You are on page 1of 3

SISTEMA DE LAGUNAJES

DATOS:

2160 m

dia

Q=
DBO=

4320 m

310 mg
l
T= 15c

dia

Q=

Z= 3 (Suelo Arenoso)
BL= 0.5m
Coronacin = 3m
T= 5 aos
mantenimiento
n= 90%
(DBO)

SST 405 mg
USANDO GLOYNA:

DBOU

310
453,37 mg
0.1(5)
l
1 10

V 0.035 453.37 1.085(3510)


V 175214.22m3

Am 87607.11m 2

H 2m

3 x 2 87607.11m 2

x 170.89m

ANCHO

LARGO

Af = 164.89m

Lf= 506.67

Am= 170.89

Lm= 512.67

Ae= 176.89

Le= 518.67

As= 179.89

Ls= 521.67

Ac= 185.89

Lc= 527.67

A) VOLUMEN REAL DE LA LAGUNA

Af 83544.816m 2 ( fondo)
Ae 91747.536m 2 (espejo)

VREAL

2
(83544.816 91747.536 83544.816 91747.536)
3

VREAL 175228.343m3
(Total con Lodos)
B) COV

COVmin

mg
m3
310
2160
l
d 3.821 g

m3 d
175228.345m3

C) COS

COS

D)

310

mg
m3
2160
l
d 72.983 kg
had
9.1747 ha

91747.536m 3

42.476d
3
2160 m
d
E) VOLUMEN DE LODOS

Vlodos

(T= 5 aos mantenimiento) n=90%

mg
m3 365d
0.9(405
2160
5aos )
l
d 1ao

1.05 kg
l

Vlodos (1520.486m3 ) 0.9 1368.437m3

F) COV (Mximo)

COVmax

mg
m3
310
2160
l
d

(175228.343m3 1368.437m3 )

g
COVmax 3.851 m3 d

DIMENSIONAMIENTO DE LA LAGUNA FACULTATIVA

2.5m

527.67
521.67
518.67
512.67
506.67

185.89

179.89

176.89

164.89 170.89

You might also like