CKT

1
2
3
4
5
6
7
8
9
10
11
12

LOAD DESCRIPTION
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
LIGHTING OUTLET 100 VA
SPARE
SPARE
SPARE
TOTAL
@ 80% DEMAND FACTOR

NO. OF OUTLETS
10
10
10
10
10
10
10
6
7
-

VOLTS
230
230
230
230
230
230
230
230
230
-

VA
1000
1000
1000
1000
1000
1000
1000
600
700
8300
USE

AMPERE
4.348
4.348
4.348
4.348
4.348
4.348
4.348
2.609
3.043
36.087
28.8695652
2-2 mm2 THHN

POLES
2
2
2
2
3
4
5
6
7
-

PROTECTION
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
90 A

WIRE SIZE
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
-

CONDUIT SIZE
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
32 mm PVC

CKT
1
2
3
4
5
6
7
8
9
10
11
12

LOAD DESCRIPTION
CONVENIENCE OUTLET 200 VA, 2-GANG
CONVENIENCE OUTLET 200 VA, 2-GANG
CONVENIENCE OUTLET 200 VA, 2-GANG
CONVENIENCE OUTLET 200 VA, 2-GANG
ACU 6AFL
ACU 6AFL
WATER HEATER 3000 VA
WATER HEATER 3000 VA
REFRIDGERATOR OUTLET 2000 VA
SPARE
SPARE
SPARE
TOTAL
@ 80% DEMAND FACTOR

NO. OF OUTLETS
10
6
10
6
1
1
1
1
1
-

VOLTS
230
230
230
230
230
230
230
230
230
-

VA
4000
2400
4000
2400
2000
2000
3000
3000
2000
24800
USE

AMPERE
17.391
10.435
17.391
10.435
8.696
8.696
13.043
13.043
8.696
107.826
86.2608696
2-2 mm2 THHN

POLES
2
2
2
2
2
2
2
2
2
-

PROTECTION
20 A
20 A
20 A
20 A
30 A
30 A
30 A
30 A
30 A
20 A
20 A
20 A
90 A

WIRE SIZE
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
2-3.5 mm2 THHN
-

CONDUIT SIZE
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
15 mm PVC
32 mm PVC