a —— WwarE (pz BAL Bee a at az — DUBAI ELECTRICITY & WATER AUTHORITY REGULATIONS FOR ELECTRICAL INSTALLATIONS 1997 EDITION P.O. BOX 564 DUBAI UNITED ARAB EMIRATES DUBAI ELECTRICITY & WATER AUTHORITY (DEWA) REGULATIONS FOR ELECTRICAL INSTALLATIONS 1997 - EDITION INTRODUCTION This edition supersedes the ‘WIRING REGULATIONS FOR ELEC- TRICAL INSTALLATION AND APPROVED CODE OF PRACTICE IN DUBAI’ issued in the year 1985 by the then DUBAI ELECTRICITY COMPANY, The object of the Regulations is to provide Consultants, Contractors, Wiremen and Consumers with a general guide for compliance with DEWA's requirements for electric installations in order to safeguard persons and property from hazards atising from the use of electricity. The Regulations, however, are not intended to substitute detailed specifications nor to serve as an instruction manual for untrained persons, It is essential that all Consultants, Contractors and Wiremen study and abide by these Regulations, This, of course, does not absolve the concemed parties from obtaining other necessary approvals from DEWA, Some of the practices followed generally in the AGCC Countries have been adapted as appropriate. References are generally made to the sixteenth edition of the IEE Wiring Regulations, British Stan- dards (BS) and International Electrotechnical Commission (IEC) doc- uments. Consideration has been given to the prevention of fire and shock hazards as. well as proper operation and maintenance of wit- ing installations and equipment. Clause ens 3.1 3.2 3.3 a4 42 424 42.2 42.3 42.4 425 42.6 427 43 43.1 43.2 44 As 454 45.2 CONTENTS Page INTRODUCTION i SECTION 1: GENERAL REQUIREMENTS 1-4 Scope Electricity Supply Ambient Conditions Approved Contractors Workmanship Standards for equipment and materials Submission of Drawings Power Factor (P.F,) Correction Under Voltage (U.Y.) Relays with Auto-Reset Timer Harmonies and rapid voltage changes Inspection and testing of installations Maintenance, periodic inspection and testing Extensions and alterations SECTION2: DEFINITIONS 5-8 SECTIONS: DEWA INCOMING SUPPLY AND TARIFF METERING © 9-11 General Point of Supply Tariff Metering SECTION4: SELECTION OF CABLES, EQUIPMENT, MATERIALS & WIRING SYSTEMS 12-20 General Cables and Conductors Selecton Minimum Size of Conductors Current rating, size and Votage drop Colour Identification Wiring Installations Exposed to High Temperatures. Wiring Installations in Hazardous areas Load Balancing Wiring Accessories and Fittings Condkits end Fittings Trunking Cable Trays & supports Low Voltage Switchgear and Control Gear Assemblies Main & Sub-Main Distribution Boards Final Distribution Boards Clause Page 46 Apparatus & Accessories 46.1 ‘Switches 462 Plugs and Socket-Outlots 46.3 Cooker Control Units 4.64 Household and similar electrcal appliances 465 Control of Water Heaters 4.6.6 Control of Air Condittoning Unitfequipment 46.0 Extra Low Voltage Safety Apparatus 468 H.V. Discharge Lighting Equipment 4.6.9 Safety and Emergency Light Fittings 4.6.10 Electric Motors and Staners 4.6.11 Standby Generators 47 Assessment of connected load and max. demand 474 Lighting & small power circulis 472 Maxirnum demand SECTION 5: EARTHING AND EARTH LEAKAGE PROTECTION 21-22 5A ‘Consumer's Earthing System 52 Consumer's Main Earth Elecitode 5.3 Earth Continuity Conductor (ECC) 54 Earth Leakage Protection 5.5 Equipotentiel Bonding SECTION 6: INSTALLATION OF CONDUITS, TRUNKING, TRAYS & ACCESSORIES 23-25 84 Trunking and Conduits 6.2 Cable Trays SECTION 7: INSTALLATION OF CABLES, EQUIPMENT, ACCESSORIES AND WIRING SYSTEMS. 26-28 tl Armoured Cables 72 Distribution Boards 73 Busbar trunking systems (Busways) 74 Wiring systens and Accessories 7.4.4 Segregation of circuits, Phases and wiring systems TAQ Mounting heights of Accessories 743 Identification Labels and Notices SECTION 5: POWER FACTOR CORRECTION CAPACITORS AND. UNDER VOLTAGE RELAYS 29-30 Bt Power Factor (PF) Correction 32 Under Voltage (U.V.) Relays with Auto-reset timer + ili Clause Page SECTION 9: CONSTRUCTION SITE INSTALLATIONS 3t on General 92 Wiring systems and Distribution Boards 93 Earth Leakege Protection Appendix APPENDICES 33 1 Reterence Standards a4 2 Details of Connected Load/Max. Demand (format) 35 3 Load Distribution Schedule - 3 phase (format) 36 4. Load Distribution Schedule - 1 phase (format) 37 5. Electrical Symbols 38 - 40 6 Contractor's Inspection Certificates (format) 41-42 7. (A). Typical arrangement of Metering Cabinet on Compound Wall 43 (8) Typical arrangement of kWh meters in Electrical Service Room 44 {C) Typical Electrical services room with 1 No. MDB 45 (D) Typical Electrical services room with 1 No. Cubicle type L.V. Switchboard’ 46 Panel 8. Selection of Cables Table 1 :- Single Core PVC Insulated non-armoured, Stranded Copper Conductors. a7 Table 2: Multi Core armoured PVG insulated, Copper Conductors. 46 Table 3:- Multi Core armoured XLPE insulated, Copper Conductors. 49 8. Colour identificetion of unarmoured, armoured and flexible cable cores and bare conductors. 50 10. Specifications of MDBs/SMDBs (format) 51-53 4 Spocitications of DBs (format) 54-56 12, Eaith Continuity Conductors (ECCs) and Equipotential Bonding Conductors, 7 43, Eaith Leakage Protection. 58 14 Spacing of Supports for Trunking, Conduits and Cables. 59 15. Number of Cables that may be installed in Trunking, Conduits and Trays. 60 16. Data Schedule for LV Electricity Meters and Current Transtormers. 61 vive A 4.2 DUBAI ELECTRICITY & WATER AUTHORITY REGULATIONS FOR ELECTRICAL INSTALLATIONS SECTION - 1 GENERAL REQUIREMENTS, SCOPE The Regulations apply to the requirements of all electrical installations in or about buildings and any additions, atterations and extensions to the existing buildings and installations therein, in the Emirate of Dubai, Installations, wherein construction of High Voltage substation/s is required, shall be relerred to DEWA at the preliminary design stage for incorporating any specific requirements The Regulations are not intended to take the place of a detailed specification or to instruct untrained persons or to provide for every circumstance. Where a difficult or special situation arises which is not covered or alowed for in the Regulations, the DEWA may be sought to obtain specitic advice, ELECTRICITY SUPPLY The nominal electric supply volage from DEWA is 220/980V + 10%, 50 Hz, 3- Phase, 4- wire with separate neutral and protective conductor (generally metallic covering of the cable supplying the installations), The neutral is soidly earthed at DEWA’s substations and Shall not normally be earthed elsewhere in the electrical installations. The design fault level within the substation i 40 kA (fault duration - 1 Sec), except for fuse protected equipmenticircut, The nominal voltage of existing 220V/380V system shall evolve towards the IEC recommended value of 230/400V + 10% (IEC .98) before the year 2005, Al equipment, apparatus, materials and accessories used in the electrical installations shall be designed and rated tor operation on this electric supply. Appropriate protective devices against over-voltages, fluctuations, transiants & harmonics, lass of one or more phases and any unforeseen interruptions shall be provided in all consumer installations as deemed essential, in addition to overload, short-circuit and earth leakage protective devices. 1.3 14 15 16 ANBIENT CONDITIONS All equipment, apparatus, materials and accessories used In the electrical insiallations shall be suitable for the purpose intended and capable of operating with satisfactory performance in the climatic conditions of the Emirate of Dubai which are as follows + - Altitude : Sea Level (Coastal) - Max. outdoor ambient temperature (shade) 48°C - Min, Ambient Air Temperature 28°C - Max. Ambient Air Temperature 48°C > Max. average over 24 Hrs. 57.8°C > Max. average over 1 Year 26.9° C + Relative humidity 100 % (Max.) - Thunder stonns per year ‘Occasional - Earthquake Loacing 0.07 - Wind speed 45 mis at 10 m height + Ground Temperature 35°C (orden of 0.9 nie) - Soil thermal resistivity 2 20° Cimiw Heavy condensation and sand storms also proveil. APPROVED CONTRACTORS Each contractor who undertakes electrical installations is required to have at least one electrical engineerfelectrician who holds a valid Competency Licance issued by DEWA and is responsible for correct installation and shall supervise and test the entire electrical works. The Gompetency Licences will be issued by DEWA only to those individuals who full the requirements sat-forth by DEWA, can understand and apply DEWA's Regulations. WORKMANSHIP Allelectrical installations shall be carried out in a neat, orderly workman like manner. Careful attention shall be paid to the mechanical execution of the work in connection with any electrical installation STANDARDS FOR EQUIPMENT AND MATERIALS All electrical installations shall comply with the requitements of the Regulations, relevant DEWA's Technical Specifications, latest Edition of the 1EE Wiring Regulations, and any other Regulations issued by DEWA from time to time, In ease of contradiction, DEWA’s Regulations shall prevail All equipment, apparatus, materials and accessories complying with the current Standards quoted in Appendix-t and/or conforming to relevant IEC (Intemational Electrctechnical commission) and ISO (Intemational Standards Organization) recom- mendations shall be deemed to satisfy the requirements of the Regulations, unless otherwise specttiod 17 18 19 SUBMISSION OF DRAWINGS Before the commencement of any electrical installations, large or small, new or additional, following details and drawings of the proposed installations shall be submitted to DEWA, for review and approval thereof i) Connosted LoadiMaximum Demand in the prescribed form given in Appendix-2. ii) Single Line Diagram, showing the L.V Distribution and tariff (kWh) metering [Refer to Appencix-5, for symbols) and relevant technical specications, ill) Load Distribution Schedule/s of final distribution boardis as per prescribed jorms, given in Appendix-8 & 4 iv) General arrangement and dimensional layout of electrical switch room's and/or anclosure/s with KWh metering facilities, as applicable, V)__ Site setting-out planikey plan with details of all extemal electrical services vi) Wiring layouts of the installations, (Roer to Appendix-5, for symbols) The design and layout drawings of substations which are specified for individual installations, shall also be prepared in compliance with DEWA's Regulations for supstations, and submitted in advarce for approval, POWER FACTOR (P. F.) CORRECTION ‘The overall Power Factor of all consumer installations shall be maintained within 0.9 (lagging) and unity, Generally all central air-conditioning plants, window & split type air-conditioning unitsiequipment shall incorporate integral means for power factor correction to achieve ard maintain a power factor not less than 0.9 lagging throughout their normal working range. All light fitings with discharge lamps, mercury vapour/sodium vapour, fluorescent tubes, etc. shall incorporate capacitors to obtain a power factor of 0.9 or above, lagging, Guideines on requirement of PF Improvements is also given in Section 8.1 of the Reguletions. UNDER VOLTAGE (U.V.) RELAYS WITH AUTO-RESET TIMER All air-conditioners or air-conditioning units/piantsiequipment installed within the consumer installation shall be provided with U.V. relays with auto-resel timer, The guidelines on requirement of UV relays aro also given in Section 8.2 of the regulations, HARMONICS AND RAPID VOLTAGE CHANGES Harmonics of the supply voltage are caused mainly by consumer's non linear loads connected to the supply system. A consumer's load is not allowed to cause deviations of the voltage characteristics other than those allowed in European Standard EN 50160, Nov. 1394, Any exces: deviations shall be compensated by the consumer at his cost INSPECTION AND TESTING OF INSTALLATIONS Contractors shall be required to submit their “Inspection Certificates" in the prescribed form, given in Appendix-6, on completion of the electrical installations. All installations and equipment installed therein, shall be subject to DEWA's inspection, testing and final approval before connecting the electric supply. The first inspection and testing by DEWA may be free of charge. All installations which require re-inspection and re-testing may be charged for each subsequent inspection, based on the type of consumer installation, connected load, ete. and as specified in Regulation 3.1.1 of Section-3. MAINTENANCE, PERIODIC INSPECTION AND TESTING Maintenance, periodic inspection and testing of every installation shall be carried out to ensure safety and salisiactory performance. The frequency of periodic inspection and testing of an installation shall be determined by the type of installation, its use and operation, the frequency of maintenance and the external influences 10 which it is subjected, Industrial and commercial installations shall at least be inspected every 2 years by an independant Consultart/Contractor, The ConsultantiContractor or person responsible for the maintenance, inspection and testing shall report to DEWA, in writing, any defects found in related parts of the existing installations and their rectifica- tion, together with a schedule of test results. Every installation shall also be subject to periodic, random inspection by DEWA, The ‘consumer shall arrange rectification of the defects, if any, notified by DEWA, at his own cost EXTENSIONS AND ALTERATIONS ‘The consumer shall not make any extensions or alterations to his electrical installation without obtaining priar approval from DEWA. Application in DEWA's prescribed form shall be submitted for every projectiinstallation whatsoever, large or small, new or additions, for provision of DEWA's supply linos and equipment, subject to terms and conditions issued by DEWA {rom time to time, SECTION -2 DEFINITIONS Following definitions shall apply for the purpose of the Regulations. Accessory. A device, other than current-using equipment, associated with such equipment or with the wiring of an installation Ambient temperature. The temperature of the air or other medium where the equipment is to be used. Appliance. An item of current-using equipment other than a luminaire or an Independent motor. Arm's reach. A zone of accessibility to touch, extending from any point on a surface where per- sons usually stand or trove about to the limits which a person can reach with a hand in any direotion without assistance. Barrier. A part providing a defined dagree of protection against contact with live parts from any usual direction cf access. Bonding conductor. A protective condustor providing equipotential bonding, Bunched. Cables are said to be bunched when two or mote are contained within a single conduit, duct, ducting, or trunking of, if not enclosed, are not separated from each other by a specified distance. Cable cleat. A component of a support system, which consists of elements spaced at intervals along the length of the cable or conduit and which mecharically retains the cable ot conduit. Cable Tray. A cable support consisting of a continuous tase with raised edges and no cover: ing. A cable tray is considered to be non-perforated, where less than 30% of the materal is removed from the base, Cable trunking. A manufactured enclosure for the protection of cables, normally of rectangular cross section, of which one side is removable or hinged. Circuit. An assembly of electrical equipment supplied from the same origin and protected against overcurrant by the same protective device(s). Circuit-breaker. A device capable of making, carrying and breaking normal load current and also making and automatically breaking, under pre-determined conditions. abnormal currents such as short-circuit currents. It is usually required to operate infrequently although some types Aare suitable for frequent operation. Conduit. A part of closed wiring system for cables in electrical installations, allowing them to be drawn in and/or replaced, but not inserted laterally. Current carrying capacity of a conductor. The maximum current which can be eartied by a conductor under specified conditions without ts steady state temperature exceeding a specified value. Currentusing equipment. Equipment which converts electical energy into ancther form of ‘onorgy, such as light, heat oF motive powor. Distribution board. An assemibly containing switching of protective devices (e.g. fuses, circuit-breakers, residual current operated devices) associated with one or mote outgoing Circuits fed from one or more incoming circuits, together with terminals for the neutral and protective circuit conduciors. It may also include signalling and other control devices. Means of isolation may be included in the board or may be provided separately. Double insulation. Insulation comprising both basic insulation and supplementary insulation. Duct. A closed passageway formed underground or in a structure and intended to receive one ‘or more cables which may be drawn in Earth. The conductive mass of the Earth, whose electric potential at any point is conventionally taken as zero. Earth electrode. A conductor of group of conductors in intimate contact with, and providing an electrical connection to, Earth Earth electrode resistance. The resistance of an earth electiode to Earth, Earth fault current. A fault current which flows to Earth. Earth leakage current. A current which flows to Earth, or to extraneous-conductive-parts, in a Circuit which is electrically sound, This current may have a capactive component including that resulting {rom the deliberate use of capacitors. Earthing. Connection of the exposed-conductive-parts of an installation to the main earthing terminal of that installation. Earthing conductor. A protective conductor connecting the main earthing terminal of an installaton to an earth electrode or to other means of earthing Electric shock. A dangerous physiological effect resulting from the passing of an electric current through a human body or livestock Electrical installation. An assembly of associated electrical equipment supplied from a common origin to full a spesitic purpose and having certain co-ordinated characteristics. Emergency switching. An operation intended to remove, as quickly as possible, danger, which may have occured unexpectedly. Enclosure. A part providing protection of equipment against certain extemal influences and in any direction protection against direct contact. Equipment. Any item for such purposes as generation, conversion, transmission, distribution or utilisation of electical energy, such as machines, transformers, apparatus, measuring instruments, protective devices, wiring systems, accessories, appliances and luminaires. Equipotential bonding, Electrical connection maintaining various exposed-conductive parts and extraneous conductive-parts at substantially the same potential. Exposed-conductive part. A conductive part of equipment which can be fouched and which is not a live part but which may become live under fault conditions. External influence. Any influence external to an electrical installation which affecis the design and safe operation of that installation, Fault. A circuit condition in which current flows through en abnormal or uni, .2nded path. This May result from an insulation falure or a bridging of insulation. Conventionally the impedance between live conductors or between jive conductor and exsosed-or extraneous-conductive-parts at the fault position is considered negligible. Fault current. A cutrent resulting from a fault. Final circuit. A circuit connected directy to currentusing equipment, or to a socketoutiet or socket-outlets or other outlet points for the connestion of such equipment. Fixed equipment. Equioment designed to be fastened to a support or otherwise secured in a ‘specific location. Flexible cable. A cable whose structure and matenals make it suitable to be flexed while in service. Flexible cord. A flexible cable in which the cross-sectional area of e2 exceed 4mm? hy conductor does not Insulation, Suitable non-conductive material enclosing, surrounding or supporting a conductor. Isolation. A mechanical switching device which, in the open position, complies with the requirements specified for isolation. An isolator is otherwise known as a disconnecter. Live part. A conductor or conductive part intended to be energised in normal use, Including a neutral conductor Luminaire. Equipment which distributes, fillers or transforms the light from one or more lamps, and which includes any par's necessary for supporting, fixing and protecting the lamps, but not the lamps themselves, and, where necessary, circuit auxiliaries together with the means for connecting them to the supply. For the pusposos of the Regulations a lamphoider, however ‘supporied, 's deerned to be a luminaire. LV ewitehgear and controlgear assembly. A combination of one of more low-voltage switching devices together with associated contiol, measuring, signaling, protective, regulating equipment, etc. completely assembled under the responsibilty of the manufacturer with all the internal electrical and mechanical interconnection and structural parts. The components of the assembly may be electromechanical or electronic. The assembly may be either type-tested oF pattially type-tested (see BS 496 Part 1). Main earthing terminal. The terminal or bat provided for the connection of protective conductors, including equipotential bonding conductors, and conductors for functional earthing, if any, to the means of earthing, Neutral conductor. The neutral conductor of @ 3-phase 4-wire system or the conductor of a single phase installation which is earthed at the source of the supply. Non-combustible. A non-combustible material is one which is not capable of undergoing combustion and satisfies the performance requirements complying with BS 476-Part 4 & Part 6, Nominal voltage. Voltage by which an installation (or part of an installation) is designated. The following ranges of nominal voltage (r.m.s. values for a.c) are detined - Extra low. Normally not exceeding 50 V a.c. or 120 V ripple free d.c., whether between condusiors or Earth. = Low. Normally exceeding exira-low voltage but nat exceeding 1000 V a.c. or 1500 V d.c. between conductors, or 600 V a.c. or 900 V dc. betweon conductors and Earth The actual voltage of the installation may differ trom the nominal value by a quantity within norma| tolerances. Overcurrent. A current exceeding the rated value, Fer conductors the rated value is the currant-carrying capacity, Overload current. An overcurrent occurring in a circuit which is electrically sound. Point (in wiring). A termination of the fixed wiring intended for the connection of current-using equipment, PVC (as insulation or sheath of cable). Polyvinyl Chloride Compound complying with BS 6746, Protective Conductor/Earth Continuity Conductor (ECC). A conductor used for some mpessuasicl Protection against electic shock and intended for connecting togethor any of the i) exposed-condustive-parss ii) extraneous-conductive-parts. iii) the main earthing terminal. iv) earth electrode(s) vy) the earthed point of the source, or an artiicial neutral. Residual current, The vector sum of the instantaneous values of current flowing through all five conductors of a circuit at a point in the electrical installation. Residual current device. A mechanical switching devico or association of devices intended to cause the opening of the contacts when the residual current attains a given value under specified conditions. Resistance area (for an earth electrode only). The suriace area of ground (around an earth electrode) on which a significant voltage gradient may exist g circuit. A circuit arranged in the formn of a ring and connected to a single point of supply, Short-circuit current. An overcurrent resulting from a fault of negligible impedance between live conductors having a difference in potential under normal operating conditions. Socket-outlet, A device, provided with female contacts, which is intended to be installed with the fixed wining, and intended to receive a plug. A luminaire track system is not regarded as 2 socket-outlet system. Space factor. The ratio (expressed as a percentage) of the sum of the effective overall of088-sectional area of cables forming @ bunch to the internal cross-sectional area of the con- duit, pipe, duct, trunking or channel in which they are installed Switch. A mechanical device capable of making. carrying ard breaking current under normal Circuit conditions, which may include specified operating overload conditions, and also of ying current for a specified abnormal circuit conditions such as these of short-ciroult. It may also be capable of making, but not breaking, short-circuit currents, Switchboard, An assembly of switcngear with or without instruments, but the term does not apply to groups of local switches in final circuit. Switchgear. An assembly of min and auxiliary switching apparatus for operation, regulation, protection or other control of an etecttical installation, XLPE (@s insulation of cable). Cross linked polyethylene complying with BS 5467, 34 att 3.24 3.22 3.2.3 3.24 3.2.6 SECTION -3 DEWA INCOMING SUPPLY AND TARIFF METERING GENERAL Power supply from DEWA network shall be subject to terms, conditions, tees, tariffs and instructions issued by DEWA from tine to time. The details of nominal electric supply from DEWA and general requirements, for compliance, are specified in Section.1 of the Regulations, ‘Consumer shall, before commencement of building construction, obtain confirmation from DEWA on availabilty of power supply. In general, where the total connected load exceeds 400 kW, provision shall be made within the building or plot for DEWA's substation. In some circumstances a substation may be required for connected load loss than 400 kW. Those requirements shall be confirmed in the issue of DEWA’s No Objection Cerificate which shall be revalidated at the end of every Six mont period. The consumer shall take all steps necessary to protect and keep safe DEWA's supply lines and equipment and shall immediately report any defect in or damage to any of DEWA's lines or equipment. POINT OF SUPPLY The point of supply which defines the boundary of DEWA equipment and where alec: tricity is made available to the consumer shall be cecided by DEWA. Point of supply shall be made available only at one location, within @ plovproject, unless otherwise approved / specified by DEWA. The cirauit breaker/s and/or main distribution bord/s provided at the incoming point of supply shall be designed and rated to suit particular applications and complying with regulations specified in clauses 4.5 & 7.2. The main Grcuit breakers at the point of supply (main switch) shell be marked as such and identifiable from other breakers to operate easily in an emergency. Where more than one incoming supply is available, in any premises, each ‘Main Switch’ shall be marked to indicate which installation or section of the installation it controls. Where a main L.V. distribution panel is connected directly to the low voltage side of the transformer, the main incomer circuit breaker proposed in the LV. panel is recommended 10 be tolally withdrawable type air circuit breaker. Where consumer's Main Low Voltage distribution board/panel is connected to DEWA's two or more distribution transformers, seperate bus-sectiors with mechanically and electrically interlocked bus-section breakers/solators shall be provided. 3.26 3.27 328 329 3.2.10 33 3.34 3.32 333 3.3.4 Al incoming cable terminations/Live connections in metering cabinets and other main and sub-main distribution boards shall be adequately shrouced and insulated, All exposed Live terminal Connections and bus bars in any low voltage distribution board shall be shrouded and/or insulated to DEWA's approval. ‘Consumer's main & sub-main Panels/Distribution Board's and final distribution boards shall be installed in Iccations to which access is available al all times. A minimum space of 1500 mm shall be provided in the front and 750 mm on the sides, to permit sefe operation, inspection, testing and maintenance, for cubicle type panels/switch boards. Panels with rear access doors shall have, in adcition, a minimum space of 750 mm in the rear, The mounting height (to the top of the board/s) shall normally be 2 metres from the groundifloor level All electrical switch rooms shall be adequately ventiated and provided with necessary heavy duty exhaust fan/s and fire resistantimetallc: louvered door's, as applicable. Adequate level of illumination shall be provided to facilitate safe operation at all tines. Incoming supply cablo/s to the consumer's main Distribution Board’s shall be totally segregated and identified from the consumer's cables, Termination of incoming supply cable al the Consumer's Metering Cabinet’Main Distribution Board (MDB) shall be carried out by consumer's contractor, in accordanca with Regulations 7.1.8 and 7.1.9, ‘TARIFF METERING For individual consumer premises, such as villas, farms, gardens, accommodation blocks, ete. the metering cabinet, with main incomer circuit breaker and metering shall be insialled outside, recessed, in the compound wall In multiple consumer premises such as residentiacommercial buildings, industries, large utility complexes, schools, etc. the main and sub-main distribution boards with associated metering shail be installed in separate electrical switch rooms, In locations close to the entrance boundary line and to which access is available a all times for operation, testing, inspection, maintenance and repair. Pror approval shall be ob- tained from DEWA as specttied in Clause 1.7 of Section 1 for every such premises. All tariff metering will normally be provided by DEWA and restiicted to one for each consumer installation, unless otherwise approved/spacified by DEWA. The minimum space required for installation of kWh meter shall be 300 mm wide and 400 mm high. The general arrangement and dimensional layout of the metering cabinets and array of meters installed in electrical switch roonvs and enclosure along with associated wiring shall be subject to DEWA's approval. The typical arrangement of Wh metering cabinevkWh meters is given, for guidance, in Appendix 7. -10 3.37 3.39 3.341 3.312 Metering by means of Current Transformers (CTs) shall be installed where the circuit breaker rating at the point of supply is 200 Amps and above. DEWA will provide the kWh meter/s and associated CTs for al tariff metering. in some circumstances consu- mer may be permitted to provide the kWh meter and CTs, complying with DEWA Technical Specifications and the Data scherlule given in Appendix-18. The above me- tet and CTs shall be tested and calibrated by DEWA prior to installation at site, The CTs shall be located on te bus bars immediately after the crcuit breaker/isolator, where the complete instalation is to be metered at. Removable links of adequate length shall be provided in the bus bar of each phase to enable easy maintenance and replacement 0! CTs. Three CTs shell be provided for each metering, The current transformer of following Rated Transformation Ratio shall be used as a standard requirement ; a) 20/5 b) 3800/5 ¢) 4900/5 a) 60/5 ©) 00/5 f) 1200/5 g) 1600/5 hy) 2400/5 Each Current Transformer shall have the fofowing markings ; a) Manuiacturer's name and/or trade mark. b) Rated primary current and secondary current ¢) Rated Frequency and primary maximum voltage, d) Accuracy Class. ©) Rated output (VA). f) Terminal (secondary winding) indentification (S1, Sz...) 9) Power flow direction (Ps, P:) Manufacturer may include any other markings that he considers to be included, ‘Transparent viewing window shall be provided in all metering cabinets and doors of enclosures housing the meters with associated distribution switchgear, for facilitating meter reading. All metering cabinets and enclosures shall be constructed from fire-resistanvinon- combustible material When meters are installed in electrical switch rooms, fire-resistaniinon-combustible bese plates shall be provided. Single core PVC or XLPE insulated & PVC sheathed cables to BS 6004 shall be used for connection to kiWh meters, except when installed! segregated within seperate metering cabinets. All_ metering cabinets/compartments shall be provided with padlocking and wire-sealing facilities on their external dooricover which shall normally be of hinged type. Generally all apparatus, circuit breakers, isolators, bus bars, removable lid section of bus bar - trunking, ets., installed on the supply side of any DEWA's metering shall have provision for sealing by DEWA, ‘The metering section/compartment in all MDB/s and SMDBVs if and when incorporated within, shall completely be segregated from other sections/compartments, 11- SECTION - 4 SELECTION OF CABLES, EQUIPMENT, MATERIALS & WIRING SYSTEMS 44 GENERAL 4.14 All equipment and metetials used in electrical installations shall be of good quality Complying with the relevant sections/clauses of the Regulations is a minimum Tequirement, 44.2 Every item of equipment used in the installation shall be designed and rated for operation on the nominal electric supply vollage declared by DEWA. 42 CABLES AND CONDUCTORS 421 Selection For general purposes and in normal situations PVC/XLPE insulated, standard copper conductor cables complying with BS 6004 & BS 6346/3 5467 shall be used for all fixed wiring installation of buildings. In inflammable/explosive situations, the cables shall be mineral insulated copper sheathed complying with BS 6207. Flexible cables and cords for use in aloctrical installation shall be PVC insulated and sheathed, stranded copper conductors complying with BS 6500/BS 6004. Cables for connection between ceiling rose and lamp holder ior pendant type light fitings and for enclosed luminzire shall be heat resistant siligone rubber insulated with stianged copper conductor complying with BS 6141 For lits and similar applications rubber insulated or PVC insulated flexible cables complying with BS 6977 shall be used. kWh meter tails shall normally be single core PVC insuleted and sheathed cables complying with BS 6004, as specified in Regulation 3.3. Single core cables armoured with sleel wire or tape shall not be used for a.c. circuits, 4.22 — Minimum Size of Conductors ‘The minimum size of conductor used for lighting circuit shall be 1.9 mm and 4 mm* for utility socket outlets. Minimum size of conductor for flexible cables and cords shall be 1 mm?, 423 Current rating, size and Voltage drop. All cables shall be adequately sized to carry continuously the normal current of the individual circuits based on various laying condiions, as applicable, and the maximum ambient temperature, Typical selection of the cables, recommended as a minimum, for general purpose applications, in the Emirate of Dubsi, is given in Appendix - 8, Tables 1,2 83. -12- AQ 425 426 427 4.3 434 432 The maximum voltage drop from the point of supply to any pcintiequipment, appliances and apparatus connected in the wirng installation shall not exceed 4% of the nominal voltage of the electric supply, unless otherwise specitied Colour Identification The colour identification of insulated cable cores of unarmoured, armoured and flexible cables and of Sleeve, band or disc of bare conductors shall be as given in Appondix-9, Wiring Installations Exposed to High Temperatures Any part of the wiring instatations such as the individual circuit cables, finet connections to equipment, appliances end light fittings shall be suitably rated for their salistactory performance ai temperatures likely to be encountered, by providing heat resistant sleeves/beeds for individual cores and/or heat resistant cables. ‘The heat resistant sleeves and cables shall be rated for operating temperatures net less than 85°C, particulary for end connections to luminaries. with incandescen! and halogen lamps and fixed heating appliances. Wiring Installations in Hazardous areas All light fittings & wiring accessories and other electrical equipment for use in potentially hazardous atmospheres shall be selected as per the guidelines specified in BS 5345, Load Balan 9 In all cases where three phase supply s availed, the various calegories of connected load such as lighting, socket outlets, water heaters, single phase air-conditioning units, equipment, apparatus, etc. shall be distributed and connected on Red, Yellow and Blue phases as evenly as possible, to ensure load balance between the phases at al distribution levels, WIRING ACCESSORIES AND FITTINGS Conduits and Fittings PVC conduits and fitings used in building installation shall be from high impact rigid PVC complying with BS 4607, BS 6053 & BS 6099 Part 2 section 2.2, suitable for use at ambient temperature up to 48" C. The material shall not soften or suffer structural degradation ata temperature of 70" C and shall be non-bygroscopic, fire retardant Stool conduits and fittings shall comply with relevant spectications in BS 4568, BS 6053, BS 6099 Part.1, BS 31 and shall be hot dip galvanized to class 4 protection, both inside and outside, Flexible steel conduits and fittings shall comply with BS 731 Part4 Trunking ‘Where applicable, surface and underfloor (uct) trunking and their fitings shell comply with BS 4678, Trunking acd fitings shall be constructed of steel, hot dip galvanized, both inside and outside or non-combustible insulating material with removable covers. Installation of the trunking shall be carried out strictly as per the manutacturers' guidelines, -19- 44 444 442 45 454 452 CABLE TRAYS & SUPPORTS. Steel cable trays, accessories and supports shall normally be hot dip galvanized or PYC coated and shall be either of the perforated type or ladder. ‘The cable trays shall have adequate strength and rigidity to support the cables installed, The trays shall be provided with upstands on both sides. All Fitings, Bends, Tees, Elbows, Couplers, ete. shall be of substantial sections and of the seme quality as the trays. Cables shall be fastened securely by puropse made lips, cleats or saddles, LOW VOLTAGE SWITCHGEAR AND CONTROL GEAR ASSEMBLIES Main & Sub-Main Distribution Boards The Main & Sub-Main Distribution Board/s (MDB/s & SMDBYs) which are installed within the consumer installations shall be factory buill assembly compiying with relevant BS EN 60439, The assemblies shall bo constructed only of materials capable of withstanding the mechanical, electrical and thermal stress as well as the effects of humidity which are likely to be encountered in normal service. Apparatus forming part of the assembly shall have clearances, creepage distances and isolating distances complying with BS EN 60439-1, maintained during the normal and relevant service conditions, The phase busbar, neutral bar and earth bar colour identified as given in Appendix-s, ‘The neutral bar shall be of the same cross section as the phase bus bar. The Circuit Breakers, Bus Bars, etc. provided in the MD8s and SMDBs shall be designed and rated to suit individual applications at the site conditions. The details and parameters of the individual equipment & components in MDBs/SMDBs, in general, may be appropriately selected and specified as per the typical guidelines given in Appendix 10, In general a Voltmeter (with R-Y-B ‘OFF' solector switch), Ammeter (with CTs as applicable), Max. Demand indicator/recorder, P.F. meter, indicating lamps and associated protective devices shall be provided in all MDBVs of 200 Amps rating and above. Provision of these in SMDB/s is not precluded. The switchgear, ecuipment and accessories shell generally comply with the standards specified in Appendix - 1 Final Distribution Boards The Distruibution Board/s (DBs) installed for connection of the final Circuits within the electrical installations shall be factory built complying with BS EN 60439, An integral isclator shall be provided for isolation of the incoming supply. -14- 46 4.6.1 4.6.2 463 The circuit breaker accessories, etc. shall generally comply with the standards specified in Appendx-1 Fewirable type fuses shall not be permittad in any type of wiring installation, The details of parameters of the incividual equipment & components and the DBs, in general, may appropriately be selected and specitied as per the typical guidelines given in Appendix-11 APPARATUS & ACCESSORIES Switches The switches provided for local isolation of electric supply to individual apparatus andi oF circuits. shall comply with BS 3676. The rating of the switches shall be selected based on individual applications, such as for resistive or inductive loads. The minimum current rating shall be 5A. For industrial use the switches shall be metal clad. Weather proof switches shall be Used for all outdoor installations, Switches installed for control of discharge lighting shall have a current rating not less than twice the steady state continuous current of the eircuits. Plugs and Socket-Outlets The single phase plugs and socket-outlets used in domestic and commercial installations shall comply with BS 1363. The socket-oullets shall be shuttered ‘ype, double pole, 3 pin flat type with switch. The industiial plugs and sooket-outlets shall comply with BS 4343 and shall be with switch, integrally built in or attached to it, The tating and type of socket-outlets with plugs provided shall be selacted to suit individual applications and shall not be interchangeable for different current ratings. Cooker Control Units Every stationary cooking appliance in domestic premises shall be controlled by a cooker control switch complying with BS 4177, separate from the appliance and installed within 2 meters of the applianc. The cooking appliance shall incorporate an integral earthing terminal. The cooker control switch shall be 2 pole for 1-phase and 4 pole for 3 phase appliance and connected to a separate final sub-circuit from the distribution board, Use of cooker contra! unit incorporating @ general purpose socket - outlet shall be avoided, to allow grouping of socket-outlet circuits in separate 30mA RCD/ELCB section. 18+ 4.6.4 46.5 466 4.6.7 4.6.8 Household and siniilar electrical appliances: The electrical appliances such as water heaters, cookers, hot plates, ete. which are used in consumer installation shall generally comply with BS3456 Control of Water Heaters Double pole switches (with neon indicator) ot appropriate rating shall be provided for control of water heaters. The final connection to the heater shall be made from a flex outlet plate mounted adjacent to the heater. The control switch for water heater situatedfinstalled in a bathroom or toilet shall be installed immediately outside the bathroom toilet Water heater shall be connected to a separate final sub-circuit ftom the distribution board. The heater shall incorporate an integral earthing terminal adjacent to the phase and neutral terminals. All terminals shall be housed in suitable recess with a splash proof removable cover. Every heater circult shall be protected by 30 MA RCCBIELCB. Control of Air Conditioning Unitvequipment ‘A.15 Amp switched socket outlet shall be provided for room air-conditioners to connect units only with cooling capacity upto to 18000 Bluthour. Double pole switch, of appropriate rating, with flex outlet mounted adjacent to the unit shall be provided for control of other toom air-conditioning units, Each room air-conditioning unit shall be connected to a separate final sub-circuit, irom the distribution board, A maximum of two air-conditioning units are permitted to connect on a single phase supply. Where three or more units are installed they shall be balanced as nearly as possible over a three phase supply. Extra Low Voltage Safety Apparatus The extra low voltage sefety apparatus such as electric buzzers & bells, mirrors lights & shaver socket ouets for installation in bathroom, ight fittings for underwater installations, ete. shall incorporate epproprietely rated double wound safety isolating transformer either intogrally builtin or mounted separately, with cartridge fuse or MCB in the secondary circ! Tho safety ‘solation transformer shall comply with BS 3535. Sogregation of low voltage and extra low voltage circuits shall be in accordance with Regulation 7.4.1 H.V. Discharge Lighting Equipment Every High Votage Discharge lighting equipment & installations shall be rated for voltages not exceeding § KV, RMS to earth, measured on open circuit and shall comply with BS 559. H.V, discharge lighting equipment, including neon signs for advertising or any other purposes, shall not be installed whithout prior approval from DEWA. “16- 4.6.9 4.6.10 Satety and Emergency Light Fittings Safety lighting to meet operational requirements shall be provided to suit particular applications such as industres, procuction tines, hospitals, utlity complexes, stadiums, shopping centres, auditoriums, ete. The source of supply for safety lighting shall be either maintained or non-maintained type as appropriate to suit individual applications, All electrical switch-rooms and operational areas shall be provided with adequate number of emergency light fittings. The salety and emergency ight fittings installed shall comply with BS 5266 and shall be rated for a period not less than 3 hours continuous operation. The light fiting’s shall normally incomorate necessary battery and charger within, The sefely light filtngs shall also incorporate appropriate sign in Arabic and English such as 'EXIT" and directional arrows, as applicable to incividual locations. Electric Motors and Starters Installation of 1-phase motors rated upto 3.7 KW (SHP) and 3-phase motors upto 110 kW (150 HP) only shall normally be permitted unloss otherwise approved by DEWA. Where a large number of motors above 150 HP are proposed, the advice of DEWA shall be sought on availing a bulk supply, All electric motors shall be adequately protected agains! overload, short circuit, earth leakage and additionally, against loss of one or more phases, voltage fluctuatons, etc. as deamod essential to suit individual applications. Starters shall be provided with overload relays of the thermal type with) automatic compensations for variation in ambiont temperature between 2.8 Cand 48° C. All three phase motors over 3 HP and single phase motors above 1 HP shall be provided with current limiting starting equipment to effectively keep the starting current within the following limits. ‘Type of Supply Rating of Motor Max. permissible Starting current Single Phase 1 HP - 5 HP 5 times full load current Three Phase Less than 1SHP 5 times full load current ASHP to < 50 HP 2 times full load current 50 HP and above. 1.5 times full load current Motors upio and including 11 KW (15 HP) may be connected for direct on-line starting with over current protection. “7- 4.6.11 The starting equipment to limit the current may consist of any of the following type or other approved by DEWA, a) Star- Delta b) Primary - Resistance ©) Auto - Transformer All motors shall be provided with an isolator, for isolating the motor from the supply uring periods of inspection or maintenance. Such means cf isclation shall effectively interruot the supply an all phases. The isolator may be integral with the control goar or separate, but shall be in close proximity to the motor. An emergency stop push button shall be Incorporated in the contro! gear. When motor starting gear is energised from an auxiliary circuit, the circuit shall also be isolated during maintenance. All starters, isolators and push buttons shall be clearly marked in Arabic and English stating which machine they contro! and their function. To avoid confusion the words ‘START and ‘STOP’ instead of OPEN’ and ‘CLOSED’ shall be used. Motors and their control gear shall be located in well ventilated situations with adequate space for operation, inspection and maintenance, Stand-by Generators Installation and connection of standby generators in the consumer's installation, for the purpose of maintaining power supply under mains falure conditions, shall be permitted ‘only with prior approval from DEWA. The change-over circuit breaker or isolator shall have 4 - Poles for 3 - Phase supply and 2 - Poles for 1 - Phase supply to ensure that the phases and neutral o! the two systems remain separate and distinct. The installation shall ensure that there will be no possibilty to parallel generator supply with DEWA supply under any circumstances or conditions. Adequate mechanical and electrical interlock between the Incomer circuit breakers o1 isolators of both generator and DEWA supplies shall be provided. The full details-of the equipment, circuit and wiring diagrams, deteils of essential loads, etc. shall be submitied to DEWA for approval before commencement of the work, ASSESSMENT OF CONNECTED LOAD AND MAXIMUM DEMAND. Lighting and small power circuits Ail lighting and fan circuits shall generally be installed with maximum load per circuit within 600 W & circuit breaker rating 6 A (1.5 mmr2 circuit conductors). or 1200 W & cir. cuit breaker rating 10 A (2.5 mm? /1.5 mm? circuit conductors). A minimum of 100 W shall be considered for each normal ligtting and fan points, Fluorescent lamp may be assessed as 1.8 x lamp W. Wherever fittings with discharge light, compect fluorescent lamps or low voll lamps are installed, the circuit breaker rating, circuit conductor sizes and number of fittings may bbe suitably selected based on the actual load, including losses, for specific application Prior approval from DEW shall be obtained for every installation, 18 are A radial final sub-circult mey be installed to serve a maximum of five 13 A, switched socket-outlets in room other than kitchen and controlled by a 20 A circuit breaker in the distribution board. A maximum of ten socket-outlets in room other than kitchen may be connected to a ring circuit, controlled by a 80 A circuit breaker, A current demand of 1 A shall be assumed for each 13 A switched socket outlet cir cuil. A minimum of 200 Watts per point may be considered for each 13 A switched socket-oultlet, instalied for general ulilily purpose, other than in kitchen. All twin socket outlets shall be considered as two separate socket-vutlet paints, A kitchen area may need separate circuits, A curtent demand of 15 A shall be assumed for each 15 A switched socket-cutlet circuit, However, for general purpose utiity socket-outlets an assumed load of 1000 W per socket-outlet installed in commercial and industrial premises and 500 W per socket- outlet in residential premises may be permitted, For stationary appliance and equipment including air-conditioners, the actual load of each appliance and equipment shall be considered as connected load, Current demand of point such as electric clock and other current using equipment of rating not greater than 5 VA may be neglected. For multi consumer installation which includes commercial type of premises such as Shops, Showrooms, Garages, Workshops, etc. where provision for connection of additional load may be required, the assumed connected load of each spare/spacel circuit shall also be indicated in the load distribution schedules submitted for DEWA's approval. Maximum Demand Alldistibution boards shall be rated or total connected loads before a diversity factor is applied, ‘The demand load of each final sub-crcult is determined by adding the actual or assumed load of individual points/appliance/equipmert, whichever is higher. An allowance for diversity may be permitted where appropriate. The deiails of load distribution schedules shall be submitted for DEWA's approval in the format given in Appendix 2,3 & 4, The total connected load of individual distribution lev- elsicircuits shall _be determined as recommended in Regulation 4.7.1. An appropriate diversity factor, worked out by a suitably quaified electrical engineer, shall be permitted to determine the maximum demand at the main or sub-main distribution level. The limit of Maximum Demand! in kW, permitted at Main Distribution Board (MDB) con- nected to DEWA’s supply feederrtransformer is nated below for guidance. a) 400. A Feeder 200 kW b) 1500. KVA Transformer 1200 kW ©) 1000 kVA Transformer : 800 kW 4d) 500. kVA Transformer 400 kW -19- The overload protective devicerincomer circuit breaker in the MDB shall be suitably set at the correspending design current. Since maximum demand can vary on each type ot project such as residential, commercial, industrial, etc. other method, used by an installation designer with sutable degree of knowledge and experience of the diversity epplicable to a particular installation, is permitted. However, the design method and the proposed diversity shall be clearly indicated in the design drawings and load schedules submitted for DEWA's approval. = 20- 54 64d 5.2.2 5.23 53 5.34 SECTION -5 EARTHING AND EARTH LEAKAGE PROTECTION CONSUMER'S EARTHING SYSTEM Every consumer installation shell be provided with separate earthing system, installed and maintained by the consumer. Each consumer's earthing system shail comprise of ‘Earth electrode/s’ main earth lead connected between the 'Eaith electrode/s’ and the consumer's main earthing terminals or bar, Earth continuity conductors (ECCs) of every outgoing circut from the main, sub-main & final distribution boards, equipotential bonding of all metal work & exposed conductive parts and enclosures, ete. The consumer's earthing system shall be connected to DEWA’s earthing system (in ‘coming supply cable armour/Earth continuity conductor, as approved by DEWA). CONSUMER’S MAIN EARTH ELECTRODE In general, minimum one Main Earth electrode shall be provided for each incoming point of supply/consumer's Main Distribution Board (MDB), within the consumer's premises. The ‘Earth electrode’ shall normally comprise of 20mm / 16mm diameter copperisteel core bonded earth rod set with driving pin and head driven toa minimum depth of 3 metres. The earth electrode shall be installed inside a 300mm x 200mm x 300mm earth pit with inspection cover. The connection to the earth electrode, within the inspection git shall be soundly made by a corrosion resistant tertrinal clamp, ‘The cansumer's “Main Earth electrode’ shall be installed as close to the main distribution board as possible. Wherever, more than one ‘Earth electrode’ is installed, within the consumer premises, these shall be spaced at minimum 6 metres apart The main earth electrode resistance shall not exceed 1 ohm, for each incoming DEWA supplyiMDB, ‘The resistance from any point of the Earth Continuity Conductor to the Main Earth Electrode shall not exceed 0.5 ohm. The consumer's earth electiode resistance and continuity of ECs shall be periodically checked and maintained as above, to ensure consumer safety. EARTH CONTINUITY CONDUCTOR (ECC) Every circuit in the Main, Sub-Main and final distribution boards shall be provided with a seperate, green and yellow (G/Y), PVC insulated copper 'ECC’. The minimum cross sectional area of ECCs shall be selected as specified in Appendix-12. -2t- 5.82 5.33 5.4 544 5.2 5.6.1 55.2 The ECCs shall be terminated at electrical equipment, apparatus and distribution switchgear, light fittings, mounting boxes of switches & sacket-outlets, ete. with tinned copper lugs, as applicable, at both ends on purpose made earth terminals. All bus bar risers installed for electrical distribution in high rise buildings and other consumer installations shall incorporate an adequately sized ‘ECC’ either integrally within or run separately along the riser EARTH LEAKAGE PROTECTION The earth leakage protection shall be suitably designed and incorporated in each and every consumer installation The Earth Leakage Circut Breakers (ELCBs\/Residuat Current Circuit Breakers (ACCBs) shall generally comply wil BS 4293, Recommended value of operating cur: rent of ELCBS/RCCBs are specified in Appendix-13. Operation of the ELCBS/ACGBs, earth leakage detection system, etc. shal be periodically checked and tested ‘o ensure consumer safety. EQUIPOTENTIAL BONDING All metal work of the consumer's installation, other then current carrying parts, including cable armour, metel conduits, metal cable tray & trunking sections, metal accessory boxes, exposed metal works of consumer's appliance, apparatus, equipment, machines, building structures and the like with metallic enclosure and parts, metal water pipes, etc, shall be provided with equipotential bonding conductors. The cross-sectional arca of ecuipctential bonding conductors shall be selected as specified in Appendix-12. ‘The oquipotential bonding conductors shall be connected to the main earthing terminal within the consumer's wiring installations and the continuity shall be tested and maintaned by the consumer. +22 612 613 6.16 617 618 6.1.10 6141 6.142 SECTION - 6 INSTALLATION OF CONDUITS, TRUNKING, TRAYS & ACCESSORIES TRUNKING AND CONDUITS ‘The type and material of the trunking and conduits shall be selected appropriately to suit indivicual site locations and complying with Regulations specified in clause 4.3 of Section 4, ‘The trunking and conduit wiring installations shall be carried out in a noat, orderly workmanlike manner with purpose - made accessories such as inspection bendsitees, terminal/diaw - in boxes, el. As far as possible, the trunking and conduit runs from the elecirical switch rooms to the indivicual consumer DB/s shall be routed only within common electrical service routes & riser ducts. Long trunking anc conduit runs from the electrical switch roorw’s located on ground floor to cansumer DBs located on upper flcor/s shall be avoided and armoured cables shall be installed in cable trays. Cable trunking may be used for housing single core PVC cables at special situations. where installation of conduits is difficult due to space limitations. Trunking and wiring conduit installations which are surlace exposed shall, as far as possible, have straight runs with branches at right angle only, Draw-in boxes shall be provided in all straight conduit runs exceeding 15 metres, Conduit runs having ‘90° bends’ shall be provided with draw-in boxes for every 2 bends, Trunking and conduit shall be completely installad before any cable is drawn in. Draw-wires shall be provided in all concealed conduits (and duets) with the ends left {ree at the outlet boxes for pulling the wiring catles. All the trunking and conduit runs shall be free Irom sharp edges and burs throughout their lengths, Suitable grommets and bushes shall be provided at the terminal outlets. The ttunking and conduit runs shall be supported at regular intervals and the number of cables that may be installed in trunking shall suitably be selected as recommended in Appendix-14 & 15. All the terminal and intermediate ends of the PVC conduits shall be firmly secured with suitable adhesives as recommended by the manutacturer. -23- 64 64 64 61 et 64 a4 Ca 61 6A. 64 64 62 62 6.2, 13 16 7 18 20 21 23 24 1 2 The circuit wires, bunched and installed in all vertical trunking runs shall be clamped! secured within the trunking at regular intervals, not exceeding 2 metros and at the terminal ends. The standard conduit boxes, draw-in boxes and mounting boxes of light fittings and appliances shall be lixed to the building structure independently of the wiring conduits. All exposed threads, tool-marks or visibla damage to the protective finish of the steo! trunking and conduits shall be coated with Zinc rich paint immediately after installation. Suitable expansion couplers shall be provided in all trunking and conduit runs at the expansion joints in the building structure and at regular intervels in all runs exceeding 7 metres in length or as recommended by the manulacturer. Suitable purpose-made boxes with adapters, ceiling 1oses etc. shall be provided at all individual outlet points 0} the wiring instalations Light fitings used with tungsten filament and halogen lamp shall be suitably segregated and supported from the PVC conduit and terminal outlet boxes to prevent deterioration due to asscciated high temperature tise, The conduit runs which are concealed within the building structure such as in floor, wall, roof, column etc, shall be provided with 2 minimum screed cover of 10 mm. ‘When the trunking and conduit runs are installed with chases in the building structure they shall be firmly fixed at regular intervals with purpose-made crimpets and/or saddles. The standard conduit boxes, draw-in boxes, flocr-outlet boxes etc, shall be installed with its coverlid flush with the outer finish of the building structure. Only flush type switches, socket outlets and accessories shall be used for concealed wiring, In surface mounted industrial installations and where situations sudject to fre risk, only galvanised steel conduits shall be used. PYC conduits shall not be used for such applications. Galvanised steel conduits shall not te used under floor ties of buildings in concealed wiring systems embedded in walls or floors. PVC. conduits shall be used for all such applications. CABLE TRAYS Trays for supporting cables are recommended for use in warehouses, industrial plant and equipment room, cable trenches, shalts in buildings, etc, The type and material of the cable trays shall be selected appropriately to suit individual site locations, and complying with Regulations specified in clause 4.4 of Section 4 24. ih 6.2.4 6.25 6.26 a27 The cable trays shail be supported at regular intervals with purpose made supports and the number of cables installad in the trays shall suitably be selected as recommended in Appendix-14 & 15. Cable trays installed in outdoor locetions, wherein the cables are exposed to the sun shall be provided with sun-shade covers, secured to the trays, with adequate ventilation and as recommended by the manufacturers. Cables shall be fastened securely by purpose-made clips, cleats or saddles at spacing as recommended in Appendix-14, Cable ties shall not be used to support multicore cables installed on cable trays fitted vertically. Cable trays shall not be used in locations where they will be subjected to severe physical damage. Suificient space shall be provided and maintained eround cable tray to permit adequate access for installing and maintaining the cables. = 25. SECTION -7 INSTALLATION OF CABLES, EQUIPMENT, ACCESSORIES AND WIRING SYSTEMS fat TAA TAS TAA TAS 718 TAT TAB 7AA0 TAAL 72 724 72.2 723 ARMOURED CABLES Armoured cables may be installed either directly buried in ground, drawn through ducts, laid in conorete trenches - cleated to wall, or mounted on cable trays. The current carrying capacity of the cable/s shall be determined only after applying suitable correotion factors based on the installation method of the cablels. Only armoured cables shall be used for underground installations. The armoured cables, for underground installation shail normally be laid at 80 cm below the ground level and provided with a layer of at least 15 cm impervious soil around. Where protective covers are required, they shall be carelully centered over the cables, throughout their length. The covers shall de of adequate width to protect the cables, with a minimum overlap on each side of 50 mm Coloured PVC warring tapes shall be laid after filing, above the cable, upto 80 cm below the ground level. The routes of ali cables shall be clearly marked by cable route markers, at regular intervals not exceeding 10 metres along straight runs and 2 metres at deviations in the routo. The route markers shall normally indicate the voliage level in Arabic and English, Cables may be installed on cable trays at specitic locations and es recommended in clause 6.2 of the Regulations Minimum internal racius of bend for cable in fixed wiring installation shall not be less. than 8 times the overall diameter of the cable. No joints shall be permitted on any cable runs in Consumer's fixed wiring installation, Where cables or wiring system passes through floor, wall, parlitons oF ceiling, the openings remaining after passage of the wiring systems shall be sealed to the degree of fire resistance required. Cable glands used for armoured cables shall be of brass compression type, complying with BS 6121, with earth tag and PVG shroud, All terminations of cable conductors shall be mechanically and electrically sound. Every termination shall be made by means of a terminal or compression type socket! lug, to the approval of DEWA, end shall not Impose any mechanical strain on the terminal or socket/lug. Separate Earth Continuity Conductors (ECCs) shall be installed and terminated for each feeder/circuit, as specified in Section-5 of the Reguiatons. DISTRIBUTION BOARDS All distribution beards either main, sub-msin or final DBs shall be installed in locations to which access is available at all times for operation, testing, inspection, maintenance and repair Main, sub-main or final Distribution Board/s shall not be installed within bathrooms, toilet, damp or wet locations, bedrooms, kitchen, above sinks, store roms, high ambient rooms, dangerous or hazardous locations or below any staircase All rain, sub-main and final distribution boards shall be selected and designed based on the guidelines specified in clause 3.2 (section-3) and 4.5 (Section-4) of the Regulations, =26- 7.24 725 726 7.27 7.28 7.29 7.34 732 7.33 7.34 7.35 7.36 737 74 7.44 Each distribution board shall incorporate means for isolation of mains supply in the form of either circuit breaker or incomer isolator as applicable Every circuit breeker or fuse within the distiibution board shall be identified and labelled to indicate the apparatus or circuit it controls, Each final distribution board shall only supply the circuits in the same floor araa, where the distribution board is located, except for specific applications such as ‘staircase & common corridor ighting’ in high nse buildings, ele, Prior approval shall be obiained from DEWA for every application, as specified in clause 1.7 (Section - 1) of the Regulations. In multi consumer installation, such as commercial or residential buildings, the consumer's distribution boardis shall be installed within the respective consumer's premises (e.g. Shops, Flats, ete.) Incoming supply cable installed to any distribution board shall be totally segregated and identitied from the outgoing circuit cables/wiring All Distribution Boards shall be installed flush or surface mounted at a height not ‘exceeding 2 metres to the top of the distribution board from the fished floor level. BUSBAR TRUNKING SYSTEMS (BUSWAYS) Busways shall be permitted for installation only where adequate access is available for inspection and repair throughout their entire length. Each busbar riser, proposed for installation in high rise buildings, is recommended to Supply a maximum of 6 floors only, The enclosures of busways shall be securely supported at intervals not exceeding 18 metres. Wherever busbar trunking systems are installed on the supply sid2 of any DEWA's kWh metering, suitable provision for sealing by DEWA shall be made as specified in Regulation 3.3.10, The requirement of earth continuity conductor (ECC) and equipotential bonding shall be as speaitied in Seotion-5 of the Regulations. Wherever the busway passes through the wall or floor, it shall be provided with fire bartier/sealing to the degree of fire resistance required The tap off unit installed at each floor level in a busbar riser shall be al a height between 50 cin and 180 om from finished tloor level ard shall have adequate access for operation, maintenance and replacement. WIRING SYSTEMS AND ACCESSORIES Segregation of circuits, phases and wiring systems All wiring and accessories shall be selected and installed to suit individual locations and complying wth relevant Regulations specified in Section-4, in addition to the {following tequrements. Crrouits from different distribution boards shall not be installed in a common conduit or trunking. The circuit wires of different voltage grades shall be segregated wth barriers in trunking runs or installed in separate conduits. - 27. 72 7.43 The cireuit wires of individual categories such as lighting, power, emergency, etc. shall be segregated with barriers in trunking runs or installed in separate conduits Where a residential premises is supplied with a tiree phase supply, as far as possible, the light fitings, socket outlets, water heaters. cookers and other single phase apparatus instaled within any room shall not be connected to more than one phase. Wherever more than one phase cannot be avoided, 2 minimum distance of 2.0 metres shall ba maintained between any oullet, accessory or appliance connected to different phases of the supply. Where switch box contains more than one phase. for group switching, approved switch boxes with phase barriers shall be usad and labelled ‘o indicate that 380 Volts exist at the box. All circuit wires shall be colour identified as specified in Regulation 4.24. Where a wiring system is located in close proximity to non-electrical service, the wiring sysiem shall be adequately segregated and protected against hazards likely to arise from the presence of the other service in normal use. Provision shall be made for safe and adequate access to all parts of the wiring system which may require inspection, maintenance or replacement. No switches controling light fitting or water heater, etc. shall be installed in bathroom In kitchen and in situations where water is regularly used, no switch shall be mounted within 2 metres of any water tap, wash basin or sink. Ii this is not possible, ceiling mounted insulated cord operated switches shail be used. No socket-outlet shall be mounted within 2 metres of any water tap, wash basin or sink ina kitchen, Mounting heights of accessories All lighting switches, D.P. switches of Air Conditioning units & Water heaters, Ceiling Fan Reguletors, Shaver Socket outlets, etc, gonerally used in the electrical installation shall be mounted at 125 cm from the finished flocr level. All switches shall be mounted in readily accessible positions. 13 A switched socket outlets used for general purpose shall be installed at 45 om above the finished floor level. 13 switched socket outlet provided in the kitchen shall be generally at a height of 25 om from the wark top. All accessories shall be suilably selected and installed as recommended in Section-4 of the Regulations, Identification labels and notices In general all sactions of the consumer installation, circuits, protection devices in the distribution boards etc shall be provided wth suitable identification labels to clearly indicate the location ané purpose of each item or circuit. Instructions oF Caution notices {for correct operation shall also be provided wherever there is a pessitilty of confusion All labels must be in both English and Arabic and of letter sizes to suit individual application 28- SECTION - 8 POWER FACTOR CORRECTION CAPACITORS AND UNDER VOLTAGE RELAYS at 814 B12 8.1.3 etd 8.1.5 are BAT 819 POWER FACTOR (PF) CORRECTION: ‘The power factor of every consumer installation shall be within the range of 0.9 lagging and unity In general all Air-Conditioning units/plants/equipment, machines, metors, light fittings \with discharge lamosimercury vapour/sodium vapourffluorescent tubes, ote. for uso in the Emirate of Dubai, shall be provided with capacitors or other approved means to achieve and maintain @ power lactor of 0.9 lagging or above, throughout their normal working range. For large installations, where individual load compensation cannot be achieved, overall compensation at main or sub-main distribution levels by incorporating capacitor banks with automatic regulated steps, within the consumers insiallation, shall be permitted, The PF. correction capacitor shall be either of dry or ol filled, encapsulated, sealed type. Capactots shail be enclosed or guarded to prevent accidental contact of conducting Metal parts with exposed energised paris, terminals or buses associated with thor, The capacitor installed for P.F. correction shall be provided with means ‘or its prompt automatic discharge immediately when the capacitor is disconnected from tho source of supply. The discharge circuit shall be either permanently connected to the terminals of the capacitor or capacitor bank, or provided with automatic means of connecting it to the terminals of the capacitor bank on removal of veltage from the line. Manual means ot switching or connecting the discharge circuit shall not be permitted The capacitors and assooiated components such as PF regulator, indicating intstruments, contactors (of capacitor switching duly), control switches, etc. shall be designed and rated for operation on the electric supply and ambient conditions specified in clause 1.2 & 1.3 (section-1) and selection details recommended in Section 4 of the Regulations. The current carrying capacity of the conductors used in capacitor circuit shall not be less than 1.5 times of the rated current of the capacitor. The current carrying capacity of conductors that connact a capacitor to the terminals of @ motor of to motor circuit concucters shall not be less than one third of the current carrying capacity of the moter circuit conductors and inno case less than 1.5 times the rated currant of the capacitor. ‘An over current device shall be provided in each circuit for each capacitor bank. A separate over current device shall not be required for a capacitor connected on the load side of a motor overload protective device. The rating or selling of the over current device shall be as low as practicable. The capacitors shalll be suitable for operation under harmonic current conditions. -29- BA10 eat B142 8143 8.144 82 824 822 823 8.2.4 The contactors used in the capacitor bank shall be able to withstand switching surges. Means shall be installed to isolate each capacitor, capacitor bank, or capacitor installation from all sources of voltage and to remove from service as unit. All non-current carrying metal parts of capacitors shall be earthed as specified in Clause 5.5, Section 5. Each capacitor shall be provided with @ nameplate indicating rated voltage, frequency, kVar, number of phases, details of liquid filed (if any), discharge device and name of the manufacturer. The controls and protection device provided in the capacitor bank shall be checked and maintained regularly. Wherever capacitor bank/panel is installed on the supply side of any DEWA's kWh metering, adequate sealing provision shall be made as specified in Requlation 2.3.11 of Section 3. UNDER VOLTAGE (U.V.) RELAYS WITH AUTO-RESET TIMER Al) air-conditioners or air-conditioning unitséplants/equipment installed within the consumer's installation shall be provided with Under Voltage (U.V.) relays with fixed voltage out off setting at 75% of the nominal supply voltage, within 0.1 seconds, and auto-reset timer with adjustable time setting between 5 and 10 minutes. “The auto-reset timer of the ULV. relays shall be set at values specified in the schedules, approved by DEWA, to suit individual installation. Necessary provision for sealing may be incorporated in the relay to restrict access for adjustments of the setting. The ULV. relays with auto-reset timer shall normally be incorporated within the respective air-conditioning unitvequipment or in their control panels. For small air-conditioners, provision of U.V. relays with auto-reset timer within tho consumers distribution board shal be permitted for individual or group of units. Prior approval shall be obtained from DEWA on every such application, ‘The U.V. relays with associated controls shall be checked and maintained regularly. - 30 a4 ona O42 218 9.2 9.2.1 9.2.2 9.23 9.26 925 98 9.34 9.3.2 9.3.8 SECTION -9 CONSTRUCTION SITE INSTALLATIONS. General Application for temporary power supply shall be submitted to DEWA at least one month in advance of the power requirement ‘Temporary power supply shall be permilied for construction purposes subject to terms, conditions, fees, tariffs and instructions issued by DEWA from time to time. The consumer shell comply with the safely requirements specified for permanent installation, in addition to the specific requirements on installation at construction sites recommended in this section of the Regulations. Every assembly for the distibution of electricity on construction sites shall comply with the requirements of BS 4363 and BS EN 60439-4. WIRING SYSTEMS AND DISTRIBUTION BOARDS. Every wiring system shall be so arranged that no stiain is placed on the terminations of conductors unless suah terminations are designed for this purpose. No cable shall run across a site road or a walkway unless adequate protection of the cable against mechanical damage is provided. All cables used on construction sites shall have a metal sheath and/or armour which shall be eflectively earthed ang continuous. Flexible cords for use at the site shall ‘comply with BS 6141 The metering cabinet, distribution board/s or any wiring installations, installed outcoor, shall be of weather proof type. Means of emergency switching shall be provided on the supply to all equipment from which it may be necessary to disconnect all ive conductors in order to remove a hazard EARTH LEAKAGE PROTECTION In addition to the over current and short circuit protection, every circuit shall be protected for earth leakage. Alll final suo-circuits connected to 13 switched socket outlets, portable tools or equipment shall be protected with ELCB/RCCE of rated operating current 30 mA. 100 mA ELCB/RCCB shall be provided for protection of other lighting circulls, fixed ‘equipment, etc. unless ctherwise specified. Consumer shall check and test the earthing systems, operation of ELOBs/RCCBs, wiring installation, etc. regularly to ensure safety of the installation. <31- APPENDICES Appendix Page 1 Reference Standards 34 2, Details of Connected Load/Max. Demand (format) 35 3. Load Distrioution Schedule - 3 phase (format) 36 4, Load Distribution Schedule - 1 Phase (formal) 37 5 Electrical Symbols 38-40 6. Contractor's Inspection Certificate (format) ar-az 7. (A) Typical arrangement of Metering Cabinet 43 on Compound Wall 8) Typical arrangement of kwh meters in ag Electrical Service Room (©) ‘Typical Electiical Services Room with 4 No. MDB 45 (0) Typical Electrical Services Room with 1 No. 46 cubicle type L.V. switchboard/panel 8, Selection of Cables Table-i :- Single Core PVC Insulated non-armoured, Stranded Copper Conductors. a7 Table-2: Multi Core armoured PVC insulated, Copper Conductors. 48 Table-3:- Multi Core armoured XLPE insulated, Copper Conductors. 49 9. Colour Identification of unarmoured, armoured and flexible cable cores and bare conductors. 50 10 Specifications of MDBs/SMDBs (format) 51-53 " Specifications of DBs (format) 54-56 12. Earth Continuity Conductors (ECGs) and Equipotential Bonding Conductors. 87 13. Earth Leakage Protection 58 14. Spacing of Supports for Trunking, Conduits and Cables. 59 15. Number of Cables that may be installed in Trunking, Conduits and Trays. 60 16. Data Schedule for LV Electricity Meters and Current Transformers 61 -93- APPENDIX - 1 REFERENCE STANDARDS All equipment, apparatus, materials and accessories complying with relevant recommendations in the following standards‘documents shall be deemed to satisly the requirements of these Regulations, unless otherwise specified (Clause 1.6, Section 1). PYC insulation (for power & lighting) + PVC insulation for switchgear & control wiring) Thermo-setting insulation - Mineral insulation Flexible cables & cords Cable glands Conduits and Conduit = Steel - PVC + Flexible Steel Degrees of Protection Distribution assemblies for construction site Earthing Electrical Accessories + General - Geling rose = Cooker control units + Plugs & Socket-outlets - Switches Emergency Lighting Hazardous areas Household appliances Isolating Transformer Low Voltage Switchgear and Control gear assemblies = General - MCB a Moc = RCCBYELCB - Fuses = Busbar trunking system Neon Signs, Non combustibility test Trunking, Ducting and Fittings ‘Thermal classification of electrical insulation BS - — Brtish Standard lec International Electrotechnical Commission BS 6004, BS 6346, BS 6231 BS 5467, BS 6284, BS 7211 BS 6207, BS 6081 BS 6500, BS 6141, BS 6004 BS 6977 BS 6121 BS 4568, BS 6053, BS 6099 BS 31 BS 4607, BS 6053. BS 6099 Bs 731 BS EN 60529 BS 4363 BS 7430, BS 951 BS 5733 BS 67 BS 4177 BS 546, BS 196, 8S 1363, BS 4943 BS 3676, BS EN 60947-3, BS 5266 BS 5345, BS 5501 BS 9456, BS EN 60035 BS 3535 BS EN 60439, BS EN 60947, BS EN 60947-1 BS EN 60898, BS 3671 BS 4293 BS 88, BS 1361 BS EN 604392 BS 559 BS 476 Bs 4078 BS 2757 502 227 702 227,245 423, 614 423, 529 364-7-704 964-5-54 47 439-1 & 3 898 755 439-2 1084 (oseud ©) (9seug 4) JOATG) vos-szt(e) vooLoidn (2) yosodn (i) (uewoou jo Bugey) say@py jo adh. aL “ ¥OLOWHLNOD. (Hd €) GYO1G3L93NNOO W1OL ALIse3/0 (Ha ©) anwwisa xWH aan (01 ¢3493NNO9 Bas S¥Hd Had Q¥O7.G3103NNOO WLOL evel FQ A VNB: 01. 03L9aNNOO BON ONOSINO | HSWOON! te) NOE wt Me uw | ww d1) DAd goW eon er swuvwias |_At BOON 30334 7 fino aa ST ee n= 0¥O7 03192NNOO xzeaavo | Be sav ONLY SQW 4O NOLLV9OT ‘ON 107d vauy GNYW3G "K¥WWaVO1 G3103NNOO 40 StIviaG meme ENV LINSNOD, ; 49 sas / saw a0 a FINMO sree 1G NOMS TANGO CANNYTd “= /ONIGTING ATI: Lo8rOdd 2- XIONSdel (1 uonaas ‘2b esnela) edi nds = 5.9 edt mepuINA = ¢y. 18AG BURR = G/M ZOTEH JOIEM = Hine 903 ‘Ad A/D "9 ALL x1 9hd TO ‘OLX rie az8 SevO. HO aya - 90S s9NkYS. = ONS HS Ved INES = NV XS UES Culleg = Wy4 ‘O 998 ‘Of A/D 70 awl” "OLX L + OAGAMNSAETX-ONA|'ND puts ovrez x 11328 Sev a als SNEWS meas a] yaocu) asim] sum | cow] uo] a8 | fo, | oz (eseud -€) 31NG3HIS NOLLASINLSIG GVOT (oe ye us) ‘ON gO €- XINaddV (1 uorpeg ‘474 e9neiD) Tuhnas = Boa wan = yA W8AG BAH G TABOH BION = Hi 008 Jones, = C'S Hg “Ueatsneua = ny “URS ‘903 ‘0nd "no 2 ‘ha no 2 “OLY + onaremsiserxrona'n9 00 ‘oh xz aais avo. 40. nee x zs s16¥9 zis ¥ Ni USWOONI 40 alAala ‘SEVIS Mm Linouio 33d VOT Buin 303 ‘Olid GON Nive BUNSOTONS HSLAW/ SQWS / 30 Wows G34 (1 uonseg ‘zt esneto) NOLWOO1 ’ (eseus 37NG3HOS NOLNEIHLsIG avo XIGNada¥ ‘ON ag ‘ONITTING / VTTIA -LOZroud APPENDIX - 5. ELECTRICAL SYMBOLS. DESCRIPTION Main Distribution Board (MOB) Sub Main Distribution Board (SMDB) Distribution Board (DB) Air Circuit Breaker (ACB) Moulded Case Circuit Breaker (MCCB) Miniature Circuit Breaker (MCB) Earth Leakage Circuit Breaker (ELCB) Fuse Link kWh Meter (Direct reading type) kWh Meter (CT operated type) ‘Switch Line (to connect up all outlets controlled by one switch) Circuit Line (to connect up alt outlets on the same circuit) Skirting Trunking Underttoor Trunking 13.A Switched socket outlet 15 A Switched socket outlet 20 4 double pole switch with neon indicator 30 4 double pole switch DESCRIPTION Shaver Socket outlet to BS 3052 Combined mirror light with integral Shaver Socket outlet to Bs 5052 48 A Cooker control unit Tungsten light fitting-ceiling mounted. {fiting “eference letter shall be shown in cirdle and detailed in legend, to Give load rating of igat iting and number of lamps). Tungsten light fitting-wall mounted. {fiting reference letter shall be shown incite detailed in logerd, to give Toad fating of ight fitng and numbor of lamps) Fluorescent tube light fiting-ceiing mounted. (iting reference letter shall be shown in circle and detailed in legend, to give longth of fitting end load rating plus the number of fluoreszent tubes). Fluorescent tube light fitting-wall mounted, (iting reference letter shall be shown in circle and detailed in legend, to sive length of fiting and load rating plus the number of fluorescent tubes) Lighting Switch - 1 WAY Lighting Switch - 2 WAY Lighting Switch - Intermediate way Lighting Switch - Pull cord operated Lighting Switch - Key operated Lighting switch - Weather proof type Clock outlet point Exhaust Fan Ceiling Mounted Fan Ceiling Fan Regulator Low level cooker outlet connection unit Earth Connection Time Switch Photo Electric Cell Bell Push. Bell (not associated with Fire Alarms) -40- APPENDIX - 6 (Clause 1.11 Section 1) CONTRACTOR'S INSPECTION CERTIFICATE 1/ We certify that the Electrical Installation at Project : Villa / Building / Consumer : ... Application No. : Account No. /S. Drawing Approval Reference : HCS / 19 Connected Load : kw Max. Demand : kW has been completed, inspected and tested in accordance with the DEWA / IEE Wiring Regulations (latest edition) and that the results are as indicated below ITEMS INSPECTED OR TESTED : 1. Type of L. V, distribution system 4 -Phase and / or 3-Phase 21 Overcurrent protection is provided by : -Main ecuits in MDB/s MCCB / Fuse / - Sub - circuits in SMDB /s MCCB / Fuse / MCB. -Final circuits in DB/s MCB /Fuse Earth leakage protection is provided by = 280} soa mA ELOB for 13 A sooket-outlet & Water heater |... circuits = 80/1007 mA ELCB for Lighting! cota circuits = 100/ 300 / mA ELCB / for NC Equipment / Pumps / Machines /... eva Earth leakage detection is provided by 2a/100 mA ELSIELR wih Audio/Visual alarm for Essent service equipment / Continuity of each earth continuity conductor is satisfactory. Insulation resistance of the fixed wiring installation with S00V meggar in mega-ohms, Continuity of fing circuit conductors is satisiactory. Polarity throughout the installation is correct and all single pole devices for protection and switching are in the phase conductor only. Power Factor (P. F.) Correction Capacitors / Panel /s installed. Min, Power factor of the wiring installation Earth fault loop impedance is satisfactory Nain earth electrode resistance in ohms Under Voltage relays with auto-reset timer for Air Conditioners! Units fitted Auto-reset timer sot at: ‘The operation of current operated earth leakage citoult breaker(s) is chacked and eifective Barriers and enclosures tor protection against electric shock in normal service are satisfactory. Yes/No All flexible cords, switches, fuses, plugs and socket outlets are in good serviceable condition excep! as noted below, (specify under para 17) There is no sign of overloading of conductors or accessories except as stated below, (specify under para 17 ). Apparatus tested [1 includes/ [1 — does not include portable appliances. We also confirm that the Main Disiribution Boacd/s (MDBs) as noted below ave fil to be energised (LV MDBs connected directly to the Transformer). 2 Yes/No MDB S/S 2 Yes/No ): Yes/No MDB . ): Yes/No In pursuance of this certification we undertake to carry out necessary tests in the wiring installations carried out by us, aiter the electric supply is released, and tectity any defects if found and/or when reported by the Owner/DEWA. Comments and deviations, if any, from the wiring Regulations Electrical wiring installations supervised and tested by : ‘ sco (Signature) Name : .. wrpperseenenenceson Position Company P.O. Box DEWA Wireman Competency Licence No. : Authorised Signature & APPENDIX -7 A-TYPICAL ARRANGEMENT OF METERING CABINET ON COMPOUND WALL 160 cm MAX. 80cm MIN. GR. LEVEL ROAD SIDE | RE \ ee i, i, MINIMUM DIMENSIONS: kWh Metering Rating of incomer breaker Dimensions in em ‘Type Reference in metering cabinet Al Bloc 7 AOA, 60A (1 - PHASE) 40_|60_[ 20 2 408, 60A, 100A 40_|60_[ 20 3 125A, 160A, 60_|_80 | 20 4 200A, 300A, 400A, 80_| 100 | 25 DESCRIPTION Compound wall. & 15/10 om PVC pipe sleeve tor Weather proof (IP 55) metering service cable Cabet. 8 18/10 em PVC sleeve for load Transparent viewing window. cable Hinged door with provision for wre 9: _—_Gonidult/s for ganhing conductors sealing & pad locking. (ECC). Cable (Gland) box. NOTE : All dimensions noted are in Position of ineomer breaker. centimetres and not io scale B-TYPICAL ARRANGEMENT OF kWh METERS IN ELECTRIC SERVICES ROOM FLOOR LEVEL DESCRIPTION = Main / Sub-main Distribution Board. PYC /GS trunking. Non-combustible type board / plate for fixing kWh meters. kWh Meter. Supply Cables. NOTES == a) Al'dimensions noted are in centimetres and not to scale. b) Layout indicates only the minimum space, maximum number of ows and arrangement, etc. of kWh motors. Earthing details, outgoing circuits & conduit terminations, ete. are not indicated. Refer to clause 3.2, 3.3 & 6.5 for regulations, C-TYPICAL ELECTRICAL SERVICES ROOM WITH 1 NO. MDB (MAX, 400 AMPS RATING) C—TYPICAL ELECTRICAL SERVICE ROOM WITH 1 NO. MDB MAX. 400 AMPS RATING? DESCRIPTION :- Main Distribution Board, PVG /GS trunking Non-combustible type board / plate for fixing kKWn meters, kWh Meters. Exhaust fan (for non-air conditioned room) Cable draw - pit. Non-maintained, minimum 3 Hrs. rated, self contained emergeney light. Light fitting Non-combustible door {Louvered type for non-air conditioned room). NOTES :- a) Alldimensions noted are in centimetres and not to scale. ‘Only minimum dimension permitted for electrical room is shown in the layout. Each electrical room shall be designed to accommodate the MDBs/ SMDBs, kWh meters, etc. Pror approval shall be obtained for construction. Refer to clause 3.2, 3.3 & 4.5 for regulations, D-TYPICAL ELECTRICAL SERVICES ROOM WITH 1 NO. CUBICLE TYPE L. V. SWITCHBOARD / PANEL DESCRIPTION :- LY Switehboard / Panel Exhaust fan (for non-ait conditioned room). Non-mainiained, minimum 3 Hrs. rated, self contained emergency light. Light fitting Non-combustible door (Louvered type for non-air conditioned room). NOTES :- a) b) All dimensions noted are in centimetres and not to scale Only the minimum clearance / space required on front, rear and sides of LV panel is ‘shown in the layout. Each elecirical room shall be designed with adequate dimensions to accomadate the MDBs / SMDBs, kWh Meters ete. Prior approval shall be obtained for construction. ‘The minimum clear space shown at the sides and rear of the panel is for switchboards with rear access requirements only. Refer to clause 3.2 & 4.6 for regulations. APPENDIX. & SELECTION OF CABLES Recommended size of cables for use in fixed wiring installation, for general purposes, and in normal situations, in the Emirate of Dubal. TABLE - 1 Single - Core PVC insulated, non-armoured, Stranded copper Conductors (BS 6004 & BS 6346) Size of cables, in ‘concealed’ conduits Max, rating of Max. Load 2x1 6,1 Phase 3/4 1C, 3 Phase ‘MCBIMCCB current/demand (mm?) (mm) (A) (A) 18 25 4 6 10 16 25 25 50 70 95 Common notes for Tables 1,2 &3 10 15 20 30 100 125 1 Assess initial demand with safe diversity and anticipated demand in future, if any, as applicable to Individual circuits, for selection of cable size, breakers rating, etc. 2 Assess individual fault levels and select MCBS/MCCBs accordingly. 3 Refer to manufacturers catalogues and select MCBs/MCCBs, cable sizes, etc. for specific applica- tions, considering inductive/capacttive loads, laying conditions, voltage drop, correction factors, etc. 4. Refer to Section 4, for Regulations, -47- TABLE-2 ‘Multi Core armoured PVC insulated, copper Conductors (BS 6346) Size of 1 No., 3/4 C PVC/SWA/PVC Max. rating of Max. Load Cable installed in normal situations MCB/MCCB current/demand (mam?) (a) (A) Refer to Table 1 for notes -48- TABLE -3 Multi Core armoured XLPE insulated, copper Conductors (@s 5467) -49- APPENDIX - 9 COLOUR IDENTIFICATION OF UNARMOURED, ARMOURED AND FLEXIBLE CABLE CORES AND BARE CONDUCTORS (Regulations 4.2.4 & 4.5.1) Non - flexible cables and bare conductors : Funetion Earth Continuity Conductor (ECC) Neutral Conductor in 1 and 3-phase circuits (N) Phase conductor in 1-phase circuits Phase conductor in 3-phase circuits R-phase Y- phase B-phase Flexible cables and Cores : Funetion Live Neutral Earth Colour Identification Green - and - Yellow Black Red or Red (R)/ Yellow (Y) / Blue (B) as applicable Colour of Core Brown Blue Green - and - Yellow -50- APPENDIX - 10 SPECIFICATIONS OF MDBs/SMDBs (Refer to clause 4.5.1) REFERENCE STANDARDS. RATING OF INCOMING SUPPLY BREAKER/ISOLATOR® (Or-loed) CONSTRUCTION Mounting Degree of protection of the enclosure for inetallation Painting Finish (Internal/Extemal) Front Cover ("Naaprone) kWh Meter reading provision Cable Tray Veniltation Seaingipad locking provision INTERNAL LAYOUT/ARRANGEMENT & FAULT RATING Segregation of live paits Incoming supply terminalstugs Busbar, tap-cff conneetione & terminals (° Separate and independent of each other) Neutral & Earth Bus-bars & Terminals Arrangement of bus-bar and tap-oft connections to outgoing circuit breakers Rating/size of phase & neutral bus-bars & terminals (at max.50 °C ambient) MDB/SMDB No. : BS EN 60439 BS 88, BS EN 60439-1, IEC 439-1 & 3 2008 soo] 4004 [ gona J 160A [J BREAKER 1 ISOLATOR Pedestal Well = [J Indoor P4142 Outdoor PS¥/55 1 ] Stove enamelled 1 Epoxy Polyester [Galvanized 1 Hinged [| JPanel lock Gasketted" tl Glass Window Gasketled Top Bottom Top & Bottom Louvres Compliance with Regutation 3.3.10 Barrier 1 Firmly secured [J * Separately mounted & Removeble by tool Shroud Barrior Firmly secured * Separately mounted & Removable by took Separately mounted with adequate working ‘clearances/spacing from incoming supply torminala/lugs Rigid, imly secured, supported, direct land as short as possible ‘Adequately sized Min, No, of bolted joints, Rated for max. 70 °C internal ambient, ‘consistent with the rated incoming supply breakerfisotator Tinned electrolytic Copper apa ating of Main Incomer and Busbars DEWA's Min. faut rating Min. & Max. rating of outgoing circuit breakers Min, fault rating Provision of min, working clearance/space for Incoming supply cable terminations 200A Incomes Gms 80016004 Incomer Cms Outgoing circuit cables Provision of supportsfacilty for dressingislamaing outgoing circuit cables Operational accessiconvenionee tor switchgear Incoming supply circuit breckerisolalor Outgoing circuit breaker Maintenance accessireplacement converience {or switchgear components Provision for termination of CU/KLPE/AWA(S.C,) IDENTIFICATION Rating of Incoming supply & Oulgoing Circuit breakers:- (vis-a-vis the rating specified - Refer to approved Single Line Diagram No. ) Type of circuit breakers Incoming Outgoing Colour codes tor internal, ‘main circuits wiring = Phase Neutral Earth Terminal ferrules for controvawniliary circuits Permanent labels, engraved, ‘trafolite’ or similar 25 a 35 75 tl Withiwithout cable box Adequate Chennols U1 Max, Height 2.0 M (From FFL) Trunking From Outside of Hinged Door! Bolted Cover Restricted ockable Breaker kWh Meter {] Ul Non-Ferrous glands plate ots Gland plate Thermat Discrimination Fault mece FS [1 FS [ Jo Mocs Red / Yellow/ Blue Black Green and Yellow kWh Metor Indicating Instruments Other Controle Indications, Board Designation Circuit Designation Warning Notce’s tl tn Conta -52+ 53 EARTHING Ratingisize of Earth bus-bar & terminals Eathing of conductive parts Termination af EOCs |. METERING Stendard indicating instruments KWH MetersiCTS. ‘Wising/Connections of CT Meter Protection of CT meter wing (“Allow 6 spare fuse cartridges in the MDB) Mounting height frorn FFL Mounting (if dooulcover mounted) CTs for Tarif Metering TESTSICERTIFICATION Typo Test Routine Tests & Checks Visual checks ScrewedsEalted Connections Operational checks Dielectac teat REMARKS Compliance with Regulation Soction - 5 ‘Adequate, consisten! with the min, fault rating spectiod under 1V.4 and V5 ‘Adequate No. 8 size to terminate Main & Circuits ECCs Enclosure Hinged Door Cable Glands Copper luge Compliance with Regulation Section - 3 Volt Meter with selector switch Power Factor Meter Ammoter Current Transformers Indicating Lamps Tested & Calibrated in DEWA ‘Load side of Incoming supply breaker Current Col Voltage coi ‘Sealed type fuse Hoat resistant! High voltage grade sri | Max. 2 Mrs, tl Min 0.8 Mt Hinged door mounted Exclusive Accuracy Class 0.2 s Matching Bato ‘Ac opocitiod by the Conoultante/Owner Certificate for reviewlreference Compliance with specifications Tightness Mechanical'Electrical 2500/2125V (85%) -53- APPENDIX - 11 SPECIFICATIONS OF DBs (Refer to clause 4.5.2) REFERENCE STANDARDS RATING OF INCOMING SUPPLY BREAKER/SOLATOR* [tOntoad) CONSTRUCTION Mounting, Degree of protection of the enclosure for nstalation Painiing/Finish (Internal/External) Front Cover (“Necprene) Gable Tray/Conduit onty Assombly INTERNAL LAYOUT/ARRANGEMENT & FAULT RATING Segragaton of live parts Incoming supply terminalsitugs Busbar, tap-off connections & torminele (Separate and independent of each other) Neutral & Farth Bus-bars & Terminals Arrangement of bus-bar and tap-off connactions te outyoing circuit breakersiNeutral bus-bars Rating/size of phase & nouttal bus-bars & terminals (at max. 50 °C ambient) DB No. : BS EN 60439, BS EN 60947, IEC-499-1 83 4293, 8S 1361 & BS 83 40a | 125A BREAKER ti oA] 4008, ISOLATOR, ‘wall L Surface | | Pecessed Pedestal Indoor-Pat/42 ‘Outdoor IP54!55 Stove enameled Epoxy Polyester Galvanized Hinged [ J Gaskotted* |. JPanel lock Top Bottom Top & Bottom Factory Assembled Barer ll Firmly scoured * Separately mounted & Removahla by tool Bariior Firmly secured * Soparatoly mounted & Removable by tool Separately mounted with adequate warking clearances/spacing from incoming supply terminale/lugs & Cutgeing terminals of MCBsIFS. Segregated for each :- Group of MCBS/TP ways ELCB Section Rigid, firmly secured, supported, direct and as short ao possible Adequately sized Min. No, of bolted joints Min. No, of looped Comectons Rated for max. 70 °C internal ambient Consistent with the rated incoming supply bioakerficolator Tinned electrolytic Copper Conta Min, fault rating ol circuit breakers Provision of supports‘taciliy for dressing clamping outgoing circuit cables (Operational access/converience for switchgear Incoming supply circutt breakeriisolator ‘Outgoing Circuit Breakers ‘Maintenance access/teplacement convenience: for switchgeer components Provision for termination of PVCISWA/PVCIXLPEISWA/PYC Cables ELCBs/ROCBs ULV. Fielays with auto-zeser timer IDENTIFICATION Rating of Incoming supply % Outgoing Circuit breakers: (vis-2-vis the rating speciied - Refer 10 approved Single Line Diagram/distribution Schedules) ‘Type of circuit breakers + Incoming Outgoing (CiL-Current Limit) Colour codes for internal, main circuits wiring =~ Phase Neutral Earth Terminal ferules for controlausiliary circuits Pemanent labels, engraved, ‘afoltie’ or similar aKA OE] Channels Trunking Max. Height 1.8 M4 (from FFL) From outside of Hinged Door! Boted Cover Restrictad/Lockable Breakers ELCBis Isolators UN, Pelays Gland plate Cable gang Window AIC Lighting Others. Split A/C ‘Small Power Window AIG Others Spit A/C Thermal Discrimination Fault Isolator [ ] meca, GILMCOBL ] FIs For general loads, Type ‘1'"L" For Motor load, Type 2''G's, Red / Yellow / Blue Black Groon and Yellow Indicating Instruments Other Board Desicnation Controls, Circuit Designation Indications Warning Notices, ELCBVU.V. Relay Section Cons 55- EARTHING Rating/size of Earth bus-bar & terminals Earthing of conductive parts Termination of ECCe METERING Standard indicating instruments Mounting height from FFL Mounting {if doortcover mounted) TESTS/CERTIFICATION Type Test Fooutine Tests & Checks Visual checks Sctewed'Bolted Connections Operational checks Dielectric test REMARKS Complience with Regulation Section - 5 . Adequate, consistent with the min faut rating specified under IV.4 ‘Adequate No, & size to terminate Main & Circuits ECCs Enclose Hinged Door Cable Glands Copper luge Compliance with Regulations Section - 3 As specified by tha Consultants! OWE sen Max, 2 Mtrs. Min, 0.8 Mtr. Hinged door mounted As specttied by the Gonsukants! Owner on Cottiticate for review/reference Compliance with specifications Tightness MechanicalElectical 2500/2125 (85%) “86 APPENDIX - 12 EARTH CONTINUITY CONDUCTORS (ECCs) & EQUIPOTENTIAL BONDING CONDUCTORS, (not less than 6) 16 <8 235 4 {need rot exceed 25) Note :- Refer to section.5 for Regulations. 2B7e APPENDIX «13 EARTH LEAKAGE PROTECTION Recommended value of operating current of ELCB/RCCB in Consumer installations : " Rated operating Current (na) 13 A switched socket outlets 30 Water heatersiCoolers 30 RefrigeratorVashing machine and similar apparatus 30 Domestic water pumps. 30 Jacuzzi pumps 10 Under water lighting 10, 1A switched scoket outlets (general purpose) 30 General lighting 37100 Flood lighting | 1004800 Window/Split type Air Conditioner 100 Fan coil/Air Handling-units/VAV 100 Package type AIC unit 100/300. Chiller 100-500-1000 Irrigation pump 100 Electric Cooker 100 Industrial machine 100/300 Elevators/Escalators 300/500, Neon sign 300 Notes :- 1 Grouping of circuits under one ELCB/RCCB is pormitted for lighting circuits, general purpose switched socket outlets, single phase equipment/appliance, ec. In such cases maximum number of Gircults proposed under each group shall be suitably selected considering the type of project such as Residertial, Commercial, Industrial, ete. and the possibie interruptions 2 Wherever un-interrupted power supply is required for equipmentcircuits of fire protection, drainage, etc. suitable earth leakage detection system with incieation nvr alarm is permitted 3 For industrial installations which are designed with co-ordinated operational system of plants and machines. the earth leakage protection shall be suitably selected considering the safety and operational requirements m Reter to clause 5.4 for Regulations. APPENDIX - 14 SPACING OF SUPPORTS FOR TRUNKING, CONDUITS AND CABLES. Recommended maximum spacing of Clips, Cleats, Saddles or supports (Refer to secton-6 for Regulations) a TRUNKING : Horizontal Vertical 2 CONDUITS : Horizontal Vertical 3. ARMOURED CABLES : Horizontal Vertical APPENDIX - 15 NUMBER OF CABLES THAT MAY BE INSTALLED IN TRUNKING, CONDUITS AND TRAYS (Refer to section-6 for Regulations) TRUNKING : Where single core insulated cables are installed in surface mounted metal or PVC trunking, the space factor shall normally not exceed 40 percent. Suitable correction factor shall be applied to the comesponding current carrying capactty, based on the number of circuits installed within the trunking. 4. CONDUIT: Size of Conduit in mm Nominal cross sectional area of Conductors, : aa 20 25 32 Maximum number of cables drawn The size of conduits selected shall allow drawing the cables freely within, without damaging the insulation. 3. CABLE TRAY: Where single core insulated & sheathed cables are installed in ventilated cable trays, the sum of he combined cross - sectional area of all cables installed in the tray shall not excaed 50% of the interior cross sectional area of the cable tray. Suitable correction factor shall be applied to the corresponding current carrying capacity based on number of circuits and method of installation (touching or spaced). Where multicore cables are installed in ventilated cable tays the sum of the diameters of all cables installed shall not exceed 60% of the cable tray width and the cables shall bo installed in a single layer. Suitable corrector factor shall be applied to the corresponding current carrying capacity based on the number of cables and the method of installation (touching or spaced). -60 APPENDIX - 16 DATA SCHEDULE FOR LV ELECTRICITY METERS AND CURRENT TRANSFORMERS (Referto section-3, for Regulations) A. Electricity Meters Description Typo of Meters Induction type Watthour Meter Reference voltages & frequency Refer to clause 1.2, Section 1 Accuracy Gi Direct Metering on LY system CT Metering on LV system Register Type of register Roller cyclameter (drum type register No. of digits (drums) 6 (minimum) Height of numerals 5 mm (minimum) | Rated Secondary Current Maximum primary voltage 600 Rated Frequeney 50Hz Rated primary Current 200A, 300A, 400A, (only one is applicable) 500A, 800A, 12008, or 24008 Rated burden BVA No. of Phases 1 Accuracy Class CT Application CT metering on LV system Medium of installation Size of Busbars (Primary) ated Primary Current Busbar Size a) 200A, 3004 20mmx 10mm b) 400A) 30mm x10 mm ©) 800A, 800A 50 mmx 10 mm, or 2Nos. x 30 mmx 10 mm, d) 120A, 16004 2.Nos. x 60 mm x 10 mm 2) 24008, 2Nos. x 80mm x 10 mm -61-

You might also like