Socomec - DIRIS A40
Socomec - DIRIS A40
Product presentation
1 2
5. P
ushbutton for maximal and average
current and power values
DIRIS A40
Select a DIRIS
Catalog number
4825 0A40
Optional functions
Select a module
Description
Pulse output
2 configurable outputs impulses (type, weight and duration) for +/- kWh, +/- kvarh and KVAh
Pulse output + harmonics
2 configurable outputs impulses (type, weight and duration) for +/- kWh, +/- kvarh and KVAh
Harmonic analysis by row up to 25 and by phase for 3I, In, 3V and 3U
Communication: RS 485 JBUS/MODBUS
RS 485 link with JBUS/MODBUS protocol (speed up to 38 400 bauds)
Analog outputs
2 configurable outputs on 3I, In, 3V, 3U, F, +/-P, +/-Q, S and PFL/C
2 modules may be installed, for 4 analog outputs max
2 inputs 2 outputs
2 to 6 outputs for monitoring 3I, In, 3V, 3U, F, +/-P, +/-Q, S and PFL/C,
THD 3I, THD In, THD 3V, THD 3U and hours run or remove control
Communication PROFIBUSDP
1 module RS 485 and 1 module protocol PROFIBUSDP (speed up to 1.5 Mbauds)
Memory
Storing P+, P-, Q+, Q- values with internal/external synchronisation signal
(5, 8, 10, 15, 20 and 30 minutes during 31 and 62 days)
Storing last 10 time-stamped alarms
Storing min/max instantaneous values
for 3I, In, 3V, 3U, F, +/-P, +/-Q, S, THD 3U, THD 3V, THD 3I, THDIn
Storing last 10 time-stamped voltage dips, surges and outage (EN 50 160)
Storing average values according to synchronisation signal for 3U, 3V and F
Catalog number
4825 0090
4825 0091
4825 0092
4825 0093
4825 0094
4825 0096
4825 0097
103
DIRISA40
Technical characteristics
Current measurement on inputs (TRMS)
CT primary
CT secondary
Measurement range
Input consumption
Measurement updating period
Accuracy
Sustained overload
Intermittent overload
Impulse withstand voltage
Voltage measurement (TRMS)
Direct measurement between phases
VT primary
VT secondary
Frequency
Input consumption
Measurement updating period
Accuracy
Sustained overload
Current-voltage product
Limitation for 1A CT
Limitation for 5A CT
Power measurement
Measurement updating period
Accuracy
Power factor measurement
Measurement updating period
Accuracy
Frequency measurement
Measurement range
Measurement updating period
Accuracy
Energy accuracy
Active (according to IEC 62053-22)
Reactive (according to IEC 62053-23)
10000 A
1 and 5 A
0 ... 11 kA
0.1 VA
1s
0.2%
6A
10 In for 1 s
4 kV
18 ... 500 VAC
500 000 VAC
60, 100, 110, 115, 120, 173, 190 VAC
50/60 Hz
0.1 VA
1s
0.2%
760 VAC
10 000 000
10 000 000
1s
0.5%
1s
0.5%
45 ... 65 Hz
1s
0.1%
Class 0.5 S
Class 2
Dimensions (in/mm)
3.65 +- 0.05
0.0
Type
Dimensions H x W x D
Case protection rating
Front protection rating
Display type
Terminal block type
Voltage and other connection section
Current connection section
Weight
92 +- 0.8
0.0
3.8
96
3.65 +- 0.05
0.0
92 +- 0.8
0.0
3.8
96
104
0.8
2.4 20
60
panel mounting
96 x 96 x 60 mm
IP 30
IP 52
LCD
fixed or pull-out
0.2 ... 2.5 mm2
0.5 ... 6 mm2
400 g
DIRISA40
Terminal blocks
DIRIS A40
V1
V2
Communication module
V3
VN
A U X
0V -
S1 S2 S1 S2 S1 S2
I1
I2
I3
DIRIS A40
1
0n
RS485
R = 120
DIRIS A40
RS485 link
R =termination resistance
Metering module
1
OUT 1
OUT 2
DIRIS A40
17 18
9 10 11 12
+
+
0/4-20 mA 0/4-20 mA
OUT 1
Memory module
OUT 1
OUT 2
A-Cd
A-Cd
OUT 2
DIRIS A40
1 3 14 15 16
5 - 6: analog output n 1
7 - 8: analog output n 2
+
IN 1
IN
synchro
DIRIS A40
IN 2
DIRIS A40
105
DIRISA40
Connections
Recommendation: when disconnecting the DIRIS, the secondaries of each current transformer must be shortcircuited. This operation can be carried out automatically from a product in the Disconnect Switch catalog, PTI,
please consult us.
Single phase
1 = 0.5 A class CC
1 = 0.5 A class CC
S1
1 = 0.5 A class CC
N
L1
L2
L3
P1
Two phases
S2
P1
S1
V1 V2 V3 VN
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
S1
P1
L1
N
S2
I1
I2
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I3
L1
L2
S2
S1 S2 S1 S2 S1 S2
I3
I1
I2
I3
1 = 0.5 A class CC
P1
S1
S2
P1
S2
S1
N
L1
L2
L3
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
1 = 0.5 A class CC
P1
S1
S2
P1
S2
S1
1 = 0.5 A class CC
P1
L1
L2
L3
S1
S1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
L1
L2
L3
P1
S2
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I3
I1
I2
I3
V
oltage transformer connection
for HV networks
Other information
Communication via RS485 link
L1
L2
L3
LIYCY-CY
0V RS485
A U X
ON
R = 120
V1 V2 V3 N
106
1 = 0.5 A class CC