Professional Documents
Culture Documents
ATV312 Uputstvo SR PDF
ATV312 Uputstvo SR PDF
ivar 31 2
Uputstvo za upotrebu
04 / 20 09
Frek
rekven
ven t ni
regulator z a
trofazne
asin h ro ne moto
oto re
BBV46396 04/2009
BBV46396 04/2009
Sadraj
VANE INFORMACIJE.............................................................................................. 4
PRE POETKA .......................................................................................................... 5
POSTUPAK INSTALACIJE REGULATORA (POGLEDAJTE I UPUTSTVO ZA
BRZI START) ............................................................................................................ 7
UGRADNJA ............................................................................................................... 8
OIENJE ............................................................................................................... 10
ENERGETSKI PRIKLJUCI.................................................................................... 13
UPRAVLJAKI PRIKLJUCI ................................................................................. 16
ELEKTROMAGNETNA KOMPATIBILNOST (EMC) ............................................... 19
KONTROLNA LISTA ................................................................................................ 21
FABRIKA PODEAVANJA ................................................................................... 22
PROGRAMIRANJE.................................................................................................. 24
PRELAZAK SA ATV31 NA ATV 312 ....................................................................... 40
OTKRIVANJE I OTKLANJANJE GREAKA .......................................................... 41
BBV46396 04/2009
Vane informacije
PANJA
Proitajte paljivo uputstvo i upoznajte se sa opremom pre montae, rukovanja ili odravanja. Na
dokumentaciji ili na opremi se mogu pojaviti sledei simboli. Oni upozoravaju na potencijalnu
opasnost ili potrebu da se obrati panja na radnje koje treba sprovesti.
Kao dodatak natpisu UPOZORNJE ili OPASNOST. Oznaava da postoji opasnost od
elektinog udara, to moe izazvati povrede ako se ne pridravate uputstva.
Ovo je simbol upozorenja. Koristi se kako bi vas upozorio na potencijalnu opasnost od povreda.
Potujte sve preporuke o bezbednosti koje stoje pored ovog simbola kako biste izbegli mogue
povrede ili smrt.
OPASNOST
OPASNOST, oznaava opasnu situaciju koja, ako se ne izbegne, moe izazvati smrt, ozbiljne povrede ili
oteenje opreme.
UPOZORENJE
UPOZORENJE, oznaava opasnu situaciju koja, ako se ne izbegne, moe izazvati povrede ili oteenje
opreme.
OPREZ
OPREZ, koristi se bez simbola upozorenja, oznaava opasnu situaciju koja, ako se ne izbegne, moe
izazvati oteenje opreme.
OBRATITE PANJU
Re regulator koja se koristi u ovom uputstvu odnosi se na upravljaki deo frekventnog
regulatora.
Elektrina oprema trebala bi biti montirana, servisirana i odravana samo od strane kvalifikovanog
osoblja. Schnider Electric ne preuzima odgovornost za posledice koje mogu nastati korienjem
opreme.
2009 Schneider Electric. Sva prava zadrana.
BBV46396 04/2009
Pre poetka
Proitajte s razumevanjem ova uputstva pre bilo kakvog rada na frekventnom
regulatoru.
OPASNOST
OPASNOST OD VISOKOG NAPONA, EKSPLOZIJE ILI ELEKTRINOG LUKA
Montirajte i zatvorite sve poklopce pre stavljanja pod napon ili ukljuivanja i iskljuivanja ureaja.
Nepotovanje ovog uputstva e izazvati smrt, teke povrede ili oteenjem opreme.
OPASNOST
NEELJENI RAD OPREME
Proitajte sa razumevanjem uputstvo pre montiranja ili putanja u rad ureaja Altivar 312
Promenu parametara moe vriti samo kvalifikovano osoblje.
Nepotovanje ovog uputstva e izazvati smrt, teke povrede ili oteenjem opreme.
UPOZORENJE
OTEENA OPREMA
Ne ugraujte i ne pokreite regulator koji je vidno oteen.
Nepotovanje ovog uputstva e izazvati smrt, teke povrede ili oteenje opreme.
BBV46396 04/2009
UPOZORENJE
GUBITAK KONTROLE
Projektant sistema upravljanja mora uzeti u obzir potencijalni kvar upravljakog dela i za odreene
vane upravljake funkcije dati reenje da se postigne sigurno stanje tokom i nakon greke.
Primeri vanih funkcija sistema upravljanja su interventno zaustavljanje i zaustavljanje zbog
preoptereenja.
Odvojeni ili redundantni upravljaki put mora biti omoguen za kritine kontrolne funkcije.
Upravljaki put ukljuuje i komunikacione veze. Uzeti u obzir mogue uticaje prilikom nepredvienih
kanjenja prenosa podataka ili neuspene uspostave veze.
Nepotovanje ovog uputstva e izazvati smrt, teke povrede ili oteenje opreme.
BBV46396 04/2009
3. Ugradite regulator
- Ugradite regulator prema uputstvima iz ovog dokumenta (str. 8)
- Ugradite dodatnu opremu (videti dokumentaciju za dodatnu
opremu).
Koraci od 2 do 4
moraju se izvriti
sa iskljuenim
naponom napajanja
6. Start
-
BBV46396 04/2009
Ugradnja
Ugradnja i temperaturni uslovi
Primer ATV312HU11M3
BBV46396 04/2009
Nain ugradnje
Mogua s u tri naina ugradnje
Nain ugradnje C: Slobodan prostor 50 mm sa svake strane. Zatitni pokloci trebali bi biti skinuti
za vreme rada na temperaturi okoline iznad 50C (s tepen zatite IP20).
Napomena: Za radnu frekvenciju preko 4 kHz i oteane uslove rada pogledajte uputstvo za montau.
BBV46396 04/2009
Oienje
Napajanje i zatita
Regulator mora biti povezan na uzemljenje da bi se zadovoljili propisi vezani za velike struje curenja
(preko 3,5 mA).
Ako nacionalni ili lokalni propisi nalau upotrebu diferencijalne zatite, za jednofazne regulatore
potrebno je koristiti diferencijalnu zatitu tipa A, a za trofazne regulatore diferencijalnu zatitu tipa B
prema standardu IEC 60755.
Izaberite odgovarajui ureaj sa sledeim funkcijama:
Ako se u instalaciji upotrebljava vie frekventnih regulatora, potrebno je svaki zatititi posebnim
ureajem za diferencijalnu zatitu.
Drite energetske kablove to dalje od niskonaponskih instalacija signalnih kola (detektori, PLC-ovi,
merni ureaji, telefoni, kamere, itd.)
Ako za povezivanje motora i frekventnog regulatora koristite kablove duine vee od 50 m dodajte
izlazne filtere (videti katalog).
Upravljanje
Energetske kablove postavite to dalje od upravljakih kablova. Za upravljaka kola i kolo za
referentnu brzinu preporuuje se oklopljeni upleteni kabal sa gustinom uvrtanja od 25 do 50 mm.
Oklop treba uzemljiti na svakom kraju.
Uzemljenje opreme
2
OPASNOST
OPASNOST OD VISOKOG NAPONA, EKSPLOZIJE ILI ELEKTRINOG LUKA
Ploa frekventnog regulatora mora biti pravilno uzemljena pre ukljuivanja napajanja.
Uzemljite ureaj na taku predvienu za povezivanje uzemljenja kao to je prikazano na slici.
Nepotovanje ovog uputstva e izazvati smrt ili teke povrede.
DA
NE
BBV46396 04/2009
10
UPOZORENJE
OPASNOST OD UNITENJA OPREME
Frekventni regulator e se otetiti ako se napajanje povee na prikljuke motora (U/T1, V/T2. W/T3).
Proverite prikljuke napajanja pre stavljanja regulatora pod napon.
Ako menjate stari ureaj, proverite da li sve veze ka Altivaru 312 odgovaraju uputstvima za
povezivanje iz ovog uputstva
Nepotovanje ovog uputstva izazvae smrt ili teke povrede.
UPOZORENJE
NEODGOVARAJUA PREKOSTRUJNA ZATITA
Prekostrujni zatitni ureaji moraju biti pravilno koordinisani.
Koristite osigurae navedene u nacionalnim preporukama.
Ne povezujte frekventni regulator na izvor ija struja kratkog spoja moe biti vea od struje kratkog spoja
navedene u uputstvu za montau.
Nepotovanje ovog uputstva izazvae smrt ili teke povrede.
ema povezivanja
ATV312M2
Monofazno napajanje
ATV312M3/N4/S6
Trofazno napajanje
Analogni izlaz
kao logiki izlaz
Potenciometar za
referentnu
Vrednost
Otpornik za
Koenje
(ako se koristi)
24 V rele
Ili
24V PLC input
Ili
LED
BBV46396 04/2009
11
OPASNOST
NEELJENI RAD OPREME
Spreite sluajno uzemljenje logikih ulaza konfigurisanih kao sink. Sluajno uzemljenje moe izazvati
neoekivan i neeljen nain rada regulatora.
Zatitite signalne provodnike od oteenja koja mogu izazvati sluajo uzemljenje.
Potujte EN 60204 preporuke za pravilno uzemljenje upravljakog kola.
.
Nepotovanje ovog uputstva e izazvati smrt ili teke povrede.
(1) Za lokaciju prekidaa na prikljunoj ploi pogledajte Pristup upravljakim prikljucima str. 16.
BBV46396 04/2009
12
Energetski prikljuci
Pristup energetskim prikljucima
OPASNOST
OPASNOST OD VISOKOG NAPONA, EKSPLOZIJE ILI ELEKTRINOG LUKA
Vratite prednji poklopac na prikljuke i zatvorite vrata pre ukljuivanja napajanja.
Nepotovanje ovih uputstava e izazvati smrt ili teke povrede
BBV46396 04/2009
13
Funkcija
Za Altivar 312
Uzemljenje
Sve klase
ATV 312 M2
R/L1 S/L2
Napajanje
ATV 312 M3
ATV 312 N4
ATV 312 S6
PO
DC kolo (+ pol)
Sve klase
PA/+
Sve klase
PB
Sve klase
PC/-
DC kolo (- pol)
Sve klase
Prikljuci motora
Sve klase
Mogui preseci
provodnika (1)
2
mm (AWG)
ATV312H
0M3, 0M2
2.5 (14)
Preporueni
preseci
provodnika (2)
2
mm (AWG)
Moment zatezanja
(3)
N.m (Ib.in)
2,5 (14)
0.8 (7.1)
2,5 (14)
0.8 (7.1)
3.5 (12)
1.2 (10.7)
6 (10)
2.5 (14)
1.2 (10.7)
1.2 (10.7)
U40N4, U22M2
Od 4 do 6 (12 do 10)
4 (12)
1.2 (10.7)
U55M3
Od 10 do 16 (8 do 6)
10 (8)
2.5 (22.3)
U75M3
Od 10 do 16 (8 do 6)
16 (6)
2.5 (22.3)
U75N4
Od 10 do 16 (8 do 6)
16 (8)
2.5 (22.3)
Od 6 do 10 (10 do 6)
6 (10)
2.5 (22.3)
Od 20 do 25 (4 do 3)
20 (4)
4.5 (10.1)
Od 16 do 25 (6 do 3)
16 (6)
4.5 (10.1)
Od 10 do 25 (od 8 do 3)
10 (8)
4.5 (10.1)
(1) Podebljane vrednosti odgovaraju minimalnoj vrednosti preseka koja obezbeuje bezbedan rad.
(2) 75C bakarni provodnik (minimalni presek pr ovodnika za deklarisano optereenje).
(3) Preporuene vrednosti.
BBV46396 04/2009
14
BBV46396 04/2009
15
Upravljaki prikljuci
Pristup upravljakim prikljucima
Prekida logikih
ulaza
Upravljaki
prikljuci
RJ45 konektor
OPASNOST
NEELJENI RAD OPREME
OPASNOST
OPASNOST OD VISOKOG NAPONA, EKSPLOZIJE ILI ELEKTRINOG LUKA
Ne dirajte prikljunu plou pre nego to:
iskljuite napajanje frekventnog regulatora
iskljuite bilo kakav napon na izlaznim ili ulaznim prikljucima
Nepotovanje ovog uputstva e izazvati smrt ili teke povrede.
BBV46396 04/2009
16
Drugi prikljuci
(1) Podebljane vrednosti odgovaraju minimalnoj vrednosti preseka koja obezbeuje bezbedan rad.
(2) Od preporuene do maksimalne vrednosti.
COM
Funkcija
C/O kontakti relea R1
(zajedniki kontakt: R1C)
N/O kontakti releja R2
Zajedniki prikljuak za
anolagne ulaze/izlaze
Al1
10 V
Al2
Napajanje referentnog
potenciometra
Analogni naponski ulaz
Al3
BBV46396 04/2009
Elektrine karakteristike
Minimalna preklopna mo: 10 mA na 5 V
Maksimalna preklopna mo sa rezistivnim optereenjem
(cos=1 i L/R=0 ms): 5 A na 250 VAC i 30 VDC
Maksimalna preklopna mo sa induktivnim optereenjem
(cos=0.4 i L/R=7 ms): 1.5 A na 250 VAC i 30VDC
Vreme odabiranja: 8 ms
ivotni vek:
- 100.000 operacija sa maksimalnim optereenjem
- 1.000.000 operacija sa minimalnim optereenjem
0V
Analogni ulaz 0 + 10 V (max. dozvoljeni napon 30 V)
Impedansa: 30 k
Rezolucija: 0.01 V. 10-bit konvertor
Otrina: 4.3, linearnost: 0,2% max vrednosti
Vreme odabiranja: 8 s
Sa oklopljenim kablom: max. 100 m
+10 V (+8% -0%), 10 mA max, zatita od kratkih spojeva i
prekostrujna zatita
Bipolarni analogni ulaz 0 10 (max. dozvoljen napon 30 V)
Polaritet napona na Al2 odreuje smer referentne
brzine, pa time i smer rada motora
Impedansa: 30 k
Rezolucija: 0.01 V, 10-bitni konvertor
Preciznost: 4.3, linearnost: 0,2% maksimalne
vrednosti
Vreme odabiranja: 8 s
Sa oklopljenim kablom: max. 100 m
Analogni izlazi od X do Y mA. X i Y se mogu programirati od
0-20 mA.
Impedansa: 250
Rezolucija 0.02 mA , 10-bit konvertor
Preciznost: 4.3, linearnost 0,2% maksimalne
vrednosti
Vreme odabiranja: 8 s
17
Prikljuak
Funkcija
Elektrine karakteristike
COM
Zajedniki prikljuak za
anolagne ulaze/izlaze
Analogni naponski izlaz AOV
ili
Analogni strujni izlaz AOC
ili
Logiki naponski izlaz AOC
AOV ili AOC moe biti
pridruen samo (jedan od
njih, ne oba istovremeno)
0V
AOV
AOC
24V
Ll1
Ll2
Ll3
Ll4
Ll5
CLI
Logiki ulazi
RJ45
Komunikacioni port
BBV46396 04/2009
18
Uzemljenje regulatora, motora i plata kabla mora biti izvedeno kao visokofekventno uzemljenje.
Upotrebljavajte oklopljeni kabl za motor iji je plat uzemljen sa obe strane 6 str.20, otpornik
koenja (ako postoji) 8 str. 20 i upravljake kablove. Kablovi se mogu voditi i kroz metalne kanale
uz uslov da su pravilno uzemljeni.
Osigurajte maksimalni razmak izmeu kabla napajanja i kabla motora.
BBV46396 04/2009
19
1.
2.
3.
4.
5.
Ako se koristi dodatni ulazni filter, treba ga montirati ispod regulatora i neoklopljenim kablom
povezati direktno na napajanje.
BBV46396 04/2009
20
Kontrolna lista
Proitajte paljivo bezbednosne informacije u uputstvu za ugradnju i podeavanje i u katalogu. Pre
ukljuivanja regulatora proverite sledee stavke koje se odnose na mehaniku i elektrinu instalaciju, i
zatim pokrenite frekventni regulator.
Za kompletnu dokumentaciju idite na www.schneider-electric.rs.
1. Mehanika instalacija
2. Elektrina instalacija
Prilikom prvog startovanja regulatora na displeju e se pojaviti [Standard mot. freq] (bFr).str
26. Proverite da li je frekvencija na regulatoru bFr (fabriki podeeno 50 Hz) u skladu sa
frekvencijom motora.
Prilikom prvog startovanja parametri [Ref. 1 channel] (Fr1) str.26 i [2/3 wire control] (tCC) str.
27 pojavljuju se nakon bFr. Ovi parametri trebaju da se podese ako elite lokalno da upravljate
regulatorom, videti Kako upravljati regulatorom lokalno na str. 39.
Pri sledeem startu bie prikazan rdY na displeju.
[Restore config.] (FCS) funkcija , str. 36, doputa vam resetovanje regulatora na
fabrika podeavanja.
BBV46396 04/2009
21
Fabrika podeavanja
Fabrika podeavanja regulatora
Altivar 312 je fabriki podeen za uobiajene pogonske uslove:
Displej : Regulator spreman (rdY) sa zaustavljenim motorom, i sa frekvencijom motora
Logiki ulazi LI5 i LI6, analogni ulaz AI3, analogni izlaz AOC i rele R2 nisu podeeni
Opis
Veliina
Stranica
50 Hz
23
24
SVC
32
[Acceleration] [Deceleration]
3.00 sekunde
27
[Low speed]
0 Hz
27
[High speed]
50 Hz
27
27
28
[Switching freq.]
4 kHz
29
[Reverse assign.]
35
[2 preset speeds]
28
[4 preset speeds]
28
[Ref. 1 channel]
24
[Summing ref. 2]
(1)
[R1 Assignment]
[Automatic restart]
[Type of stop]
(1)
(1)
(1)
(1)
BBV46396 04/2009
22
Napred
Nazad
2 brzine
4 brzine
ATV312M2
Monofazno napajanje
ATV312M3/N4/S6
Trofazno napajanje
Referentna
brzina
Dodatna
referenca
BBV46396 04/2009
23
Programiranje
Opis upravljakog panela
Funkcije displeja i tastera
Charge LED
,,,,,
ili meni aktivan.
prelazi na meni, u
suprotnom, prelazi na meni,
str. 28.
nije podeen na
zaustavljanje je
slobodno
ako ( meni) je
Toki za okretanje u
lokalnom modu je
potenciometar koji slui:
za upravljanje - kada se
toki okree u smeru
kazaljke na satu + ili
obrnuto od kazaljke na
satu i za izbor/
potvrivanje pritiskom na
toki.
podeen na ,
koenje je definisano
rampom koenja, ali ako
je indukovano koenje u
toku prelazi na slobodno
koenje.
frekvencija motora)
:
inicijalizacija sekvence
:
:
:
:
:
Regulator spreman
koenje jednosmernom strujom
Slobodno zaustavljanje
Brzo zaustavljanje
Samopodeavanje parametara u toku
BBV46396 04/2009
24
Struktura menija
Za detaljno uputstvo pogledajte uputstvo za programiranje.
Ukljuivanje
Izbor parametra
[SPEED REFERENCE]
(rEF-)
[SETTINGS] (SEt-)
[MOTOR CONTROL]
(drC-)
[INPUTS / OUTPUTS CFG]
(I-O-)
[COMMAND] (CtL-)
[APPLICATION FUNCT.]
(FUn-)
[FAULT MANAGEMENT]
(FLt-)
[COMMUNICATION]
(COM-)
[MONITORING] (SUP-)
Videti uputstvo za
programiranje
Crtica se pojavljuje iza koda menija kako biste ga razlikovali od koda parametra. Primer:
[SETTINGS] (SEt-) meni,
BBV46396 04/2009
parametar.
25
Fabriko
podeavanje
Naziv/opis
30, str. 32 ,
[Ref. 1 channel]
str. 29 , str.
str. 34.
[AI1] (AI1)
[Network AI] (AIV1) Toki za okretanje. U modu zakljuane tastature toki slui kao
potenciometar.
Ako je LAC=L2 ili L3 mogua su dodatna podeavanja: [+/speed] (UPd) + brzina / - brzina preko LI1
[+/- spd HMI] (UPdH) + brzina / - brzina preko tokia ili preko udaljenog
[Network] (nEt) Referentna brzina preko komunikacijskog protokola koji nije Modbus.
BBV46396 04/2009
26
Kod
Fabriko
podeavanje
Naziv/ opis
[2 wire] (2C)
[2 wire] (2C) 2-ino upravljanje: otvoreno ili zatvoreno stanje ulaza odreuje start
ili zaustavljanje:
Primer oienja:
Ll1 : naprijed
Llx: nazad
[3 wire] (3C) 3- ino upravljanje (impulsno upravljanje): impuls napred ili nazad je
dovoljan za pokretanje, a stop impuls je dovoljan za zaustavljanje. Videti u uputstvu
za programiranje.
Primer oienja:
Ll1 : stop
Ll2: naprijed
Llx: nazad
OPASNOST
NEELJENI RAD OPREME
Kada se manjaju podeavanja [2/3 wire control] (tCC), parametri [Raverse assign.]
(rrS), [2 wire type] (tCt), kao i sve funkcije koje utiu na logike ulaze vraaju se na
fabrika podeavanja.
Proverite da li su ove promjene kompatibilne sa emom povezivanja.
Nepotovanje ovog uputstva e izazvati smrt ili teke povrede.
Kako bi promenili dodeljenu vrednost ovog parametra drite pritisnut ENT taster 2
sekunde.
BBV46396 04/2009
27
Kod
Naziv/ opis
[HMI Frequency ref.]
Fabriko
podeavanje
0 do 500 Hz
0 do 100%
LSP do HSP Hz
BBV46396 04/2009
28
[SETTINGS] (SEt-)
Parametre je mogue menjati dok ureaj radi i dok je zaustavljen.
Vano: Preporuuje se da se izmene vre dok ureaj ne radi. Proverite izmene pre vraanja ureaja u
rad.
Kod
Naziv/opis
Opseg
podeavanja
[Acceleration]
[Deceleration]
Zavisi od
podeavanja
parametra Inr
Fabriko
podeavanje
3s
3s
0 do HSP
0 Hz
LSP do tFR
bFR
0 do 1,5In (1)
Zavisi od veliine
regulatora
Termika zatita motora mora se podesiti na nominalnu vrednost struje motora koja je
navedena na nazivnoj ploici motora.
Ako elite da iskljuite termiku zatitu pogledajte uputstvo za programiranje.
[IR compensation]
0 do 100%
20%
1 do 100%
20%
1 do 100%
20%
BBV46396 04/2009
29
Kod
Naziv/opis
Opseg
podeavanja
Fabriko
podeavanje
[Slip compensation]
0 do 150%
100%
0.1 do 30 s
0.5 s
1 do 1.2 In(1)
0.7 In (1)
0.1 do 30 s
1 do 1.2 In(1)
[Skip frequency]
0 do 500
0s
0.5 In (1)
0 Hz
[Skip frequency 2]
0 do 500
0 Hz
[2 preset speeds]
0.0 do 500.0 Hz
10 Hz
[4 preset speeds]
0.0 do 500.0 Hz
15 Hz
[8 preset speeds]
[Current Limitation]
0.0 do 500.0 Hz
20 Hz
1.5 In (1)
0.25 do 999.9 s
0.0.s
0 do 500 Hz
bFr
BBV46396 04/2009
30
Kod
Naziv/ opis
Opseg
podeavanja
0 do 118%
Fabriko
podeavanje
100%
0 do 1,5 In (1)
In
1 do 200
30
2.0 do 16 kHz
4 kHz
Frekvencija motora moe biti podeena tako da se smanji buka motora. Ako je frekvencija
podeena na vrednost veu od 4 kHz u sluaju prevelikog porasta temperature,
regulator e automatski smanjiti frekvenciju, a poveae je ponovno kada se
temperatura vrati u normalno stanje.
Ovi prametri se mogu podesiti i u meniju [MOTOR CONTROL] (drC-) str. 32.
BBV46396 04/2009
31
Kod
Naziv/ opis
Opseg
podeavanja
Fabriko
podeavanje
50 Hz
Videti str. 26
[Rated motor volt.]
Zavisno od
veliine
regulatora
Zavisno od
veliine regulatora
Nominalni napon motora oznaen je na nazivnoj ploici. Ako je linijski napon manji od
nominalnog , bi trebao biti podeen na vrednost linijskog napona na klemama
regulatora.
[Rated motor freq.]
10 do 500 Hz
50 Hz
0.25 do 1.5 In
(1)
Zavisno od
veliine regulatora
0 do 32760
RPM
Zavisno od veliine
regulatora
0.5 do 1
Zavisno od veliine
regulatora
[No] (nO)
BBV46396 04/2009
32
Kod
Fabriko
podeavanje
Naziv/ opis
[Auto Tuning]
[No] (nO)
OPASNOST
OPASNOST OD VISOKOG NAPONA, EKSPLOZIJE ILI ELEKTRINOG LUKA
Prilikom samopodeavanja motor radi sa nominalnom strujom
Prilikom samopodeavanja ne radite nita na motoru.
Nepotovanje ovog uputstva e izazvati smrt ili teke povrede
OPASNOST
NEELJENI RAD OPREME
,
i ili
.
do
LI6
[LI6] (LI6)
Panja:
Samopodeavanje se vri ako ni jedna naredba nije aktivna. Ako je funkcija slobodno
zaustavljanje ili brzo zaustavljanje dodeljena logikom ulazu, taj ulazni signal mora biti
podeen na 1 (aktivno na 0). Samopodeavanje moe trajati 1 do 2 sekunde. Nemojte ga
prekidati. Saekajte da se prikaz na displeju promeni na
ili .
Vano:
Prilikom samopodeavanja motor radi sa nominalnom strujom.
BBV46396 04/2009
33
Kod
Naziv/ opis
Opseg
podeavanja
-
Fabriko
podeavanje
[Not done] (tAb)
[Not done] (tAb) : Predefinisana vrednost otpora statora se koristi za upravljanje motorom.
[Pending] (PEnd) : Zadat je nalog za samopodeavanje, ali jo nije izvren.
[In Progress] (PrOG) : Samopodeavanje u toku
[Failled] (FAIL) : Greka pri samopodeavanju
[Done] (DonE) : Vrednost otpora statora izmerena pri samopodeavanju i koristi se za
upravljanje motorom.
[U/F mot 1 selected]
[SVC] (n)
[Cst. torque] (L) : Konstantan obrtni momenat za motore vezane u paralelu ili specijalne
motore
[Var. torque] (P) : Promenjivi obrtni momenat. Primenjuje se kod ventillatora i pumpi.
[SVC] (n): Vektorsko upravljanje bez senzora za optereenje sa konstantnim momentom
[Energy sav.] (nLd) : Reim utede energije za optereenje sa promenljivim
momentom sa slobom dinamikom (ponaa se slino kao P bez optereenja i kao n
sa opetereenjem).
[Noise reduction]
[Yes] (YES)
2.0 do 16
kHz
4 kHz
10 do 500 Hz
60 Hz
[Yes] (YES) : Povratna sprega brzine je raskinuta (kod upravljanja poloajem smanjuje
vreme odziva, ali referentna vrednost moe bitit premaena)
[No] (nO) : Povratna sprega brzine je aktivna (spreava da referentna vrednost bude
premaena)
10 do 500 Hz
60 Hz
Fabriko podeavanje je 60 Hz, ili 72 Hz ako je [Standard mot. freq] (bFr) podeena na 60
Hz.
(1) Parametru takoe moete pristupiti u [SETTINGS] (Set-) meniju.
BBV46396 04/2009
34
Kod
Fabriko
podeavanje
Naziv/ opis
[No] (nO)
[Factory set.]
(Std)
[Macro configuration]
OPASNOST
(1) ,
i se moe pristupiti iz nekolika menija
BBV46396 04/2009
35
Kod
Fabriko
podeavanje
Naziv/ opis
[No] (nO)
OPASNOST
NEELJENI RAD OPREME
Proverite da li je odabrana makro konfiguracija kompatibilna sa emom povezivanja koju
koristite.
Nepotovanje ovog uputstva e izazvati smrt ili teke povrede.
(1)
(2)
,
i moe se pristupiti iz nekoliko konfiguracijskih menija.
Sledei parametri nisu promenjeni ovim funkcijama; oni zadravaju svoju konfiguraciju:
(Standard motor frequency) str. 26.
(Control via remote terminal) u [COMMAND] (CtL-) meniju. Videti uputstvo za
programiranje.
(Terminal locking code) str. 39.
Parametri [COMMUNICATION] (COM-) menija. Videti uputstvo za programiranje.
Parametri [MONITORING] (SUP-) menija. Videti uputstvo za programiranje.
Kako bi promenili vrednost ovog parametra drite ENT taster pritisnut 2 sekunde.
36
Parametri se mogu menjati samo kada je regulator zaustavljen i nije aktivna naredba RUN.
Kod
Fabriko
podeavanje
Naziv/ opis
[2 wire] (2C)
[Transition] (trn)
OPASNOST
[Transition]
operacija, kako bi se izbeglo sluajno pokretanje nakon prekida napajanja.
[Fwd] (PFO): Stanje 0 ili 1 se koristi za pokretanje ili zaustavljanje, ali forward ulaz
ima prioritet u odnosu na reverse ulaz.
[Reverse assign.]
[LI2] (LI2)
Ako je
,
=
aktivna je inverzna operacija (npr. negativan napon na AI2)
BBV46396 04/2009
37
[MONITORING] (SUP-)
Parametre je mogue menjati dok ureaj radi ili dok ne radi.
Neke funkcije imaju mnogo parametara. Kako bi programiranje bilo jednostavnije i kako bi izbegli potrebu
prolaenja kroz listu parametara, ove funkcije grupisane su u podmenije.
Kao i meniji, podmeniji su oznaeni sa crticom iza svog koda: npr. LIF-.
Dok regulator radi prikazana je vrednosti monitoring parametra. Fabriki, prikazana vrednost je frekvencija
motora (rFr parametar). Prikazana vrednost data je kao indikacija. Ova vrednost nije toliko tana kao ona
merena instrumentom.
Kada izaberete novu vrednost koju elite da prikaete potrebno je taster ENT pritisnuti jo
jednom u trajanju od 2 sekunde. Od tada e se ovaj parametar prikazivati u toku rada
regulatora (ak i posle iskljuivanja regulatora sa napajanja).
Ako promena parametra nije potvrena pritiskom ENT tastera u trajanju od 2 sekunde, regulator e vratiti
prethodno podeeni parametar nakon iskljuivanja regulatora.
Napomena: nakon iskljuivanja ili gubitka linijskog napona, prikazuje se status regulatora (npr. rdY).
Kod
Naziv/opis
[HMI Frequency ref..]
Fabriko
podeavanje
0 do 500 Hz
0 do 100%
[Output frequency]
0 do 500 Hz
-500 do +500 Hz
Ovaj parametar se koristi i za funkciju +/- brzina koristei tastaturu ili udaljeni displej. Slui za
prikaz i potvrdu izabrane brzine. U sluaju gubitka napajanja nije sauvan i funkcija +/brzina mora biti ponovno potvrena u meniju [MONITORING] (SUP-)
[Motor speed]
[Motor current]
[Motor power]
[Mains voltage]
BBV46396 04/2009
38
Kod
Naziv/opis
Fabriko
podeavanje
0 do 65530 sati
BBV46396 04/2009
39
Dimenzije
Jedina razlikaje u dimenzijama je dubina. ATV312 regulatori su 2 mm dublji.
Zamena ATV31A
Prebacivanje sa HMI verzije Evropa ATV 312 na ATV31A .
Da biste lako zamenili ATV31A sa ATV312 , trebate izvriti sledee jednostavne operacije
prebacivanja ATV312 sa Evropa verzije na Asia verziju.
Prilikom prvog ukljuivanja 2 parametra se prikazuju posle bFr. Ovi parametri bi trebali biti podeeni na
sledei nain:
[Ref. 1 channel] (Fr1) na .
na .
Parameter
ATV31A
ATV312
Lokalno upravljanje
[Ref. 1 channel]
[Cmd channel] 1
Lokalno upravljanje
[Reverse assign.]
(ako
je = )
Toki
Vano: Za ATV31A prekida logikih ulaza podeen je na sink poloaj, ATV312 fabriki je
podeen na source. Videti str. 12.
BBV46396 04/2009
40
Ako se displej ne ukljuuje, proverite napajanje regulatora, oienje ulaznih signala AI1 i AI2 i
vezu RJ45.
Drugi sluajevi: pogledajte uputstvo za programiranje
Naziv
[NETW ORK FAULT]
Mogu uzrok
Greka u konmunikaciji na
komunikacionoj kartici
Otklanjanje
Proverite okruenje
(elektromagnetsku kompatibilnost)
Proverite oienja
Proverite time-out
Zamenite komunikacionu karticu
Proverite komunikacione kablove
[CANopen
FAULT]
[PRECHARGE
FAULT]
Zamenite regulator
[EEPROM FAULT]
Pogledati dokumentaciju
Zamenite regulator
[INTERNAL LINK
FAULT]
Greka u komunikaciji
izmeu regulatora i
komunikacione kartice
[INTERNAL FAULT]
Nepoznat opseg
[INTERNAL FAULT]
Zamenite regulator
Ponovo pokrenite regulator
Kontaktirajte predstavnika Schneider
Electric-a
Nedostaje displej
[INTERNAL FAULT]
Problem sa EEPROM-om
[INTERNAL FAULT]
Greka na industrijskom
EEPROM-u
BBV46396 04/2009
41
[OVERBREAK]
[OVERCURRENT]
[DRIVE OVERHEAT]
Naglo koenje
Mehanika blokada
Temperatura regulatora
previsoka
[MOTOR
OVERLOAD]
[MOTOR PHASE
LOSS]
[MAINS
OVERVOLTAGE]
[INPUT PHASE
LOSS]
Nesimetriano optereenje
Ova zatita funkcionie
samo kada je regulator
optereen.
[MOTOR SHORT
CIRCUIT]
BBV46396 04/2009
Poremeaj u napajanju
42
[MODBUSS FAULT]
[OVERSPEED]
Pogledajte dokumentaciju
odreenog proizvoda
Nestabilnost
[AUTO-TUNINIG
FAULT]
Naziv
Mogu uzrok
Otklanjanje
[INCORRECT
CONFIG] (CFF)
Trenutna konfiguracija je
neispravna
[INVALID CONFIG]
(CFI)
Neispravna konfiguracija
(konfiguracija uitana u
regulator preko serijske veze
ili mree je neispravna)
[UNDERVOLTAGE]
(USF)
Zamenite regulator
BBV46396 04/2009
43