/P 12.16.32 p210

40

1600

VD4/P 12.16.40 p210

50

1600

VD4/P 12.16.50 p210

20

2000

VD4/P 12.20.20 p210

25

2000

VD4/P 12.20.25 p210

31.5

2000

VD4/P 12.20.32 p210

40

2000

VD4/P 12.20.40 p210

50

2000

VD4/P 12.20.50 p210

40

1250

VD4/P 12.12.40 p275

20

1600

VD4/P 12.16.20 p275

25

1600

VD4/P 12.16.25 p275

31.5

1600

VD4/P 12.16.32 p275

40

1600

VD4/P 12.16.40 p275

50

1600

VD4/P 12.16.50 p275

20

2000

VD4/P 12.20.20 p275

25

2000

VD4/P 12.20.25 p275

31.5

2000

VD4/P 12.20.32 p275

40

2000

VD4/P 12.20.40 p275

50

2000

VD4/P 12.20.50 p275

Width of the circuit-breaker.


Pole horizontal centre distance.
Distance between bottom and top terminal.
Diameter of the isolating contact.

VD4 (12 kV) withdrawable circuit-breaker


Ur

kV

12

Isc

kA

Rated uninterrupted current (40 C) [A]


W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

=35

=79

=79

=109

=109

Circuit-breaker type

20

2500

VD4/P 12.25.20 p275

25

2500

VD4/P 12.25.25 p275

31,5

2500

VD4/P 12.25.32 p275

40

2500

VD4/P 12.25.40 p275

50

2500

VD4/P 12.25.50 p275

20

3150 (1)

VD4/P 12.32.20 p275

25

3150

(1)

VD4/P 12.32.25 p275

31,5

3150

(1)

VD4/P 12.32.32 p275

40

3150

(1)

VD4/P 12.32.40 p275

50

3150

(1)

VD4/P 12.32.50 p275

W = Width of the circuit-breaker.


P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.

31

2. Selection and ordering



Withdrawable circuit-breakers

VD4 (17.5 kV) withdrawable circuit-breaker for UniGear ZS1 switchboard


Ur

kV

17.5

W =
P =
u/l =
=

32

Isc

kA

Rated uninterrupted current (40 C) [A]


W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

=35

=79

=79

=109

=109

Circuit-breaker type

16

630

VD4/P 17.06.16 p150

20

630

VD4/P 17.06.20 p150

25

630

VD4/P 17.06.25 p150

31.5

630

VD4/P 17.06.32 p150

16

1250

VD4/P 17.12.16 p150

20

1250

VD4/P 17.12.20 p150

25

1250

VD4/P 17.12.25 p150

31.5

1250

VD4/P 17.12.32 p150

40

1250

VD4/P 17.12.40 p210

50

1250

VD4/P 17.12.50 p210

20

1600

VD4/P 17.16.20 p210

25

1600

VD4/P 17.16.25 p210

31.5

1600

VD4/P 17.16.32 p210

40

1600

VD4/P 17.16.40 p210

50

1600

VD4/P 17.16.50 p210

20

2000

VD4/P 17.20.20 p210

25

2000

VD4/P 17.20.25 p210

31.5

2000

VD4/P 17.20.32 p210

40

2000

VD4/P 17.20.40 p210

50

2000

VD4/P 17.20.50 p210

40

1250

VD4/P 17.12.40 p275

20

1600

VD4/P 17.16.20 p275

25

1600

VD4/P 17.16.25 p275

31.5

1600

VD4/P 17.16.32 p275

40

1600

VD4/P 17.16.40 p275

50

1600

VD4/P 17.16.50 p275

20

2000

VD4/P 17.20.20 p275

25

2000

VD4/P 17.20.25 p275

31.5

2000

VD4/P 17.20.32 p275

40

2000

VD4/P 17.20.40 p275

50

2000

VD4/P 17.20.50 p275

Width of the circuit-breaker.


Pole horizontal centre distance.
Distance between bottom and top terminal.
Diameter of the isolating contact.

VD4 (17.5 kV) withdrawable circuit-breaker for UniGear ZS1 switchboard


Ur

kV

17.5

Isc

kA

Rated uninterrupted current (40 C) [A]


W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

=35

=79

=79

=109

=109

Circuit-breaker type

20

2500

VD4/P 17.25.20 p275

25

2500

VD4/P 17.25.25 p275

31.5

2500

VD4/P 17.25.32 p275

40

2500

VD4/P 17.25.40 p275

50

2500

VD4/P 17.25.50 p275

20

3150

(1)

VD4/P 17.32.20 p275

25

3150

(1)

VD4/P 17.32.25 p275

31.5

3150

(1)

VD4/P 17.32.32 p275

40

3150

(1)

VD4/P 17.32.40 p275

50

3150

(1)

VD4/P 17.32.50 p275

W = Width of the circuit-breaker.


P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.

33

2. Selection and ordering



Withdrawable circuit-breakers

VD4 (24 kV) withdrawable circuit-breaker for UniGear ZS1 switchboard


Ur

kV

Isc

kA

W=800

W=1000

W=1000

W=1000

P=210

P=275

P=275

P=275

u/l=310

u/l=310

u/l=310

u/l=310

=35

=35

=79

=109

630

VD4/P 24.06.16 p210

20

630

VD4/P 24.06.20 p210

25

630

VD4/P 24.06.25 p210

16

1250

VD4/P 24.12.16 p210

20

1250

VD4/P 24.12.20 p210

25

1250

VD4/P 24.12.25 p210

31.5

1250

VD4/P 24.12.32 p210


630

VD4/P 24.06.16 p275

20

630

VD4/P 24.06.20 p275

25

630

VD4/P 24.06.25 p275

16

1250

VD4/P 24.12.16 p275

20

1250

VD4/P 24.12.20 p275

25

1250

VD4/P 24.12.25 p275

16

1600

VD4/P 24.16.16 p275

20

1600

VD4/P 24.16.20 p275

25

1600

VD4/P 24.16.25 p275

31.5

1600

VD4/P 24.16.32 p275

16

2000

VD4/P 24.20.16 p275

20

2000

VD4/P 24.20.20 p275

25

2000

VD4/P 24.20.25 p275

31.5

2000

VD4/P 24.20.32 p275

16

2300

(1)

VD4/P 24.25.16 p275

20

2300

(1)

VD4/P 24.25.20 p275

25

2300

(1)

VD4/P 24.25.25 p275

31.5

2300

(1)

31.5
W = Width of the switchgear.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) 2500 A rated current guaranteed with forced ventilation.
(2) 3150 A rated current guaranteed with forced ventilation.

34

Circuit-breaker type

16

16

24

Rated uninterrupted current (40 C) [A]

VD4/P 24.25.32 p275


2700

(2)

VD4/P 24.32.32 p275

VD4 (36 kV) withdrawable circuit-breaker


Ur

Isc

Rated uninterrupted current (40 C) [A]


H=951
D=788

kV

kA

u/l=380

Circuit-breaker type

=399
P=275
W=778

31.5

36

1250 A

VD4/W 36.12.32 p275

1600 A

VD4/W 36.16.32 p275

2000 A

VD4/W 36.20.32 p275

2500 A *

( )

H
D
u/l

P
W
(*)

=
=
=
=
=
=
=

VD4/W 36.25.32 p275

Height of the circuit-breaker.


Depth of the circuit-breaker.
Distance between bottom and top terminal.
Diameter of the isolating contact.
Pole horizontal centre distance.
Width of the circuit-breaker.
Contact ABB.

Standard fittings of withdrawable circuit-breakers


for UniGear ZS1, ZS2 switchgear and similar panels
The basic versions of the withdrawable circuit-breakers are
three-pole and fitted with:
EL type manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
set of ten circuit-breaker open/closed auxiliary contacts

locking electromagnet in the truck (compulsory for ABB


switchgear). This device prevents racking the circuit-breaker
into the switchgear with the auxiliary circuits disconnected
(plug not inserted in the socket)
door interlock (compulsory for ABB switchgear); this device
prevents racking the circuit-breaker into the switchgear
when the switchgear door is open.

Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and four make contacts (signalling circuit-breaker closed)
are available.

lever for manually charging the closing springs


isolating contacts
cord with connector (plug only) for auxiliary circuits, with
striker pins which does not allow the plug to be inserted
into the socket if the rated current of the circuit-breaker is
lower than the rated current of the panel
racking-out/in lever (the quantity must be defined according
to the number of pieces of apparatus ordered)

VD4 up to 24 kV

VD4 - 36 kV

35

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable version circuit-breakers


for PowerCube modules (12 kV)

Circuit-breaker

VD4/P 12 ( 3)

VD4/W 12 (3)

PowerCube module PB1

PB2

IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency

Ur [kV] 12

12

Us [kV] 12

12

Ud (1 min) [kV] 28

28

Up [kV] 75

75

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

(1)

Rated breaking capacity


(rated short-circuit breaking
current symmetrical)

Isc [kA]

Rated short-time
withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

50-60
1250

630

1250

16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

50

50

50

50

63

63

63

63

80

80

80

80

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

60 ... 80

H [mm] 628

628

691

691

W [mm] 503

503

653

853

D [mm] 662

662

642

642

Pole distance P [mm] 150

150

210

210

[kg] 116

116

135

135

7412

7420

7420

TN 7412
1VCD
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1

IEC: 62271-1

(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature
(2) Up to 4000 A with forced ventilation.
(3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

36

- 5 ... + 40

VD4/P 12

VD4/W 12

PB2

PB3

PB3

12

12

12

12

12

12

28

28

28

75

75

75

50-60

50-60

50-60

1250

1250

1600

1600

1600

2000

2000

2500

2500

3150

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

50

50

50

50

50

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

50

50

50

50

50

50

50

50

50

63

63

63

63

80

80

80

80

100

100

100

100

100

125

125

125

125

125

33 ... 60

33 ... 60

33 ... 60

10 ... 15

10 ... 15

10 ... 15

43 ... 75

43 ... 75

43 ... 75

60 ... 80

60 ... 80

60 ... 80

(2)

3150 (2)

691

691

691

691

691

690

691

691

691

730

691

653

681

653

653

681

653

681

853

853

853

853

641

643

642

641

643

642

643

640

643

640

643

210

210

210

210

210

210

210

275

275

275

275

174

180

160

174

180

160

190

186

225

221

240

7415

7415

7417

003284

003444

003284

003444

003444

003445

000152

003596

- 5 ... + 40

- 5 ... + 40

- 5 ... + 40

37

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable version circuit-breakers


for PowerCube modules (17.5 kV)

Circuit-breaker

VD4/P 17 ( 3)

VD4/W 17 (3)

PowerCube module PB1

PB2

IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency

Ur [kV] 17.5

17.5

Us [kV] 17.5

17.5

Ud (1 min) [kV] 38

38

Up [kV] 95

95

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

(1)

Rated breaking capacity


(rated short-circuit breaking
current symmetrical)

Isc [kA]

Rated short-time
withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

Operation sequence

50-60
1250

630

1250

16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

16

16

16

16

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

50

50

50

50

63

63

63

63

80

80

80

80

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

60 ... 80

H [mm] 628

628

691

W [mm] 503

503

653

853

D [mm] 662

662

642

642

Pole distance P [mm] 150

150

210

210

[kg] 116

116

135

135

7412

7420

7420

TN 7412
1VCD
[C] - 5 ... + 40

- 5 ... + 40

IEC: 60068-2-30, 60721-2-1

IEC: 62271-1

(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature.
(2) Up to 4000 A with forced ventilation.
(3) Circuit-breakers up to 1250 A and 31.5 kA have polyamide poles.

38

691

VD4/P 17

VD4/W 17

PB2

PB3

PB3

17,5

17,5

17,5

17,5

17,5

17,5

38

38

38

95

95

95

50-60

50-60

50-60

1250

1250

1600

1600

1600

2000

2000

2500

2500

3150

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

50

50

50

50

50

20

20

20

20

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

50

50

50

50

50

50

50

50

50

63

63

63

63

80

80

80

80

100

100

100

100

100

125

125

125

125

125

(2)

33 ... 60

33 ... 60

33 ... 60

10 ... 15

10 ... 15

10 ... 15

43 ... 75

43 ... 75

43 ... 75

60 ... 80

60 ... 80

3150

(2)

60 ... 80

691

691

691

691

691

690

691

691

691

691

730

653

681

653

653

681

653

681

853

853

853

853

641

643

642

641

643

642

643

640

643

643

640

210

210

210

210

210

210

210

275

275

275

275

174

180

160

174

180

160

190

186

225

240

221

7415

7415

7417

003284

003444

003284

003444

003444

003445

003596

000152

- 5 ... + 40

- 5 ... + 40

- 5 ... + 40

39

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable version circuit-breakers


for PowerCube modules (24 kV)

Circuit-breaker

VD4/P 24
PowerCube module PB4

Standards

PB5

IEC 62271-100

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage

Ur [kV] 24

24

Us [kV] 24

24

Ud (1 min) [kV] 50

50

Up [kV] 125

Rated frequency

125

fr [Hz] 50-60

Rated normal current (40 C)

Ir [A] 630

(1)

Rated breaking capacity


(rated short-circuit breaking
current symmetrical)

Isc [kA]

Rated short-time
withstand current (3s)

Ik [kA]

Making capacity

Ip [kA]

1600

16

16

16

16

20

20

20

20

25

25

25

25

25

31.5

31.5

31.5

31.5

16

16

16

16

16

20

20

20

20

20

25

25

25

25

25

31.5

31.5

31.5

31.5

40

40

40

40

40

50

50

50

50

50

63

63

63

63

63

80

80

80

80

Opening time

[ms] 33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

60 ... 80

H [mm] 794

794

838

838

838

W [mm] 653

653

853

853

853

D [mm] 802

802

790

790

790

275

275

275

228

228

228

7418

7418

7418

Pole distance P [mm] 210


[kg] 140
TN 7413
1VCD

210
140/146

(3)

7413
000173

(3)

[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1

(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature.
(2) 2300 A rated uninterrupted current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
(3) 31.5 kA version.

40

2500

16

[O - 0.3 s - CO - 15 s - CO]

P P

2000

20

Operation sequence

50-60
1250

(2)

Types of withdrawable version circuit-breakers available for PowerCube modules


Complete the circuit-breaker selected with the optional accessories indicated on the following pages.
VD4 withdrawable circuit-breaker (12 kV)
Ur

kV

12

Isc

kA

Rated uninterrupted current (40 C) [A]


W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

=35

=79

=79

=109

=109

Circuit-breaker type

16

630

VD4/P 12.06.16 p150

20

630

VD4/P 12.06.20 p150

25

630

VD4/P 12.06.25 p150

31.5

630

VD4/P 12.06.32 p150

16

1250

VD4/P 12.12.16 p150

20

1250

VD4/P 12.12.20 p150

25

1250

VD4/P 12.12.25 p150

31.5

1250

VD4/P 12.12.32 p150

16

630

VD4/W 12.06.16 p210

20

630

VD4/W 12.06.20 p210

25

630

VD4/W 12.06.25 p210

31.5

630

VD4/W 12.06.32 p210

16

1250

VD4/W 12.12.16 p210

20

1250

VD4/W 12.12.20 p210

25

1250

VD4/W 12.12.25 p210

31.5

1250

VD4/W 12.12.32 p210

40

1250

VD4/P 12.12.40 p210

50

1250

VD4/P 12.12.50 p210

20

1600

VD4/P 12.16.20 p210

25

1600

VD4/P 12.16.25 p210

31.5

1600

VD4/P 12.16.32 p210

40

1600

VD4/P 12.16.40 p210

50

1600

VD4/P 12.16.50 p210

20

2000

VD4/P 12.20.20 p210

25

2000

VD4/P 12.20.25 p210

31.5

2000

VD4/P 12.20.32 p210

40

2000

VD4/P 12.20.40 p210

50

2000

VD4/P 12.20.50 p210

20

2500

VD4/P 12.25.20 p275

25

2500

VD4/P 12.25.25 p275

31.5

2500

VD4/P 12.25.32 p275

40

2500

VD4/P 12.25.40 p275

50

2500

VD4/P 12.25.50 p275

20

3150 (1)

VD4/W 12.32.20 p275

25

3150

(1)

VD4/W 12.32.25 p275

31.5

3150

(1)

VD4/W 12.32.32 p275

40

3150

(1)

VD4/W 12.32.40 p275

50

3150

(1)

VD4/W 12.32.50 p275

W = Width of the switchgear.


P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.

41

2. Selection and ordering



Withdrawable circuit-breakers

VD4 withdrawable circuit-breaker (17.5 kV)


Ur

kV

17,5

Isc

kA

Rated uninterrupted current (40 C) [A]


W=650

W=800

W=1000

W=1000

W=1000

P=150

P=210

P=275

P=275

P=275

u/l=205

u/l=310

u/l=310

u/l=310

u/l=310

=35

=79

=79

=109

=109

16

630

VD4/P 17.06.16 p150

20

630

VD4/P 17.06.20 p150

25

630

VD4/P 17.06.25 p150

31.5

630

VD4/P 17.06.32 p150

16

1250

VD4/P 17.12.16 p150

20

1250

VD4/P 17.12.20 p150

25

1250

VD4/P 17.12.25 p150

31.5

1250

VD4/P 17.12.32 p150

16

630

VD4/W 17.06.16 p210

20

630

VD4/W 17.06.20 p210

25

630

VD4/W 17.06.25 p210

31.5

630

VD4/W 17.06.32 p210

16

1250

VD4/W 17.12.16 p210

20

1250

VD4/W 17.12.20 p210

25

1250

VD4/W 17.12.25 p210

31.5

1250

VD4/W 17.12.32 p210

40

1250

VD4/P 17.12.40 p210

50

1250

VD4/P 17.12.50 p210

20

1600

VD4/P 17.16.20 p210

25

1600

VD4/P 17.16.25 p210

31.5

1600

VD4/P 17.16.32 p210

40

1600

VD4/P 17.16.40 p210

50

1600

VD4/P 17.16.50 p210

20

2000

VD4/P 17.20.20 p210

25

2000

VD4/P 17.20.25 p210

31.5

2000

VD4/P 17.20.32 p210

40

2000

VD4/P 17.20.40 p210

50

2000

VD4/P 17.20.50 p210

20

2500

VD4/P 17.25.20 p275

25

2500

VD4/P 17.25.25 p275

31.5

2500

VD4/P 17.25.32 p275

40

2500

VD4/P 17.25.40 p275

50

2500

VD4/P 17.25.50 p275

20

3150

(1)

25

3150

(1)

VD4/W 17.32.25 p275

31.5

3150

(1)

VD4/W 17.32.32 p275

40

3150

(1)

VD4/W 17.32.40 p275

50

3150

(1)

VD4/W 17.32.50 p275

W = Width of the switchgear.


P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.

42

Circuit-breaker type

VD4/W 17.32.20 p275

VD4 withdrawable circuit-breaker (24 kV)


Ur

kV

Isc

kA

W=800

W=1000

P=210

P=275

u/l=310

u/l=310

=35

=79

Circuit-breaker type

16

630

VD4/P 24.06.16 p210

20

630

VD4/P 24.06.20 p210

25

630

VD4/P 24.06.25 p210

16

1250

VD4/P 24.12.16 p210

20

1250

VD4/P 24.12.20 p210

25

1250

VD4/P 24.12.25 p210

31.5

1250

16
24

Rated uninterrupted current (40 C) [A]

VD4/P 24.12.32 p210


1600

VD4/P 24.16.16 p275

20

1600

VD4/P 24.16.20 p275

25

1600

VD4/P 24.16.25 p275

31.5

1600

VD4/P 24.16.32 p275

16

2000

VD4/P 24.20.16 p275

20

2000

VD4/P 24.20.20 p275

25

2000

VD4/P 24.20.25 p275

31.5

2000

16

2300

(1)

VD4/P 24.20.32 p275


VD4/P 24.25.16 p275

20

2300

(1)

VD4/P 24.25.20 p275

25

2300

(1)

VD4/P 24.25.25 p275

31.5

2300

(1)

VD4/P 24.25.32 p275

W = Width of the switchgear.


P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 2500 A rated current guaranteed with forced ventilation.

Standard fittings of withdrawable circuit-breakers


for PowerCube modules
The basic versions of the withdrawable circuit-breakers are
always three-pole and fitted with:
EL type manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
set of ten circuit-breaker open/closed auxiliary contacts

racking-in/out lever (the quantity must be defined according


to the number of pieces of apparatus ordered)
locking electromagnet in the truck. This prevents the
circuit-breaker being racked into the panel with the auxiliary
circuits disconnected (plug not inserted in the socket).
door interlock (compulsory for ABB switchgear); this device
prevents racking the circuit-breaker into the switchgear
when the switchgear door is open.

Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and four make contacts (signalling circuit-breaker closed)
are available.

lever for manually charging the closing springs


isolating contacts
cord with connector (plug only) for auxiliary circuits, with
striker pin which does not allow the plug to be inserted
into the socket if the rated current of the circuit-breaker is
different from the rated current of the panel

43

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable circuit-breakers for ZS8.4


type switchgear (12 - 17.5 - 24 kV)

Circuit-breaker

VD4/Z8
Panel without partitions
Panel with partitions
Preussen Elektra - EON

(2)

Width [mm] 650

650

650

650

800

800

Depth [mm] 1000

1000

1000

1000

1200

1200

IEC 62271-100

Standards

VDE 0671

Rated voltage

Ur [kV] 12

12

17.5

17.5

24

24

Rated insulation voltage

Us [kV] 12

12

17.5

17.5

24

24

Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency

Ud (1 min) [kV] 28

28

38

38

50

50

Up [kV] 75

75

95

95

125

125
1250

fr [Hz] 50-60

Rated normal current (40 C)

(1)

Rated breaking capacity


(rated symmetrical
short-circuit current)
Rated short-time
withstand current(3 s)

Making capacity
Operation sequence

Ir [A] 630

1250

630

1250

630

16

16

Isc [kA] 20

20

20

20

20

20

25

25

25

25

25

25

16

16

Ik [kA] 20

20

20

20

20

20

25

25

25

25

25

25

40

40

Ip [kA] 50

50

50

50

50

50

63

63

63

63

63

63

[O-0.3s-CO-15s-CO]

Opening time

[ms] 33...60

Arcing time

[ms] 10...15

Total breaking time

[ms] 43...75

Closing time

[ms] 60...80
P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalisation
Electromagnetic compatibility

H [mm] 579

579

579

579

680

680

W [mm] 503

503

503

503

653

653

D [mm] 548

548

548

548

646

646

Pole distance P [mm] 150

150

150

150

210

210

[kg] 116

116

116

116

140

140

000137

000137

000137

000089

000138

1VCD 000092
[C] 5 ... + 40
IEC 60068-2-30
IEC 60721-2-1
IEC 62271-1

(1) Rated current guaranteed with circuit-breaker installed in switchgear with 40 C ambient temperature.
(2) Special type with device for charging the closing spring by means of a rotary handle outside the operating mechanism.

44

VD4/ZT8

VD4/ZS8

650

650

650

650

800

800

650

650

800

800

1200

1200

1200

1200

1200

1200

1200

1200

1200

1200

12

12

17.5

17.5

24

24

12

12

24

24

12

12

17.5

17.5

24

24

12

12

24

24

28

28

38

38

50

50

28

28

50

50

75

75

95

95

125

125

75

75

125

125

50-60

50-60

630

1250

630

1250

630

1250

630

1250

630

1250

16

16

16

16

20

20

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

25

25

16

16

16

16

20

20

20

20

20

20

20

20

20

20

25

25

25

25

25

25

25

25

25

25

40

40

40

40

50

50

50

50

50

50

50

50

50

50

63

63

63

63

63

63

63

63

63

63

33...60

40...60

10...15

10...15

43...75

50...75

60...80

60...80

579

579

579

579

680

680

579

579

680

680

503

503

503

503

653

653

503

503

653

653

638

638

638

638

646

646

638

638

646

646

150

150

150

150

210

210

150

150

210

210

116

116

116

116

140

140

116

116

140

140

000093

000134

000134

000134

000090

000136

000091

000133

000088

000135

5 ... + 40

5 ... + 40

45

2. Selection and ordering



Withdrawable circuit-breakers

VD4/ZS8 - VD4/ZT8 - VD4/Z8 withdrawable circuit-breaker for ZS8.4 switchgear


Ur

kV

12

17.5

Isc

kA

Rated uninterrupted current (40C) [A]


Panel without partition

Panel with partition

Special panel EON

W = 650

W = 800

W = 650

W = 800

W = 650

W = 800

P = 150

P = 210

P = 150

P = 210

P = 150

P = 210

u/l = 205

u/l = 310

u/l = 205

u/l = 310

u/l = 205

u/l = 310

= 35

= 35

= 35

= 35

= 35

= 35

20

630

VD4/Z8 12.06.20 p150

25

630

VD4/Z8 12.06.25 p150

20

1250

VD4/Z8 12.12.20 p150

25

1250

VD4/Z8 12.12.25 p150

20

630

VD4/ZT8 12.06.20 p150

25

630

VD4/ZT8 12.06.25 p150

20

1250

VD4/ZT8 12.12.20 p150

25

1250

VD4/ZT8 12.12.25 p150

20

630

VD4/ZS8 12.06.20 p150

25

630

VD4/ZS8 12.06.25 p150

20

1250

VD4/ZS8 12.12.20 p150

25

1250

VD4/ZS8 12.12.25 p150

20

630

VD4/Z8 17.06.20 p150

25

630

VD4/Z8 17.06.25 p150

20

1250

VD4/Z8 17.12.20 p150

25

1250

VD4/Z8 17.12.25 p150

20

630

25

630

VD4/ZT8 17.06.25 p150

1250

VD4/ZT8 17.12.20 p150

25

W =
P =
u/l =
=

46

VD4/ZT8 17.06.20 p150

20
16

24

Circuit-breaker type

1250

VD4/ZT8 17.12.25 p150

630

VD4/Z8 24.06.16 p210

20

630

VD4/Z8 24.06.20 p210

25

630

VD4/Z8 24.06.25 p210

16

1250

VD4/Z8 24.12.16 p210

20

1250

VD4/Z8 24.12.20 p210

25

1250

VD4/Z8 24.12.25 p210

16

630

VD4/ZT8 24.06.16 p210

20

630

VD4/ZT8 24.06.20 p210

25

630

VD4/ZT8 24.06.25 p210

16

1250

VD4/ZT8 24.12.16 p210

20

1250

VD4/ZT8 24.12.20 p210

25

1250

VD4/ZT8 24.12.25 p210

16

630

VD4/ZS8 24.06.16 p210

20

630

VD4/ZS8 24.06.20 p210

25

630

VD4/ZS8 24.06.25 p210

16

1250

VD4/ZS8 24.12.16 p210

20

1250

VD4/ZS8 24.12.20 p210

25

1250

VD4/ZS8 24.12.25 p210

Width of the switchgear.


Pole horizontal centre distance.
Distance between bottom and top terminal.
Diameter of the isolating contact.

Standard fittings of withdrawable circuit-breakers for


ZS8.4 switchgear
The basic versions of the withdrawable circuit-breakers are
three-pole and fitted with:
EL type manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
set of ten circuit-breaker open/closed auxiliary contacts
Note: with the group of ten auxiliary contacts supplied as standard and the

maximum number of electrical applications, three break contacts (signalling


circuit-breaker open) and four make contacts (signalling circuit-breaker
closed) are available.

lever for manually charging the closing springs incorporated


in the operating mechanism for VD4/Z8 and VD4/ZT8,
external with rotary movement for VD4/ZS8
isolating contacts
racking in/out lever (the quantity must be defined according
to the number of pieces of apparatus ordered)
VD4/ZS8 (Preussen Elektra-EON version)
device for closing spring charging, with the door closed,
by means of a removable rotary crank handle outside the
operating mechanism and the switchgear
Harting 64-pin socket with mechanical interlock which
prevents traverse of the circuit-breaker when the plug is not
inserted in the socket
interlock with the door which prevents the spring charging
lever when the circuit-breaker is closed
interlock with the door and Harting 64 pin socket which
prevents door closing when the plug is not inserted in the
socket.

Caption
1) Spring charging device with rotary crank handle
2) Harting 64 plus socket with mechanical interlock which prevents traverse
when the socket is not inserted
3) Door - socket - spring charging device interlock (only VD4/ZS8 version)

VD4/Z8 - VD4/ZT8
Harting 64-pin socket with mechanical interlock which
prevents traverse of the circuit-breaker when the plug is not
inserted in the socket.

47

2. Selection and ordering



Withdrawable circuit-breakers

Withdrawable circuit-breakers for UniSwitch


switchgear (CBW type unit) and UniMix switchgear
P1/E type unit) (24 kV)

Circuit-breaker

VD4/US 24

Standards

VD4/US 24

(3)

(4)

UniSwitch (unit CBW type)

UniMix (unit P1/E type)

IEC 62271-100

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 24

24

24

24

Rated insulation voltage

Us [kV] 24

24

24

24

Ud (1 min) [kV] 50

50

50

50
125

Withstand voltage at 50 Hz
Impulse withstand voltage

Up [kV] 125

Rated frequency
Rated normal current (40 C)

(1)

Rated breaking capacity


(rated symmetrical short-circuit current)

Rated short-time
withstand current (3 s)

(2)

125

125

fr [Hz] 50-60

50-60

50-60

50-60

Ir [A] 630

1250

630

1250

16 (20)

(5)

16 (25)

(5)

16

16

Isc [kA] 20 (25)

(5)

20 (25)

(5)

20

20

(5)

16 (25)

(5)

16

16

Ik [kA] 20 (25)

(5)

20 (25)

(5)

20

20

25

25

40 (50)

(5)

40 (50)

(5)

40

40

Ip [kA] 50 (63)

(5)

50 (63)

(5)

Operation sequence

25

16 (20)

Making capacity

25

[O - 0.3 s - CO - 15 s - CO]

50

50

63

63

Opening time

[ms] 33 ... 60

33 ... 60

33 ... 60

33 ... 60

Arcing time

[ms] 10 ... 15

10 ... 15

10 ... 15

10 ... 15

Total breaking time

[ms] 43 ... 75

43 ... 75

43 ... 75

43 ... 75

Closing time

[ms] 60 ... 80

60 ... 80

60 ... 80

60 ... 80

P P

Maximum
overall
dimensions

H
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1)
(2)
(3)
(4)
(5)

48

H [mm] 680

680

680

680

W [mm] 653

653

653

653

D [mm] 742

742

742

742

Pole distance P [mm] 210

210

210

210

[kg] 125

125

125

125

000047

000047

000047

- 5 ... + 40

- 5 ... + 40

- 5 ... + 40

IEC: 60068-2-30, 60721-2-1

IEC 62271

1VCD 000047
[C] - 5 ... + 40

Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 C ambient temperature
The value and duration of the rated short-time withstand current depends on the switchgear. See the specific catalogues of the UniSwitch and UniMix switchgear
The top shutter activation wheels of the UniSwitch switchgear (CBW unit) are mounted and adjusted by the manufacturer of the UniSwitch switchgear
The top shutter activation wheels of the UniMix switchgear (P1/E unit) are available on request
The values in brackets refer to the 12 kV rated voltage.

Withdrawable c.-breaker for UniSwitch switchgear (CBW type unit) and UniMix switchgear (P1/E type unit)
Ur

kV

24

Isc

kA

Rated uninterrupted current (40 C) [A]


UniSwitch CBW

UniMix P1/E

P=210

P=210

u/l=310

u/l=310

=35

=79
630
630

VD4/US 24.06.20 p210

630

VD4/US 24.06.25 p210


VD4/US 24.12.16 p210

Circuit-breaker type

16

630

(1)

20

630

(1)

25

16

1250

(1)

1250

20

1250

(1)

1250

VD4/US 24.12.20 p210

25

1250

VD4/US 24.12.25 p210

VD4/US 24.06.16 p210

(1) Isc 25 kA at 12 kV.


P = Horizontal centre distance between poles.
u/l = Distance between top and bottom terminal.
= Diameter of the isolating contacts.

Standard fittings of withdrawable circuit-breakers for


UniSwitch and UniMix switchgear
The basic versions of the withdrawable circuit-breakers are
three-pole and fitted with:
EL type manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
set of ten circuit-breaker open/closed auxiliary contacts
Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and four make contacts (signalling circuit-breaker closed)
are available.

lever for manually charging the closing springs


isolating contacts
cord with connector (plug only) for auxiliary circuits, with
striker pin which does not allow the plug to be inserted
into the socket if the rated current of the circuit-breaker is
different from the rated current of the panel
racking-in/out lever (the quantity must be defined according
to the number of pieces of apparatus ordered)
locking electromagnet in the truck. This prevents the
circuit-breaker being racked into the panel with the auxiliary
circuits disconnected (plug not inserted in the socket).

49

2. Selection and ordering



Withdrawable circuit-breakers

General characteristics of withdrawable


circuit-breakers for UniSec switchgear

Circuit-breaker

VD4/SEC
IEC 62271-100

Standards

VDE 0671; CEI EN 62271-100- File 7642

Rated voltage

Ur [kV] 24

Rated insulation voltage

Us [kV] 24

Withstand voltage at 50 Hz

Ud (1 min) [kV] 50

Impulse withstand voltage

Up [kV] 125

Rated frequency
Rated normal current (40 C)

fr [Hz] 50-60
Ir [A] 630 - 1250

(1)

16

Rated breaking capacity


(rated symmetrical short-circuit current)

Isc [kA] 20
25
16

Rated short-time
withstand current (3 s)

Ik [kA] 20
25
40

Making capacity

Ip [kA] 50
63

Opening time

[O - 0.3 s - CO - 15 s - CO]

Opening time

[ms] 33 ... 60

Arcing time

[ms] 10 ... 15

Total breaking time

[ms] 43 ... 75

Closing time

[ms] 60 ... 80
P P

Maximum overall dimensions

W [mm] 653
H

D [mm] 742
W

Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility

H [mm] 743

Pole distance P [mm] 210


[kg] 133
1VCD 000190
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC 62271

(1) Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 C ambient temperature.

50

Withdrawable circuit-breaker for UniSec switchgear


Ur

Isc

kV

kA

Rated uninterrupted current (40 C) [A]


P=210
u/l=310

Circuit-breaker type

=79
16

24

630

VD4/SEC 24.06.16 p210

20

630

VD4/SEC 24.06.20 p210

25

630

VD4/SEC 24.06.25 p210

16

1250

VD4/SEC 24.12.16 p210

20

1250

VD4/SEC 24.12.20 p210

25

1250

VD4/SEC 24.12.25 p210

P = Horizontal centre distance between poles.


u/l = Distance between top and bottom terminal.
= Diameter of the isolating contacts.

Standard fittings of withdrawable circuit-breakers for


UniSec
The basic versions of the withdrawable circuit-breakers are
three-pole and fitted with:
EL type manual operating mechanism
mechanical signalling device for closing springs charged/
discharged
mechanical signalling device for circuit-breaker open/closed
closing pushbutton
opening pushbutton
operation counter
set of ten circuit-breaker open/closed auxiliary contacts
Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and four make contacts (signalling circuit-breaker closed)
are available.

lever for manual loading of the closing spring built into the
operating mechanism
isolating contacts
cord with connector (plug only) for auxiliary circuits, with
striker pin which does not allow the plug to be inserted
into the socket if the rated current of the circuit-breaker is
different from the rated current of the panel
racking-in/out lever (the quantity must be defined according
to the number of pieces of apparatus ordered)

51

2. Selection and ordering



Optional accessories

The accessories identified with the same number are alternative to each other.

1 Shunt opening release (-MO1)

2 Additional shunt opening release (-MO2)

This allows remote opening control of the apparatus. The


release can operate both in direct and alternating current.
This release is suitable for both instantaneous and permanent
service. In the case of instantaneous service, the minimum
current impulse time must be 100 ms.
Checking functionality and continuity is only possible
using the STU device (accessory 21).

Like the shunt opening release described above, this allows


remote opening control of the apparatus and can be supplied
by a circuit completely separate from the release (-MO1).
It keeps all the electrical and operating characteristics of the
shunt opening release.
Checking functionality and continuity is only possible
using the STU device (accessory 21).

Characteristics
Un

24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V

Un

48 - 60 - 110 - 120...127 - 220...240 - V~ 50 Hz

Un

110 - 120 - 127 - 220 - 240 - V~ 60 Hz

Operating limits

70 110 % Un

Power on inrush (Ps)

DC 200 W; AC = 200 VA

Inrush duration

approx. 100 ms

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Opening time

40...60 ms

Closing time

(1)

(2)

Insulation voltage
(1)
(2)

Valid for -MO1 e -MO2.


Valid for -MC.

52

40...80 ms
2000 V 50 Hz (for 1 min)

3 Opening solenoid (-MO3)

4 Shunt closing release (-MC)

The opening solenoid (-MO3) is a special release with


demagnetisation to be combined with an overcurrent protection
relay of the self-supplied type.
It is located in the operating mechanism (in the left side piece) and
is not alternative to the additional shunt opening release (-MO2).
It is not available for 40 and 50 kA circuit-breakers.
Should the application of this accessory be required, specify
the request at the time of order since subsequent application
by the customer is not possible.

This allows remote closing control of the apparatus.


The release can operate both in direct and alternating current.
This release is suitable both for instantaneous and permanent
service.
In the case of instantaneous service, the minimum current
impulse time must be 100 ms.
Use of the permanently supplied release is recommended to carry
out the electrical anti-pumping function.
It keeps all the electrical and operating characteristics of the
shunt opening release.
Checking functionality and continuity is only possible
using the STU device (accessory 21).

Note: for combination with the protection relays, please ask for the
document: Data sheet 1VCD600854.

53

2. Selection and ordering



Optional accessories

5 Undervoltage release (-MU)

The undervoltage release is available in the following versions:


5A Undervoltage release with power supply branched on the
supply side.
5B Undervoltage release with electronic time delay - KT (0.5
- 1 - 1.5 - 2 - 3s) (power supply branched on the supply
side). This device is set at 0.5s (for adjustment, please
see the Electric Circuit Diagram chapter).
Characteristics
Un

24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V

Un

48 - 60 - 110 - 120 - 127 - 220...240 V~ 50 Hz

Un

110 - 120...127 - 220...240 V~ 60 Hz

Operating limits

The undervoltage release opens the circuit-breaker when


there is notable lowering or lack of its power supply. It can
be used for remote trip (by means of normally closed type
pushbuttons), lock on closing or to control the voltage in the
auxiliary circuits.
The circuit-breaker can only close with the release supplied
(the closing lock is made mechanically).
The release can operate both in direct and alternating current.
Note
As an alternative to the undervoltage release, an additional
shunt opening release (-MO4) with the same electrical and
operating specifications as shunt opening release (-MO1) can
be installed on request.
Warning! Installation of the additional shunt opening release
(-MO4) requires a special mounting plate for releases.
Moreover, application (-MO4) must be requested at the time
of order and not afterwards.

54

circuit-breaker opening: 35-70% Un


circuit-breaker closing: 85-110% Un

Power on inrush (Ps)

DC 200 W; AC = 200 VA

Inrush duration

approx. 100 ms

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Opening time

60...80 ms

Insulation voltage

2000 V 50 Hz (for 1 min)

5a Electronic time delay device (-KT)

6 Undervoltage release mechanical override

The electronic time delay device must be mounted externally


in relation to the circuit-breaker. It allows release trip delay
with established and adjustable times.
The use of the undervoltage release is recommended in order
to prevent trips when the power supply network of the release
may be subject to cuts or voltage drops of short duration.
If it is not supplied, circuit-breaker closing is disabled.
The time delay device must be combined with an
undervoltage release for d.c.
Rated voltage of the undervoltage release must be within the
selected range of working of the time-delay device.

This is a mechanical device which allows the undervoltage


release trip to be temporarily excluded.
It is always fitted with electrical signalling.
Should the application of this accessory be required,
specify the request at the time of order since subsequent
application by the customer is not possible.

Characteristics of the time-delay device

Un

24...30 - 48 - 60 - 110...127 - 220...250 V

Un

48 - 60 - 110...127 - 220...240 - V~ 50/60 Hz

Adjustable opening time (release + time delay device): 0.5-1-1.5-2-3 sec

55

2. Selection and ordering



Optional accessories

7 Circuit-breaker auxiliary contacts (-BB1; -BB2; -BB3)

General characteristics
Insulation voltage according
to VDE 0110 standard. Group C

660 V a.c.
800 V d.c.

Rated voltage

24 V ... 660 V a.c.

Test voltage

2 kV 50 Hz (for 1 min)

Rated overcurrent

10 A

Number of contacts

Contact run

6 mm ... 7 mm

Activation force

26 N

Resistance

3 m

Storage temperature

20 C ... +120 C

Operating temperature

20 C ... +70 C

Contact overtemperature

20 K

Number of cycles

30.000

Unlimited breaking capacity if used with 10 A fuse in series

Electrical signalling of circuit-breaker open/closed can be


provided with a set of 15 auxiliary contacts as an alternative
to the 10 provided as standard.
Note
With the group of ten auxiliary contacts supplied as standard
and the maximum number of electrical applications, three
break contacts (signalling circuit-breaker open) and five make
contacts (signalling circuit-breaker closed) are available.
With the group of 15 auxiliary contacts, according to the
electrical applications required, the following are available:
for fixed circuit-breakers: thirteen auxiliary contacts,
differently divided between break contacts and make
contacts according to the figure selected of the electrical
diagram;
for withdrawable circuit-breakers, since the plug of the
auxiliary circuits has a limited number of poles: five break
contacts (signalling circuit-breaker open) and five make
contacts (signalling circuit-breaker closed).

Electrical characteristics
Un

Rated current

Breaking capacity

220 V a.c.

Cosj = 0.7

2.5 A

25 A

380 V a.c.

Cosj = 0.7

1.5 A

15 A

500 V a.c.

Cosj = 0.7

1.5 A

15 A

660 V a.c.

Cosj = 0.7

1.2 A

12 A

1 ms

10 A

12 A

15 ms

10 A

12 A

50 ms

8A

10 A

200 ms

6A

7.7 A

1 ms

8A

10 A

24 V d.c.

60 V d.c.

110 V d.c.

220 V d.c.

56

15 ms

6A

8A

50 ms

5A

6A

200 ms

4A

5.4 A

1 ms

6A

8A

15 ms

4A

5A

50 ms

2A

4.6 A

200 ms

1A

2.2 A

1 ms

1.5 A

2A

15 ms

1A

1.4 A

50 ms

0.75 A

1.2 A

200 ms

0.5 A

1A

8 Transient contact (-BB4)

9 Position contact (-BT3)

This contact closes momentarily (duration > 30 ms) on circuitbreaker opening controlled remotely with a shunt opening
release.
The indication is not provided when opening is manual and
local. In fact, a contact (BB11) is activated by the manual
pushbutton and cuts off the transient contact closure (BB4).
The transient contact is activated directly from the main
operating shaft when the indication is provided only on actual
opening of the main circuit-breaker contacts.

This contact is used, together with the locking magnet in the


operating mechanism (-RL1) to prevent remote closing during
traverse into the unit.
It is only supplied for the withdrawable version circuit-breakers
for UniGear ZS1 switchgear and PowerCube modules.
It cannot be supplied when the transmitted contacts are
requested in the truck (-BT1; -BT2).

10 Transmitted contacts in the truck (-BT1; -BT2)

Transmitted contacts of the withdrawable circuit-breaker


(installed in the circuit-breaker truck - only for VD4/P
withdrawable circuit-breaker).
These contacts are either in addition or as an alternative to
the position contacts (for signalling circuit-breaker racked
out) located in the unit. They also carry out the function of the
position contact (-BT3).

57

2. Selection and ordering



Optional accessories

11 Motor operator (-MS)

12 C ontact for signalling closing spring charged/


discharged (-BS2)

This carries out automatic charging of the circuit-breaker


operating mechanism closing spring. After circuit-breaker
closing, the geared motor immediately recharges the closing
springs.
In the case of a power cut or during maintenance work,
the closing spring can be charged manually in any case
(by means of the special crank handle incorporated in the
operating mechanism).

This consists of a microswitch which allows remote signalling


of the state of the circuit-breaker operating mechanism
closing pring.
The following signals are possible:
contact open: signalling spring charged
contact closed: signalling spring discharged.
The two signals must be used for circuits which have the
same power supply voltage.

Characteristics
Un

24...30 - 48...60 - 110...130 - 220...250 V

Un

100...130 - 220...250 V~ 50/60 Hz

Operating limits

85 110% Un
40 kA

50 kA (*)

DC = 600 W;
AC = 600 VA
DC = 200 W;
AC = 200 VA

DC = 900 W;
AC = 900 VA
DC = 350 W;
AC = 350 VA

Charging time

0,2 s

0,2 s

Charging time

6-7 s

6-7 s

Insulating voltage

2000 V 50 Hz
(for 1 min)

2000 V 50 Hz
(for 1 min)

Power on inrush (Ps)


Rated power (Pn)

(*) Not available for versions with motorized truck.

58

Protections and locks


Various mechanical and electromechanical locking and protection devices are available.

13 Opening and closing pushbutton protection

14 Opening and closing pushbutton padlock

The protection only allows the opening and closing


pushbuttons to be operated using a special tool.

The device allows the opening and closing pushbuttons to be


locked using a maximum of three padlocks (not supplied):
4 mm. Also prevents closing using remote control.
This lock is available in two versions:
14A Possibility of padlocking both the pushbuttons without
distinction
14B Separate padlocking of the opening and/or closing
pushbutton.
N.B. Lock 14A prevents closure by remote control; lock 14B does not prevent
closure by remote control.

59

2. Selection and ordering



Optional accessories

15 Key lock in open position

16 Locking magnet on the operating mechanism (-RL1)

The lock is activated by a special circular lock.


Different keys (for a single circuit-breaker) are available, or the
same keys (for several circuit-breakers).
To activate the lock, keep the opening pushbutton pressed
down, turn the key and remove it.
With the key removed, the opening pushbutton automatically
remains in the pressed position preventing local manual
closing and remote electrical closing.

Only allows activation of the command with the electromagnet


supplied.

60

Characteristics
Un

24 - 30 - 48 - 60 - 110 132 - 220 - 250 V

Un

48 - 60 - 110 - 120 ... 127 220 ... 240 V~ 50/60 Hz

Operating limits

85 110% Un

Power on inrush (Ps)

DC 250 W; AC = 250 VA

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Inrush duration

150 ms

Insulating voltage

2000 V 50 Hz (for 1 min)

17 Locking magnet on the truck (-RL2)

18 Interlock for fixed circuit-breaker

Compulsory accessory for the withdrawable versions for


UniGear ZS1 switchgear and PowerCube modules, to prevent
circuit-breaker racking into the switchgear with the auxiliary
circuit plug disconnected.
The plug also makes the anti-insertion lock for a different rated
current. Special striker pins do not allow insertion of the plug
in the socket if the rated current of the circuit-breaker is lower
than the rated current of the panel.
Note: on request, a specific version for the circuitbreakers for ZS8.4 switchgear is available.

Device for fixed circuit-breakers which are converted into


withdrawable ones by the customer. It allows a mechanical
lock to be made, by the customer, which prevents rackingout/in with the circuit-breaker closed and prevents circuitbreaker closing during translation.
Note: The device must be requested when ordering since
it must be assembled and tested in the factory.

Characteristics
Un

24 - 30 - 48 - 60 - 110 - 125 127 - 132 - 220 - 240 V

Un

24 - 30 - 48 - 60 - 110 - 125 - 127 220 - 230 ... 240 V~ 50/60 Hz

Operating limits

85 110% Un

Nominal power (Pn)

DC 250 W; AC = 250 VA

Continuous power (Pc)

DC = 5 W; AC = 5 VA

Inrush duration

150 ms

Insulating voltage

2000 V 50 Hz (for 1 min)

61

2. Selection and ordering



Optional accessories

19 M echanical interlock with the door

20 M otorised truck (-MT)

This device prevents circuit-breaker racking-in when the


switchgear door is open. It is only provided for circuitbreakers used in switchgear UniGear ZS1 and PowerCube
modules, fitted with a special actuator on the door.

It allows racking-in and racking-out of the circuit-breaker in


the switchgear to be carried out remotely, (only for circuitbreaker in withdrawable version for UniGear ZS1 and ZS8.4
switchgear and PowerCube modules).
Characteristics

62

Un

24 - 30 - 48 - 60 - 110 - 220 V

Operating limits

85 110% Un

Nominal power(Pn)

40 W

21 STU Shunt Test Unit

Due to the particular construction of these releases, checking


the functionality of the shunt closing (-MC) and opening
(-MO1, -MO2) releases is not possible with dedicated
relays (e.g. TCS Test Control Supervision, CCC Control Coil
Continuity) or with the REF control and protection unit. The
only device able to carry out a check of the functionality is the
STU device. Please contact us if you want to carry out this
control with devices other than STU.
This device can be combined with the shunt opening release
(-MO1; -MO2) or with the shunt closing release (-MC) to
check functionality and continuity.

The control/monitoring Shunt Test Unit allows the continuity


of releases with a rated operating voltage between 24 V and
250 V (AC and DC) to be checked, as well as the functionality
of the electronic circuit of the release.
Checking continuity is carried out cyclically with an interval of
20 seconds between one test and the next.
The unit has optical signals by means of LEDs on the front. In
particular the following information is indicated:
POWER ON: power supply present
(-MO) TESTING: test being carried out
TEST FAILED: signal following a failed test or in the absence
of auxiliary power supply
ALARM: signal after three failed tests.
Two relays and a changeover are also available on board the
unit, which allow remote signalling of the following two events:
failure of a test (resetting is carried out automatically when
the alarm stops)
failure of three tests (resetting is only carried out by means
of the manual - RESET from the front of the unit).
There is also a manual - RESET button on the front of the
unit.
Characteristics
Un

24 ... 250 V AC/DC

Maximum interrupted current

6A

Maximum interrupted voltage

250 V AC

63

3. Specific product characteristics

Resistance to vibrations

Galvanisation is carried out in accordance with UNI ISO 2081


Standards, classification code Fe/Zn 12, with a thickness of
12x10-6 m, protected by a conversion layer mainly consisting
of chromates in compliance with the UNI ISO 4520 Standard.
These construction characteristics mean that the whole VD4
series of circuit-breakers and its accessories comply with
climate graph 8 of the IEC 60721-2-1 and IEC 60068-2-2
(Test B: Dry Heat / IEC 60068-2-30 (Test Db: Damp Heat,
cyclic) Standards.

Altitude
The VD4 circuit-breakers are designed to satisfy high levels of
resistance to stresses caused by mechanical vibrations.
Many versions are able to satisfy both the approval criteria of the
major International Shipping Registers (DNV, Lloyds Register,
RINA) and the qualification criteria of the International Seismic
Standards (IEEE 344, IEEE 323 and IEC 60980).
For the versions approved by the shipping registers, please
contact us.

Tropicalization

VD4 circuit-breakers are manufactured in compliance with


the strictest regulations regarding use in hot-humid-saline
climates.
All the most important metal components are treated against
corrosive factors according to UNI EN 12500 Standards
environmental class C.

64

The insulating property of air decreases as the altitude


increases, therefore this must always be taken into account
for external insulation of the apparatus (the internal insulation
of the interrupters does not undergo any variations as it is
guaranteed by the vacuum).
The phenomenon must always be taken into consideration
during the design stage of the insulating components of
apparatus to be installed over 1000 m above sea level.
In this case a correction coefficient must be considered,
which can be taken from the graph on the next page, built up
on the basis of the indications in the IEC 62271-1 Standards.
The following example is a clear interpretation of the
indications given above.

Graph for determining the Ka correction factor according to the altitude


Example
Installation altitude 2000 m
Operation at the rated voltage of 12 kV
Withstand voltage at power frequency 28 kV rms
Impulse withstand voltage 75 kVp
Ka factor obtained from graph = 1.13.

kA
1,50

m=1

Ka = e m (H 1000)/8150
1,40

Considering the above parameters, the apparatus will have to


withstand (under test and at zero altitude, i.e. at sea level):
withstand voltage at power frequency equal to:
28 x 1.13 = 31.6 kVrms
impulse withstand voltage equal to:
75 x 1.13 = 84.7 kVp.

1,30

From the above, it can be deduced that for installations at an altitude


of 2000 m above sea level, with 12 kV service voltage, apparatus
must be provided with 17.5 kV rated voltage, characterised by
insulation levels at power frequency of 38 kVrms with 95 kVp impulse
withstand voltage.

1,10

1,20

1,00
1000

1500

2000

2500

3000

3500

4000 H

H = altitude in metres;
m = value referred to power frequency and the lightning impulse withstand
voltages and those between phases.

Anti-pumping device
The EL operating mechanism of VD4 circuit-breakers
(in all versions) is fitted with a mechanical anti-pumping
device which prevents re-closing due to either electrical or
mechanical commands.
Should both the closing command and any one of the
opening commands (local or remote) be active at the same
time, there would be a continuous succession of opening and
closing commands.
The anti-pumping device avoids this situation, ensuring
that each closing operation is only followed by an opening
operation and that there is no other closing operation
after this. To obtain a further closing operation, the closing
command must be released and then re-launched.
Furthermore, the anti-pumping device only allows circuitbreaker closure if the following conditions are present at the
same time:
operating mechanism spring fully charged
opening pushbutton and/or shunt opening release
(-MO1/-MO2) not activated
circuit-breaker open.

65

3. Specific product characteristics

REF 601 protection Device

On request, the REF 601 switchgear protection device is


available for protection of the installations, which requires an
auxiliary power supply for its operation unlike the previous
PR512 which was a self-supplied release.
The REF 601 has protections and trip curves in accordance
with the IEC 255-3 Standard. It sees to the protection function
against overload (51), against instantaneous and delayed
short-circuit (50-51) and against instantaneous and delayed
homopolar ground fault (50N and 51N). It also detects the
second harmonic component to prevent unwarranted tripping
on connection of a transformer (68).
The unit has 3 inputs from current sensors of the type with
Rogowsky coil, one input from external toroidal CT and from
the keyboard 4 rated currents can be set: 40, 80, 250 and
1250 A.
If the unit is connected to 3 current sensors, the 50N and 51N
protection functions are carried out with the vectorial sum of
the phase currents; if only 2 current sensors are used, then
the external toroidal current transformer must be provided for
functions 50N and 51N.
The external toroidal current transformer can be with
openable core or closed and with any transformation ratio as
long with a 1 A secondary current.
The ABB current sensors of the type with Rogowsky coil
provided for REF 601, are only suitable for installation on MV
insulated cables.

66

The characteristics of the device are:


- trip precision
- wide adjustment ranges
- single and simultaneous adjustment of the three phases
- no limitation (due to the current sensors) to the rated
breaking capacity and at the short-time withstand current of
the circuit-breaker
- pushbuttons for local electrical operation of the circuitbreaker (opening and closing pushbutton
- 5 distinct indicators: relay in operation, relay in trip
threshold, relay tripped, relay tripped due to exceeding
phase current, relay tripped due to exceeding ground fault
current
- interface consisting of an LCD display and of arrow
keys, enter and esc for easier navigation inside the
measurement, data recording, event recording,
settings, configuration and test menus
- three user levels: operator (only display, with free
access, by keeping this key pressed for at least 5 sec.),
configurator (like the previous one, but also with
permission to set the protection parameters, i.e. times and
thresholds, and communication, if present - access limited
by a password), administrator (like the previous ones, but
also with permission to set the password and configure the
basic settings of the device, such as the rated current access limited by a password)
- continual display of the current on the most highly loaded
phase and of the round current
- recording of the value of the currents which caused the
device to trip
- storage of the number of openings carried out by the device
- event log (storage of the parameters described above in the
last 5 trips of the device) in a non-volatile memory
- curves = 1 or = 5 and curve RI specific for the
Belgian market (only REF 601 IEC)
- circuit-breaker opening by means of an undervoltage
release (only REF 601 CEI)
- version, on request, with RS485 4-wire serial
communication
- MODBUS RTU full duplex protocol
- multi-voltage feeder 24 240 V a.c.- d.c

Environmental protection programme

Spare parts

VD4 circuit-breakers are manufactured in accordance with


the ISO 14000 Standards (Guidelines for environmental
management).
The production processes are carried out in compliance
with the Standards for environmental protection in terms of
reduction in energy consumption as well as in raw materials
and production of waste materials. All this is thanks to
the medium voltage apparatus manufacturing facility
environmental management system.
Assessment of the environmental impact of the life cycle of
the product, obtained by minimising energy consumption
and overall raw materials of the product, became a concrete
matter during the design stage by means of targeted selection
of the materials, processes and packing.
This is to allow maximum recycling at the end of the useful life
cycle of the apparatus.

Shunt opening release


Additional shunt opening release
Undervoltage release
Time delay device for undervoltage release
Shunt closing release
Spring charging geared motor with electrical signalling of
spring charged
Contact signalling geared motor protection circuit-breaker
open/closed
Contact signalling closing spring charged/discharged
Transient contact with momentary closing during circuitbreaker opening
Circuit-breaker auxiliary contacts
Locking electromagnet on the operating mechanism
Position contact of the withdrawable truck
Contacts signalling connected/isolated
Opening solenoid
Key lock in open position
Isolation interlock with the door
Protection for opening pushbutton
Protection for closing pushbutton
Locking electromagnet on the withdrawable truck
Set of six isolating contacts.

Ordering
For availability and to order spare parts, please contact our
Service department, specifying the circuit-breaker serial
number.

67

4. Overall dimensions
Fixed circuit-breakers
450

VD4

20

kA

20

kA

31.5

12

25

4XM12 PROF.25

12

kA

20

475

20

20
2XM10 PROF.20

14
97

77.5

170

28

236
49
25

56

A
310

1600

32

599

kV

435

Isc

kV

17.5

237.5

Ir

12

16

Ur

95

248

1VCD000050

56 31

TN

28

345*

400
150

250

45
150

DETAIL A
SCALE 1 : 2 . 5

44*
114

12

409
424

22

12

160

(*) Fixing interchangeability with previous series (345 x 400).

Fixed circuit-breakers
450

VD4

M12 PROF.25

31.5

kA

475

kA

22

28
49

25

DETAIL A
SCALE 1:2

56

kA

25

77.5

kA

20

205

16

115

217.5

A
461

1250

16

22

kV

630

236

345*

28
45

400

250
409

150

150

424

(*) Fixing interchangeability with previous series (345 x 400).

12

22

160

68

2xM10 PROF.18

kV

170

Isc

17.5

45

32

95

31

Ir

12

435

Ur

248

7405

56

TN

44*
114

12

Fixed circuit-breakers
570

VD4

kA

25

kA

31.5

kA

22

kA

20

475

16

115

22

296

28
49

25

DETAIL A
SCALE 1:2
24

205

1250

77.5

A
461

630

M12 PROF. 25

31

kV

56

kV

17.5

217.5

Isc

12

45

2XM10 PROF.20

95

16

Ir

32

308

170

Ur

7406

435

TN

44 *

345 *

28
45

520

250

114

12

409
210

210

424

12

22

160

(*) Fixing interchangeability with previous series (345 x 520).

Fixed circuit-breakers
570

40

kA

M12x25 deep

eep

x18 d

M10

11

1600

11

475

A
310

kV

1250

A (1:4)
77.5
24

171

238

56

435

Isc

17.5

11

589

Ir

kV

16

Ur

12

95
308

1VCD003282

30

TN

11

VD4

296

28
49

45

520
210

250

44 *
114

409

210

422

12

12

160

26

345 *

28

(*) Fixing interchangeability with previous series (345 x 650).

69

4. Overall dimensions
Fixed circuit-breakers
700

VD4

1600

40

kA

11

M10x18 deep

11

kV

1250

310

17.5

M12x25 deep

24
77.5

171

238

56

475

435

Isc

kV

11

589

Ir

12

11

95

373

30

Ur

1VCD003285

16

TN

36

28

361

49

45

250

28

650

25
275

114

345 *

44

422

12

275

12

22

213

(*) Fixing interchangeability with previous series (345 x 650).

Fixed circuit-breakers
700

VD4

32

kA

31.5

kA

475

kA

25

77.5
24

20

205

kA

217.5

16

115

461

14

1250

16

49
25

345 *

28

45

650

250
409
424

275

275

22

12

213

(*) Fixing interchangeability with previous series (345 x 650).

70

22

DETAIL A
SCALE 1 : 2

28

236

M12 PROF. 25

22

kV

630

2XM 10 PROF. 18

97

Isc

17.5

45

kV

170

Ir

12

435

Ur

95

373

1VCD000051

56 31

TN

44 *
114

12

Fixed circuit-breakers

20

kA
kA

31.5

kA

Isc

kV

17.5

kV

2000

2500

40

kA

25

345 *
45

650

44 *

250

114

409

12

424
275

275

20

20

2XM10 PROF.20
12

12

28

213

20

Ir

28
49

12

Ur

361

7408

20

VD4
TN

24

78

25

616

2500

475

2000

310

599

1600

32

237

kV

31

kV

17.5

16

Isc

12

95

95

170

Ir

373

435

Ur

7408

56

TN

2500A

1600-2000A

700

VD4

4XM12 PROF.25

12

22

DETAIL A
SCALE 1:2

(*) Fixing interchangeability with previous series (345 x 650).

Fixed circuit-breakers

7407

Ur

12

kV

Ir

2500

20

kA

308

2000

20

kA

25

kA

31.5

kA

40

kA

310

616
475

296

28
49

25

28

520

345 *
45

44 *

250
409

12

2XM10 deep 20

424
210

210
160

20

20

4XM12 deep 25

20

12

Isc

1600

12

12-17.5 kV

24

7407

Ur

77.5

TN

Ir

599
170

VD4

237.5

kA

16

40

31

kA

32

435

kA

31.5

56

25

2500A
95

95

20

TN

Isc

1600-2000A

570

VD4

12

22

DETAIL A
SCALE 1:2

(*) Fixing interchangeability with previous series (345 x 650).

71

4. Overall dimensions
Fixed circuit-breakers
373

12
28

49
361

5
th 2
dep

474

A (1:4)

4xM
12

2.5

24

77.5

25

20

12

310
635

kA

237

kA

50

171

kA

40

30

31.5

16

kA

20

kA

25

pth

A (**)

20

de

4000

0
M1
2x

Isc

kV
kV
A

20

32

Ir

12
17.5
3150

20

307

435

Ur

1VCD000149

56

TN

424
95

20

VD4

142
345*

28
45

650

250

44*
114

409

700
275

275

12

22

213

(*) Fixing interchangeability with previous series (345 x 650).


(**) With forced ventilation.

Fixed circuit-breakers
600

VD4

kA

20

50

20

2.5

28

165

28

210

12

22

31

172

142
404
428

520

210

2.5

77.5

171

237

56

116

135

40

72

20

20

2000

32

24

12

1600

74
12

475

kV

1250

310

17.5

2xM10 deep 20

435

Isc

kV

610

Ir

12

4xM12 deep 25

459
130

300

16

Ur

323

1VCD003440

30

TN

156

Fixed circuit-breakers
750

kA

20

50

20

2500

12

2000

20

475

78

24

24

1600

20

310

74

610

1250

2xM10 deep 20

32

237

kV

30

17.5

171

Isc

kV

16

Ir

12

4xM12 deep 25

435

Ur

1VCD003441

130

56

TN

459
398
375

12

VD4

28

116

69.5

28

165
30.5

2.5

2.5

135

270

689

225

64.7

404
31

12

275

22

275

24

428

Fixed circuit-breakers

Isc

50

kA

74
32

20

A (*)

12

3150

20
20

475

30
435

2.5

116

30.5

172

28

165

69.5

28

689

270
404

31

275

2.5

24

171

237

56

135

24

Ir

189

130

12

kV

375

310

kV

17.5

4xM12 deep 25
2xM10 deep 20

636

12

Ur

189

118

1VCD003443

240

16

TN

459
398

20

750

VD4

64.5

225
24

428

275

12

22

12

(*) 4000 A with forced ventilation.

73

4. Overall dimensions
Fixed circuit-breakers
570

VD4

1250

16

kA

20

kA

25

kA

2XM10 PROF.20

M12 PROF.25

115
22

22

DETAIL A
SCALE 1:2

296

28
49

25

24

77.5

170

282.5

435
56

Isc

32

22

475

630

45
A

310

kV

631

24

31

Ur

16

7409

Ir

95
308

TN

M12

345*

28

45

250
409
424

520
210

39*
114

12

210
160

(*) Fixing interchangeability with previous series (345 x 520).

Fixed circuit-breakers
700

VD4

16

kA

20

kA

25

kA

115
45

77.5

170

56

282.5

16

Isc

22

1250

32

475

Ir

310

kV

630

631

24

M12 PROF.25

31

Ur

2XM10 PROF.18

435

7410

22

95

373

TN

28
49

25

28

45

424

275

12

22

213

(*) Fixing interchangeability with previous series (345 x 650).

74

250
409

650
275

345 *

24

361

44 *
114

12

DETAIL A
SCALE 1:2

Fixed circuit-breakers
700

VD4

kA

361

28
49

25

28

345 *
45

250

44 *
114

409

650

424

275

20

275

20

2XM10 DEEP 20

20

12

12

213

20

kA

31,5

56

25

661

kA

Isc

475

kA

20

24

16

310

77.5

2500

647

2000

Ir

95

282.5

kV

1600

31

24

16

Ur

170

7411

95

435

TN

2500A

1600-200A
373

22

4XM12 DEEP 25

DETAIL A
SCALE 1:2

(*) Fixing interchangeability with previous series (345 x 650).

Fixed circuit-breakers
570

VD4
1VCD000172

Ur

24

Ir

1250

Isc

31.5

kA

95

308

85
4XM12 DEEP25

kV

2XM10 DEEP 20
40

12

310

32

72

TN

475
77.5

282.5

16

24

17 0

72
DETAIL A
SCALE 1 : 2

296

28
49

M12

28

210

250
344.5 *

520

25

45

114
39*

409

210

424
160

22

435

56

31

12

647

22

75

4. Overall dimensions
Fixed circuit-breakers
784

VD4

2000

31.5

kA

R16

612
482.5
305

15.5

571

57.9

Isc

245

28
49

28
786

275

275

87.5

1600

Ir

104.5

kV

1250

328

36

876

1VYN300901-LT

Ur

31.17

TN

331
447

478.5

470

76

22

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules


492

VD4/P

303

kA

98
35
628
71

38

18

19.5

14

24

340
503
531

76

kA

31.5

35

kA

25

260

20

15

154

kA

205

16

618
31

1250

62.5

28

10

28

79

kV

630

121

91

17.5

36

19

Isc

kV

1250A

124

56
16

Ir

12

630A

36

42.5

213

Ur

7412

624.5

TN

234
49

25

501
490
456

383
416

53

438

150

662

48

38

121

124

609

55

150

320
370

Withdrawable circuit-breakers for PowerCube modules


636

35
310

688

691

71

38

280
165

25

320

18

14

650

19.5

653

21.5

76

kA

31.5

303

359.5

640

370

626

383

550

416

53

642
210

210

55

kA

36

111

kA

25

16

16

28

213

A
31

1250

111

62.5

56

36

119

630

119

28

38

kV

688

kV

17.5

691

Isc

12

Ir

230

49

589

Ur

7420

48

TN

44

VD4/W

77

4. Overall dimensions
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
636

40

kA

28

37

688

36

17

62.5

303

79

1600

28

310

1250

30

kV

49

111

71

25

18

19.5

21.5

14

320

650

359.5

640

370

626

383

552
210

38

76

280
4

214
4

653

165

56

Isc

kV

17.5

230

16

Ir

12

688

Ur

1VCD003284

691

TN

125

44

VD4/P

416

210

53

587

55

640

38

53

640

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules


842

40

kA

303

37

165

76

640

275

55
38

320
359.5

416

750

587

25

383

806

53

38

370

836

275

19.5

14

850

21.5

853

213

280

56

71

78

1600

688

17

79

kV

1250

111

310

17.5

36

119

230

16

Isc

kV

30

Ir

12

688

Ur

144
49 28
28

1VCD003286

691

TN

122

VD4/P

53

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules

kV

36

Ur
Ir

8
688

19.5

21.5

25

320
359.5

650

17.5

kV

640

2000

626

40

14

653

kV

370
383
416

550

kA

38

53

640

210

210

111

38

53

119

587

55

Isc

7415

79

310

71
165

kA

213

kA

31.5

303

36

76

kA

25

280

A
31

2000

12

17

28

VD4/P
TN

119

kV

1600
20

Isc

28

16

17.5

111
62.5

49

688

Ir

12

230

56

Ur

7415

691

TN

122

636
44

VD4/P

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules


842

71

836
806

40

kA

19.5

320
359.5
370

34

53

640

750
275

383
416

275

55

Isc

25

111

119

2000

21.5

76

kV

Ir

14

850

38

17.5

853

kV

587

12

7416

53

Ur

165

VD4/P
TN

38

280

kA

16

kA

31.5

213

25

310

A
kA

303

36

31

2000

28

36

688

1600

119
110
62.5

230
28

79

kV

20
Isc

kV

17.5

56

Ir

12

49

691

Ur

144

7416

688

TN

122

VD4/P

79

4. Overall dimensions
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
842

40

kA

109

8
688

kA

303

36

280

213

14

853

71

19.5

kA

31.5

21.5

25

165

kA

62.5

38

76

20

17

111

310

kV

2500

31

17.5

56

Isc

kV

28
28

16

Ir

12

119

230

49
36

691

Ur

144

7417

688

TN

152

VD4/P

25

320
359.5

850

370

836

383

806

416

750

53

640

275

38

53

111

119

55

587

275

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules

2000

50

kA

36

433
20

688

19.5

26

14

14

21.5

653

605

12

76

165

19

213

280

56

478

1600

16

122

111
28

79

kV

1250

116

310

17.5

135

691

Isc

kV

119

28

16

Ir

12

25

220
165

30

Ur

636
44

1VCD003444

688

TN

10

VD4/P

25
320

650

359.5

640

34

626

80

12

23

303

360

590

29

590

210

49.5

383
416

550

210

370

53

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules


842

50

kA

28

116

433

36
20

688

2000

16

26
165

853

14

25

19.5

12

805
14

21.5

76

19

213

280

56

478

111

122

1600

135

119

25

79

kV

28

310

17.5

217.5

165

691

Isc

kV

144

16

Ir

12

30

Ur

1VCD003445

688

TN

10

VD4/P

320
370

850

359.5

836

34

806

416

750

53

590

275

275

12

22

303

360

590

29

49.5

383

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules


VD4/P

10

152

433
688

691

109

310

36
20

478

16

14

19.5
76

26

25

21.5
4

853

165

280
19

12

805
14

320
370
359.5

850
34

836

49.5

383
417

812

590

750

275

275

303
12

22

kA

213

50

16

29

Isc

111

28

360

119

25

kV

2500

28

30

17.5

Ir

217.5

164
115

136

688

kV

143

56

12

Ur

842

1VCD003446

590

TN

81

4. Overall dimensions
Withdrawable circuit-breakers for PowerCube modules
842

50

kA

20
433

26

19,5

165
4

25

21,5

805
853
850
836
806

14

12

76

19

213

280

56

478

742

36

732

Isc

152

A (*)

109

3150

28

310

Ir

165
116 28

135

16

130

742

kV

119
111

240

678

17.5

Ur

25

30

16

kV

730

12

129

10

361

1VCD003596

30

TN

118

VD4/W

370
34
750

275
29

320
359,5

49,5

383
416,5

53

590
275

22

(*) 4000 A with forced ventilation.

12

303

360

590

189

Withdrawable circuit-breakers for UniGear ZS1 switchgear

kV

17.5

kV

Ir

3150

A (*)

Isc

50

kA

111

240

28

16

130
116 28

135

118

12

36
109

433
733

742

20

19.5

26
76

165

19

213

280

56

478

678

16

30

730

310

Ur

25

361
165

1VCD003447

152

TN

10

842

VD4/P

850
836
806

25

21.5
4

12

805
853

14

320
370
359.5

34

29

750

590

275

(*) 4000 A with forced ventilation.

82

22
12

303

360

589

189

49.5

383
416

275

53

Withdrawable circuit-breakers for UniGear ZS1 switchgear

2
166

732

356
853

14

850
836
806
750

275

19.5

76

kA

21.5

40

109

kA

165

kA

31.5

149

kA

25

310

20

86

52

280

A (*)

3150

19

kV

17

30

17.5

93

28
36

214

Isc

kV

56

Ir

12

730

Ur

1VCD000153

17kV

12kV

16

TN

111

373.5

49

10

842

VD4/P

53

303
320

25

360
370
382

34

275

416
640
16

12

189

22

(*) 4000 A with forced ventilation.

39

96

587

55

Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules


44

7413

Ur

24

kV

49

28

630

36

28

1250

16

kA

20

kA

25

kA

1250A

770

16

31

325

72

213

38

197

775

770

56

71

210

13.5

653

25

320

650
641

370

610

458

383

303

210

53

79

79

98

800

35

55
119

19

35

36

747

Isc

23

48

310

TN

Ir

119
19

232

20

630A

636

VD4/P

83

4. Overall dimensions
Withdrawable circuit-breakers for UniGear ZS1 switchgear
842

16

kA

20

kA

25

kA

56

Isc

28
28

48
790

1250

49
36

7
3

71

38

25

72

213

197

1250A

23

19

310

kV

630

119

232

325

24

770
31
16

Ur

775

7414

Ir

630A
144

TN

20

VD4/P

853

14

320
370
383

850

458

836

303

805

98

35

55

35

747

36

53

119

19

79

275
79

275

53

800

Withdrawable circuit-breakers for UniGear ZS1 switchgear


1600-2000A

842
141

7418

Ur

24

kV

49

30

1600

36

28

2000

2500

16

kA

20

kA

834

16

197

31

810

853

14

25

72

kA

345

kA

31.5

233

25

56

Isc

(1)

817

Ir

310

TN

2500A

119

233
20

VD4/P

320
370
383
303

850
836

46
53

458

805
785

132

275

52

119

55

79

732

275

(1) The rated uninterrupted current of 2300 A is guaranteed with natural ventilation. The rated uninterrupted current of 2500 A is guaranteed with forced ventilation.

84

Withdrawable circuit-breakers for UniGear ZS1 switchgear


636

kA

49 28
36

20

31.5

28

48
770

Isc

310

kV

1250

23

19

35

24

Ir

232

71

653

72

197

213

326

16

56 31

Ur

119

44

775

1VCD000173

770

TN

79

VD4/P

13.5

25

320
303

53

370

650

383

641

458

610
800

210

19

119

55

747

210

Withdrawable circuit-breakers for UniGear ZS1 switchgear


842

834

109

310
345
14

853

25

320

46

370

850

383
303

836
805

458

53

787
275

55

275

119

kA
31

31.5

Isc

28
28

56

36

16

3150

Ir

49

233

734

kV

2700

52

24

817

Ur

233

141

810

1VCD000177

TN

166

VD4/P

85

4. Overall dimensions
Withdrawable circuit-breakers for PowerCube modules
842

kA

40

kA

166

742

kA

31.5

356
853

14

850
836

275

640

55

29

16
8

12

22

94

38

382
416

275

587

86

320
360

34

302

(*) 4000 A with forced ventilation.

303
25

370

806
750

189

19.5

76

165

25

52

109

kA

149

20

310

A (*)

280

3150

86

36

19

kV

30

17.5

17

111

92

17kV

12kV

28

214

Isc

kV

125

230

56

Ir

12

730

Ur

144
49

1VCD000152

16

TN

10

VD4/W

53

Withdrawable circuit-breakers for ZS8.4 switchgear


531

12

kV

Ir

630

20

kA

25

kA

260

510

Isc

52

563

Ur

303

205

1VCD000092

35

TN

91

VD4/Z8

503

53

548
150

495

55

150

Withdrawable circuit-breakers for ZS8.4 switchgear


531
486
455

503

563
153

kA

91

25

205

kA

Isc

260

20

kV

630

510

12

Ir

52

195
380

486
150

150

53

640

55

1VCD000093

Ur

584

TN

303

35

VD4/ZT8

87

4. Overall dimensions
Withdrawable circuit-breakers for ZS8.4 switchgear
531
486
455

20

kA

25

kA

86

153

260

510

Isc

69
503

195
380

486
150

53

640

67

584

55

150

563

kV

630

12

Ir

52

524

Ur

303

205

1VCD000091

35

TN

91

VD4/ZS8

Withdrawable circuit-breakers for ZS8.4 switchgear


531
486
455

kA

25

kA

86

153

260

514

Isc

69

195

503

380
637

486

67

88

150

55

583

150

53

563

20

524

kV

1250

52

98

12

Ir

35

1VCD000133

Ur

205

TN

303

VD4/ZS8

Withdrawable circuit-breakers for ZS8.4 switchgear


531

VD4/Z8

52

1250

20

kA

25

kA

563

630

84

kV

260

Isc

kV

17.5

205

Ir

12

35

Ur

303

1VCD000137

507

TN

503
150

53

495

55

150

Withdrawable circuit-breakers for ZS8.4 switchgear


530
486
455

kA

25

kA

563

20

503

195
383

486
150

153

1250

52

98

A
205

630

260

kV

Isc

kV

17.5

514

Ir

12

303

53

637

150

55

Ur

1VCD000134

583

TN

35

VD4/ZT8

89

4. Overall dimensions
Withdrawable circuit-breakers for ZS8.4 switchgear
681
636

24

kV

Ir

630

16

kA

20

kA

25

kA

611

86

325

524

563

Isc

52

680

Ur

303

310

1VCD000088

35

TN

91

VD4/ZS8

69
653
636

195
380

210

67

583

55

210

53

640

Withdrawable circuit-breakers for ZS8.4 switchgear


681

24

kV

Ir

630

16

kA

20

kA

25

kA

325

563

Isc

52

680

Ur

303

35

1VCD000089

310

TN

91

VD4/Z8

90

53

210

640

55

583

210

653

Withdrawable circuit-breakers for ZS8.4 switchgear


681

16

kA

20

kA

25

kA

325

Isc

563

kV

1250

84

24

Ir

35

1VCD000138

Ur

52

677

TN

303

310

VD4/Z8

210

53

653

640

587

55

210

Withdrawable circuit-breakers for ZS8.4 switchgear


681
636

VD4/ZT8

kA

25

kA

680

20

Isc

563

kA

310

16

611

325

653
636
210

kV

630

35

24

Ir

52

195
380

210

53

640

55

1VCD000090

Ur

585

TN

303

91

4. Overall dimensions
Withdrawable circuit-breakers for ZS8.4 switchgear
681
636

VD4/ZT8
24

kV

Ir

1250

16

kA

20

kA

25

kA

611

325

563

677

Isc

52

84

Ur

303

35

1VCD000136

310

TN

210

653
636

195
380

210

53

587

55

640

Withdrawable circuit-breakers for ZS8.4 switchgear


681
636

VD4/ZS8

16

kA

20

kA

25

kA

86

325

524

Isc

611

69
653
636

195
380
640

67

92

210

55

587

210

53

563

kV

1250

52

84

24

Ir

35

Ur

303

310

1VCD000135

677

TN

Withdrawable circuit-breakers for UniSwitch and UniMix switchgear

1250

16

kA

20

kA

25

kA

48

38

325

Isc

35

kV

630

435,5

24

121

310

1VCD000047

Ur

1250A

570

35

TN

Ir

630A

626

VD4/US

25

13,5

653
650

320
370

23

210

303

210

36.3

383
53

742

55

DETAIL A
SCALE 1 : 2

Withdrawable circuit-breakers for UniSec switchgear

42

35

38

653
650

2101

14

2101

25

320
370
383
303
415
648 1.5
742

23
36.3

kA

25

739

kA

4351

20

Isc

18

kA

1250A

41

79

16

35

1250

Ir

A
3101

kV

630

3251

24

1211

53

DETAIL A
SCALE 1 : 2

55

1VCD000190

Ur

149
45

TN

630A

6261
604

VD4/SEC

93

4. Overall dimensions

Withdrawable circuit-breakers for UniGear ZS2 switchgear and PowerCube modules (36 kV)
842

VD4
kV

1250

1600

2000

31.5

kA

Ir

776

853

125

198

480

953

Isc

"A"

973

36

956

1VYN300901-KG

Ur

380

TN

880

460

4
53

736
275

736

275

94

Breaker type

A mm

VD4 36.12.32

35

VD4 36.16.32 - VD4 36.20.32

79

5. Electric circuit diagram

State of operation represented


The diagrams shows the following conditions:
Circuit-breaker open and connected (only withdrawable circuit-breaker)
Circuits de-energized
Closing springs discharged

Graphical symbols for electric diagrams


Thermal effect

Mass, frame

Capacitor (general
symbol)

Passing make contact


closing momentarily
during release

Electromagnetic effect

Conductors in shielded
cable (two conductors
shown)

Motor
(general symbol)

Closing position contact


(limit switch)

Timing

Connection of
conductors

Rectifier with two


half-waves (bridge)

Opening position
contact (limit switch)

Pushbutton control

Terminal or clamp

Make contact

Power circuit-breaker
with automatic opening

Key control

Socket and plug


(female and male)

Break contact

Control coil
(general symbol)

Earth
(general symbol)

Resistor
(general symbol)

Change-over break
before make contact

Lamp
(general symbol)

95

5. Electric circuit diagram

Electric circuit diagram of fixed circuit-breakers 1VCD 400046


The electric circuit diagram given in this section regards the fixed circuit-breakers with breaking capacity up to 40 kA.

96

97

5. Electric circuit diagram

98

Caption

= Reference number of diagram figure.
= See the note indicated by the letter.
*
-BB1,..2-3 = Circuit-breaker auxiliary contacts.
-BB4
= Circuit-breaker auxiliary passing contact with
momentary closing during opening.
-BB6
= Contact for the undervoltage release de-
energized electrical signal
-BB11
= Contact to interrupt the BB4 signal during the
manual opening operation
-BM
= STU Test unit for supervision of shunt opening
release and shunt closing release winding
continuity (see note D).
= Spring-charging motor limit contacts.
-BS1
= Limit contacts for signalling closing springs
-BS2
charged/discharged.
-MO1
= First shunt opening release (see note D).
-MO2
= Second shunt opening release (see note D).
-MO3
= Opening solenoid for release outside the circuitbreaker.
-MO4
= Third shunt opening release (see note D).
-MC
= Shunt closing release (see note D).
-MS
= Motor for closing spring charging (see note C).
-MU
= Undervoltage release (see note B).
-QB
= Circuit-breaker accessories.
-RL1
= Locking magnet. If de-energized, it mechanically
prevents circuit-breaker closing (it is possible to
limit its consumption by connecting a delayed
pushbutton in series to enable the operation).
= Pushbutton or contact for circuit-breaker closing.
-SC
-SO
= Pushbutton or contact for circuit-breaker
opening.
-XB
= Terminal box for the circuit-breaker circuits.
-XB2...16 = Accessory connectors.

Description of figures
= Motor circuit for closing spring charging (see note
Fig. 1
C).
Fig. 2
= Shunt closing release (anti-pumping is carried out
mechanically) (see note D).
= Locking magnet. When de-energised, it
Fig. 3
mechanically prevents circuit-breaker closing. It
is possible to limit consumption by connecting
a delay pushbutton in series to enable the
operation.
= Instantaneous undervoltage release (see note B).
Fig. 5
= Circuit of third opening release with continuous
Fig. 6
control of the winding (see note D).
Fig. 7
= Circuit of the first shunt opening release with
possibility of continuous control of the winding
(see note D).
Fig. 9
= Circuit of the second shunt opening release with
possibility of continuous control of the winding
(see note D).
Fig. 10
= Opening solenoid for release outside the circuitbreaker.
Fig. 26
= Electrical signalling of closing springs charged
and discharged.
Fig. 30
= Circuit-breaker auxiliary passing contact with
momentary closing during circuit-breaker
opening.
= Available circuit-breaker auxiliary contacts.
Fig. 31
Fig. 32 35 = Available circuit-breaker auxiliary contacts. It
is possible to have one of these figures. The
standard configuration is figure 32.
= Contact for the undervoltage release deFig.60
energized electrical signal.
Fig. 70 to 73 = Available auxiliary contacts of the circuit-breaker.
One of these figures can be obtained.

99

5. Electric circuit diagram

Selection of the figures


Description

Figures Notes

-MS

Spring charging motor

-MC

Shunt closing release

-MO1

Shunt opening release

-MU

Undervoltage release

-MO2

Additional shunt opening release

-BB1 -BB2

Set of 10 circuit-breaker auxiliary contacts

31

Set of 5 extra circuit-breaker auxiliary


contacts 3C-20

32

Set of 5 extra circuit-breaker auxiliary


contacts 5C

33

Set of 5 extra circuit-breaker auxiliary


contacts 2C-30

34

Set of 5 extra circuit-breaker auxiliary


contacts 50

35

-BB3

Notes:
C = normally open contact with
circuit-breaker open
0 = normally closed contact with
circuit-breaker open
-RL1

Locking magnet on operating mechanism

-BB4

Transient contact

30

-BS2

Contact for signalling closing spring


charged/discharged

26

-MO3

Opening solenoid for release outside the


circuit-breaker

10

-MO4

Third shunt opening release

100

Incompatibility
The combination of circuits given in the figures below are not
possible on the same circuit-breaker:
32-33-34-35
Notes
A) The circuit-breaker is only fitted with the accessories specified
in the order acknowledgement. To draw up the order, please
consult this catalogue.
B) The undervoltage release can be supplied for power supply
branched on the supply side of the circuit-breaker or from an
independent source.
Circuit-breaker closing is only possible with the undervoltage
release energized (the lock on closing is made mechanically).
In the case where there is the same power supply for the shunt
closing and undervoltage releases and automatic circuitbreaker closing is required on return of the auxiliary voltage,
a delay of 50ms must be introduced between the moment of
consent to the undervoltage release and energization of the
shunt closing release.
Incompatible with -MO4.
C) Check the auxiliary circuit power to verify the possibility of
starting several motors for charging the closing springs at the
same time.
To prevent excessive consumption the closing springs must be
charged manually before energizing the auxiliary circuit.
D) The circuit for controlling the shunt opening release winding
continuity must only be used for this purpose.
It is possible to use the STU Test Unit to check continuity of the
various release.
E) When fig. 06 is required, contact -BB3 (41-42) of fig. 32-33
is not available and figs. 34-35 cannot be supplied. When
fig. 09 is required, contact -BB1 (43-44) of fig. 31 is not
available.

Electric circuit diagram of fixed circuit-breakers 1VCD 400099


The electric circuit diagram given in this section regards the fixed circuit-breakers with breaking capacity up to 50 kA.

101

5. Electric circuit diagram

102

103

5. Electric circuit diagram

Caption

= Reference number of diagram figure.
= See the note indicated by the letter.
*
-BB1,..2-3 = Circuit-breaker auxiliary contacts.
-BB4
= Circuit-breaker auxiliary passing contact with
momentary closing during opening.
-BB6
= Contact for the undervoltage release deenergized electrical signal.
-BB11
= Contact to interrupt the BB4 signal during the
manual opening operation.
-BM
= STU Test unit for supervision of shunt opening
release and shunt closing release winding
continuity (see note D).
= Spring-charging motor limit contacts.
-BS1
= Limit contacts for signalling closing springs
-BS2
charged/discharged.
-MO1
= First shunt opening release (see note D).
-MO2
= Second shunt opening release (see note D).
-MO4
= Third shunt opening release (see note D).
-MC
= Shunt closing release (see note D).
-MS
= Motor for closing spring charging (see note C).
-MU
= Undervoltage release (see note B).
-QB
= Circuit-breaker accessories.
-RL1
= Locking magnet. If de-energized, it mechanically
prevents circuit-breaker closing (it is possible to
limit its consumption by connecting a delayed
pushbutton in series to enable the operation).
= Pushbutton or contact for circuit-breaker closing.
-SC
= Pushbutton or contact for circuit-breaker
-SO
opening.
= Terminal box for the circuit-breaker circuits.
-XB
-XB2...16 = Accessory connectors.

104

Description of figures
Fig. 1
= Motor circuit for closing spring charging (see note
C).
= Shunt closing release (anti-pumping is carried out
Fig. 2
mechanically) (see note D).
Fig. 3
= Locking magnet. When de-energised, it
mechanically prevents circuit-breaker closing. It
is possible to limit consumption by connecting a
delay pushbutton in series to enable the operation.
Fig. 5
= Instantaneous undervoltage release (see note B).
= Circuit of third opening release with continuous
Fig. 6
control of the winding (see note D).
= Circuit of the first shunt opening release with
Fig. 7
possibility of continuous control of the winding (see
note D).
Fig. 9
= Circuit of the second shunt opening release with
possibility of continuous control of the winding (see
note D).
Fig. 26
= Electrical signalling of closing springs charged and
discharged.
Fig. 30
= Circuit-breaker auxiliary passing contact with
momentary closing during circuit-breaker opening.
Fig. 31
= Available circuit-breaker auxiliary contacts.
Fig. 32 35 = Available circuit-breaker auxiliary contacts. It
is possible to have one of these figures. The
standard configuration is figure 32.
Fig. 60
= Contact for the undervoltage release deenergized electrical signal.
Fig. 70 to 73 = Available auxiliary contacts of the circuit-breaker.
One of these figures can be obtained.

Selection of the figures


Description

Figures Notes

-MS

Spring charging motor

-MC

Shunt closing release

-MO1

Shunt opening release

-MU

Undervoltage release

-MO2

Additional shunt opening release

-BB1 -BB2

Set of 10 circuit-breaker auxiliary contacts

31

Set of 5 extra circuit-breaker auxiliary


contacts 3C-20

32

Set of 5 extra circuit-breaker auxiliary


contacts 5C

33

Set of 5 extra circuit-breaker auxiliary


contacts 2C-30

34

Set of 5 extra circuit-breaker auxiliary


contacts 50

35

-BB3

Notes:
C = normally open contact with
circuit-breaker open
0 = normally closed contact with
circuit-breaker open
-RL1

Locking magnet on operating mechanism

-BB4

Transient contact

30

-BS2

Contact for signalling closing spring


charged/discharged

26

-MO3

Opening solenoid for release outside the


circuit-breaker

10

-MO4

Third shunt opening release

Incompatibility
The combination of circuits given in the figures below are not
possible on the same circuit-breaker:
32-33-34-35
Notes
A) The circuit-breaker is only fitted with the accessories
specified in the order acknowledgement. To draw up the
order, please consult this catalogue.
B) The undervoltage release can be supplied for power supply
branched on the supply side of the circuit-breaker or from an
independent source.
Circuit-breaker closing is only possible with the undervoltage
release energized (the lock on closing is made mechanically).
In the case where there is the same power supply for the shunt
closing and undervoltage releases and automatic circuitbreaker closing is required on return of the auxiliary voltage,
a delay of 50ms must be introduced between the moment of
consent to the undervoltage release and energization of the
shunt closing release.
Incompatible with -MO4.
C) Check the auxiliary circuit power to verify the possibility of
starting several motors for charging the closing springs at the
same time.
To prevent excessive consumption the closing springs must be
charged manually before energizing the auxiliary circuit.
D) The circuit for controlling the shunt opening release winding
continuity must only be used for this purpose.
It is possible to use the STU Test Unit to check continuity of the
various release.
E) When fig. 06 is required, contact -BB3 (41-42) of fig. 32-33
is not available and figs. 34-35 cannot be supplied.
When fig. 09 is required, contact -BB1 (43-44) of fig. 31 is
not available.

105

5. Electric circuit diagram

Electric circuit diagram of withdrawable circuit-breakers 1VCD 400047


The electric circuit diagram given in this section regards the withdrawable circuit-breakers with breaking capacity
up to 40 kA. For withdrawable circuit-breakers with motorized truck, see diagram 1VCD400048.
For circuit-breaker of ZS8.4 switchgears the following diagrams are available:
1VCD400080 Standard version
1VCD400085 Version with motorized truck.

106

107

5. Electric circuit diagram

108

109

5. Electric circuit diagram

Caption

= Reference number of diagram figure.
= See the note indicated by the letter.
*
-BB1,..2-3 = Circuit-breaker auxiliary contacts.
-BB4
= Circuit-breaker auxiliary passing contact with
momentary closing during opening.
-BB6
= Contact for the undervoltage release deenergized electrical signal.
-BB11
= Contact to interrupt the BB4 signal during the
manual opening operation,
-BD
= Enclosure door position contact.
-BM
= STU Test Unit for checking winding continuity of
the shunt opening and closing release (see note
D).
= Spring-charging motor limit contacts.
-BS1
-BS2
= Limit contact for signalling closing springs
charged/discharged.
-BT1
= Contacts for electrical signalling of circuitbreaker in connected position (see note E).
= Contacts for electrical signalling of circuit-BT2
breaker in isolated position (see note E).
-BT3
= Circuit-breaker position contact, open during
the circuit-breaker isolation run.
-MO1
= First shunt opening release (see note D).

-MO2
-MO3

= Second shunt opening release (see note D).


= Opening solenoid for release outside the
circuit-breaker.
-MO4
= Third shunt opening release (see note D).
-MC
= Shunt closing release (see note D).
= Motor for closing spring charging (see note C).
-MS
= Undervoltage release (see note B).
-MU
-QB
= Circuit-breaker accessories.
-RL1
= Locking magnet. If de-energized, it prevents
mechanical closing of the circuit-breaker (it is
possible to limit its consumption by connecting
a delayed pushbutton in series to enable the
operation).
-RL2
= Locking magnet (on the truck). If de-energized,
it prevents mechanical connection and isolation
of the circuit-breaker (it is possible to limit
its consumption by connecting a delayed
pushbutton in series to enable the operation).
= Pushbutton or contact for circuit-breaker
-SC
closing.
= Pushbutton or contact for circuit-breaker
-SO
opening.
-XB
= Connector for the circuit-breaker circuits.
-XB2...16 = Accessory connectors.

Selection of the figures


Description

Figures

Notes

-MS

Closing spring charging motor

-MC

Shunt closing release

-MO1

Shunt opening release

-MU

Undervoltage release

-MO2

Additional shunt opening release

D-F

-RL2

Locking magnet on the truck

-BB4

Auxiliary passing contact

30

-BS2

Contact for signalling closing spring charged/discharged

26

-MO3

Opening solenoid for release outside the circuit-breaker

10

-MO4

Third shunt opening release

D-F

110

Selection of the figures


Set of 10
circuit-breaker
auxiliary
contacts

Set of 5 other
circuit-breaker
auxiliary
contacts

Circuit-breaker
connected
isolated
contact

Position
contact for
withdrawable
circuit-breakers

Locking
magnet on
the operating
mechanism

-BB1 -BB2

-BB3

-BT1 -BT2

-BT3

-RL1

X
X

X
X

X
X

X
X

X
X

3-4
31-32-52

31-32-33-34
33-34-51

32

31 / 51

E-F

32 / 51

E-F

3 / 31 / 51

E-F-G

3 / 32 / 51

E-F-G

4 / 33

E-F-G

4 / 34

E-F-G

4 / 33 / 52

E-F-G

4 / 34 / 52

E-F-G

Incompatibility
The circuits given in the figures below cannot be supplied at
the same time in the same circuit-breaker:

31

Notes

X
X

Figures

4-31-32
51-52

3-33-34
5-6

Notes
A) The circuit-breaker is only fitted with the accessories
specified in the order acknowledgement. To draw up the
order, please consult the present catalogue.
B) The undervoltage release can be supplied for power supply
branched on the supply side of the circuit-breaker or from
an independent source. Circuit-breaker closing is only
possible with the undervoltage release energized (the lock
on closing is made mechanically). In the case where there
is the same power supply for the closing and undervoltage
releases and automatic circuit-breaker closing is required
on return of the auxiliary voltage, a delay of 50ms must
be introduced between the moment of consent to the
undervoltage release and energization of the shunt closing
release.
Incompatible with -MO4.

C) Check the power available on the auxiliary circuit to verify


the possibility of starting several motors for charging the
closing springs at the same time. To prevent excessive
consumption the closing springs must be charged manually
before energizing the auxiliary circuit.
D) The circuit for controlling the shunt opening release winding
continuity must only be used for this purpose. It is possible
to use the STU Shunt Test Unit to check continuity of the
winding.
E) The contacts for electrical signalling of circuit-breaker
in the connected and isolated position (-BT1 and -BT2)
shown in fig. 51 or 52 are located in the circuit-breaker
truck
F) When fig. 10 is requested, contact -BB3 31-32 indicated
of fig. 32-34 is not available. When fig. 30 is requested,
contact -BB3 (53-54) indicated of fig. 32-34 is not
available. When fig. 9 is requested, contact -BB1 (43-44
indicated) of fig. 31-32-33-34 is not available.
When fig. 06 is required, contact -BB3 (terminals 41-42) of
figs. 32 and 34 is not available.
G) Fig. 3 is supplied when fig. 31 or 32 is requested. Fig. 4 is
supplied when fig. 33 or 34 is requested (in this case it is
compulsory to supply the -BT3).

111

5. Electric circuit diagram

Electric circuit diagram of withdrawable circuit-breakers 1VCD 400100


The electric circuit diagram given in this section regards the withdrawable circuit-breakers with breaking capacity
up to 50 kA. For withdrawable circuit-breakers with motorized truck, see diagram 1VCD400102.

112

113

5. Electric circuit diagram

114

115

5. Electric circuit diagram

Caption

= Reference number of diagram figure.
= See the note indicated by the letter.
*
-BB1,..2-3 = Circuit-breaker auxiliary contacts.
-BB4
= Circuit-breaker auxiliary passing contact with
momentary closing during opening.
-BB6
= Contact for the undervoltage release de-
energized electrical signal
-BB11
= Contact to interrupt the BB4 signal during the
manual opening operation,
-BD
= Enclosure door position contact.
-BM
= STU Test Unit for checking winding continuity of
the
shunt opening and closing release (see note D).
-BS1
= Spring-charging motor limit contacts.
-BS2
= Limit contact for signalling closing springs
charged/discharged.
-BT1
= Contacts for electrical signalling of circuit-
breaker in connected position (see note E).
-BT2
= Contacts for electrical signalling of circuit-
breaker in isolated position (see note E).
-BT3
= Circuit-breaker position contact, open during the
circuit-breaker isolation run.

-MO1
-MO2
-MO4
-MC
-MS
-MU
-QB
-RL1

= First shunt opening release (see note D).


= Second shunt opening release (see note D).
= Third shunt opening release (see note D).
= Shunt closing release (see note D).
= Motor for closing spring charging (see note C).
= Undervoltage release (see note B).
= Circuit-breaker accessories.
= Locking magnet. If de-energized, it prevents
mechanical closing of the circuit-breaker (it is
possible to limit its consumption by connecting
a delayed pushbutton in series to enable the
operation).
-RL2
= Locking magnet (on the truck). If de-energized,
it prevents mechanical connection and isolation
of the circuit-breaker (it is possible to limit
its consumption by connecting a delayed
pushbutton in series to enable the operation).
-SC
= Pushbutton or contact for circuit-breaker closing.
-SO
= Pushbutton or contact for circuit-breaker
opening.
-XB
= Connector for the circuit-breaker circuits.
-XB2...16 = Accessory connectors.

Selection of the figures


Description

Figures

Notes

-MS

Closing spring charging motor

-MC

Shunt closing release

-MO1

Shunt opening release

-MU

Undervoltage release

-MO2

Additional shunt opening release

D-F

-RL2

Locking magnet on the truck

-BB4

Auxiliary passing contact

30

-BS2

Contact for signalling closing spring charged/discharged

26

-MO4

Third shunt opening release

116

F
D-F

Selection of the figures


Set of 10
circuit-breaker
auxiliary
contacts
-BB1 -BB2

Set of 5 other
circuit-breaker
auxiliary
contacts
-BB3

Circuit-breaker
connected
isolated
contact
-BT1 -BT2

Position
contact for
withdrawable
circuit-breakers
-BT3

Locking
magnet on
the operating
mechanism
-RL1

Figures

Notes

31

32

31 / 51

E-F

32 / 51

E-F

3 / 31 / 51

E-F-G

X
X

X
X

X
X

X
X

3 / 32 / 51

E-F-G

4 / 33

E-F-G

4 / 34

E-F-G

4 / 33 / 52

E-F-G

4 / 34 / 52

E-F-G

X
X

X
X

Incompatibility
The circuits given in the figures below cannot be supplied at
the same time in the same circuit-breaker:

3-4
31-32-52

31-32-33-34
31-34-51

4-31-32
51-52

3-33-34
5-6

Note
A) The circuit-breaker is only fitted with the accessories
specified in the order acknowledgement. To draw up the
order, please consult the apparatus catalogue.
B) The undervoltage release can be supplied for power supply
branched on the supply side of the circuit-breaker or from
an independent source.
Circuit-breaker closing is only possible with the
undervoltage release energized (the lock on closing is
made mechanically).
In the case where there is the same power supply for
the closing and undervoltage releases and automatic
circuit-breaker closing is required on return of the auxiliary
voltage, a delay of 50ms must be introduced between
the moment of consent to the undervoltage release and
energization of the shunt closing release.
Incompatible with -MO4

C) Check the power available on the auxiliary circuit to verify


the possibility of starting several motors for charging the
closing springs at the same time. To prevent excessive
consumption the closing springs must be charged manually
before energizing the auxiliary circuit.
D) The circuit for controlling the shunt opening release winding
continuity must only be used for this purpose.
It is possible to use the Shunt Test Unit to check continuity
of the winding.
E) The contacts for electrical signalling of circuit-breaker
in the connected and isolated position (-BT1 and -BT2)
shown in fig. 51 or 52 are located in the circuit-breaker
truck
F) When fig. 9 is required, contact -BB1 (terminals 41-42) of
figs. 31-32-33-34 is not available. When fig. 30 is required,
contact -BB3 (terminals 53-54) of figs. 32 and 34 is not
available. When fig. 06 is required, contact -BB3 (terminals
41-42) of figs. 32-34 is not available.
G) Fig. 3 is supplied when fig. 31 or 32 are required. Fig. 4 is
supplied when fig. 33 or 34 are required (in this case, it is
obligatory for -BT3 to be supplied).

117

118

119

ABB S.p.A.
Power Products Division
Unit Operativa Sace-MV
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: info.mv@it.abb.com

ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
Petzower Strasse 8
D-14542 Glindow
D-40472 Ratingen
Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916
E-mail: powertech@de.abb.com
www.abb.com

The data and illustrations are not binding. We reserve


the right to make changes without notice in the course
of technical development of the product.
Copyright 2012 ABB. All rights reserved.