You are on page 1of 1

HAWKER S.A.R.L.

Rue A. Fleming Z.I EST BP 962


62033 Arras Cedex - France
Tel : +33 (0)3 21 60 25 25
Fax : +33 (0)3 21 73 16 51
E mail : hawker.france@fr.enersys.com
www.enersys.com

STATEMENT
We, HAWKER SARL Arras, hereby certify that :
The float/charge voltage for Powersafe VE, VE FT, V, V FT ranges (valve regulated
lead acid batteries) is 2.28Vpc at 20c
It is required to adjust the float voltage according to the temperature as follows :
Temperature
00c
10c
20c
25c
30c
35c
40c

Float voltage range per cell


2.33-2.36 V
2.30-2.33 V
2.27-2.30 V
2.25-2.28 V
2.24-2.27 V
2.22-2.25 V
2.21-2.24 V

For battery charger with automatic temperature compensation, the


voltage/temperature compensation is + 3mV/C/Cell f or a temperature lower than
20C (the reference temperature being 20C) and - 3 mV/C/Cell for a temperature
higher than 20C

Arras,

2007-02-08

Christian LEMOINE
Xavier MUNERET
Reserve Power
Engineering Europe
Hawker S.A.R.L. Arras

Socit Responsabilit Limite au Capital de 6.929.004,81 Euros


R.C.S. Arras B 381 473 297
Usine d'ARRAS