Professional Documents
Culture Documents
SpiraxSarco B1 Introduction
SpiraxSarco B1 Introduction
Module 1.1
Module 1.1
Steam - The Energy Fluid
1.1.1
Block 1 Introduction
Module 1.1
1.1.2
Block 1 Introduction
Module 1.1
It can be generated at high pressures to give high steam temperatures. The higher the pressure,
the higher the temperature. More heat energy is contained within high temperature steam so its
potential to do work is greater.
o
Modern shell boilers are compact and efficient in their design, using multiple passes and
efficient burner technology to transfer a very high proportion of the energy contained in the
fuel to the water, with minimum emissions.
The boiler fuel may be chosen from a variety of options, including combustible waste, which
makes the steam boiler an environmentally sound option amongst the choices available for
providing heat. Centralised boiler plant can take advantage of low interruptible gas tariffs,
because any suitable standby fuel can be stored for use when the gas supply is interrupted.
Highly effective heat recovery systems can virtually eliminate blowdown costs, return valuable
condensate to the boiler house and add to the overall efficiency of the steam and condensate
loop.
The increasing popularity of Combined Heat and Power (CHP) systems demonstrates the high
regard for steam systems in todays environment and energy-conscious industries.
Fig. 1.1.3
1.1.3
Block 1 Introduction
Module 1.1
Fig. 1.1.4 Typical two port control valve with a pneumatic actuator and positioner
1.1.4
Block 1 Introduction
Module 1.1
Ways of increasing energy efficiency include monitoring and charging energy consumption to
relevant departments. This builds an awareness of costs and focuses management on meeting
targets. Variable overhead costs can also be minimised by ensuring planned, systematic
maintenance; this will maximise process efficiency, improve quality and cut downtime.
Most steam controls are able to interface with modern networked instrumentation and control
systems to allow centralised control, such as in the case of a SCADA system or a Building /Energy
Management System. If the user wishes, the components of the steam system can also operate
independently (standalone).
Boiler
With proper maintenance a steam plant will last for many years, and the condition of many
aspects of the system is easy to monitor on an automatic basis. When compared with other
systems, the planned management and monitoring of steam traps is easy to achieve with a trap
monitoring system, where any leaks or blockages are automatically pinpointed and immediately
brought to the attention of the engineer.
This can be contrasted with the costly equipment required for gas leak monitoring, or the timeconsuming manual monitoring associated with oil or water systems.
In addition to this, when a steam system requires
maintenance, the relevant part of the system is easy to
isolate and can drain rapidly, meaning that repairs may
be carried out quickly.
In numerous instances, it has been shown that it is far
less expensive to bring a long established steam plant
up to date with sophisticated control and monitoring
systems, than to replace it with an alternative method
of energy provision, such as a decentralised gas system.
The case studies refered to in Module 1.2 provide real
life examples.
1.1.5
Block 1 Introduction
Module 1.1
Steam is flexible
Not only is steam an excellent carrier of heat, it is also
sterile, and thus popular for process use in the food,
pharmaceutical and health industries. It is also widely
used in hospitals for sterilisation purposes.
The industries within which steam is used range from
huge oil and petrochemical plants to small local
laundries. Further uses include the production of
paper, textiles, brewing, food production, curing
rubber, and heating and humidification of buildings.
Many users find it convenient to use steam as the same
working fluid for both space heating and for process
applications. For example, in the brewing industry,
steam is used in a variety of ways during different stages
of the process, from direct injection to coil heating.
Steam is also intrinsically safe - it cannot cause sparks and presents no fire risk. Many petrochemical
plants utilise steam fire-extinguishing systems. It is therefore ideal for use in hazardous areas or
explosive atmospheres.
1.1.6
Block 1 Introduction
Inexpensive
Some water treatment costs
Inexpensive
Only occasional dosing
Expensive
Moderate coefficients
Relatively poor
coefficients
Temperature breakdown is
easy through a reducing valve
Temperature breakdown
more difficult
Temperature breakdown
more difficult
Condensate to be handled
No condensate handling
No condensate handling
No flash steam
No flash steam
No blowdown necessary
No blowdown necessary
Less corrosion
Negligible corrosion
Reasonable pipework
required
Searching medium,
welded or flanged joints usual
No fire risk
No fire risk
Fire risk
System inflexible
Module 1.1
1.1.7
Block 1 Introduction
Module 1.1
System benefits
Small bore pipework, compact size
and less weight
No pumps, no balancing
Two port valves - cheaper
Maintenance costs lower than
for dispersed plant
Capital cost is lower than for
dispersed plant
SCADA compatible products
Automation; fully automated boiler houses
fulfil requirements such as PM5 and
PM60 in the UK
Low noise
Reduced plant size
(as opposed to water)
Longevity of equipment
Boilers enjoy flexible fuel
choice and tariff
Systems are flexible and
easy to add to
Environmental factors
Uses
1.1.8
Sterilisation
Space heating
Range of industries
Block 1 Introduction
Module 1.1
Questions
1. How does the heat carrying capacity of steam compare with water ?
a| It is about the same
b| Its heat transfer coefficient is more than thermal oil and water
c| Controlling condensation
4. Approximately how much potential energy will steam hold compared to an equivalent
mass of water?
a| Approximately the same
b| Half as much
c| 5 to 6 times as much
d| Twice as much
b| By radiation
c| By conduction
d| By condensation
b| Steam pipes will be smaller than water or high temperature oil pipes
Answers
1: c, 2: d, 3: a, 4: c, 5: d, 6: c
The Steam and Condensate Loop
1.1.9
Block 1 Introduction
1.1.10
Module 1.1
Block 1 Introduction
Module 1.2
Steam and the Organisation
1.2.1
Block 1 Introduction
Chief executive
The highest level executive is concerned with the best energy transfer solution to meet the strategic
and financial objectives of the organisation.
If a company installs a steam system or chooses to upgrade an existing system, a significant capital
investment is required, and the relationship with the system, and the system provider, will be long
and involved.
Chief executives and senior management want answers to the following questions:
Q. What kind of capital investment does a steam system represent ?
A steam system requires only small bore pipes to satisfy a high heat requirement. It does not
require costly pumps or balancing, and only two port valves are required.
This means the system is simpler and less expensive than,
for example, a high temperature hot water system. The
high efficiency of steam plant means it is compact and
makes maximum use of space, something which is often
at a premium within plant.
Furthermore, upgrading an existing steam system with
the latest boilers and controls typically represents 50%
of the cost of removing it and replacing it with a
decentralised gas fired system.
Q. How will the operating and maintenance costs of
a steam system affect overhead costs ?
Fig. 1.2.1
Centralised boiler plant is highly efficient and can use low interruptible tariff fuel rates. The boiler
can even be fuelled by waste, or form part of a state-of-the-art Combined Heat and Power plant.
Steam equipment typically enjoys a long life - figures of thirty years or more of low maintenance
life are quite usual.
Modern steam plant, from the boiler house to the steam using plant and back again, can be fully
automated. This dramatically cuts the cost of manning the plant.
Sophisticated energy monitoring equipment will ensure that the plant remains energy efficient
and has a low manning requirement.
All these factors in combination mean that a steam system enjoys a low lifetime cost.
Q. If a steam system is installed, how can the most use be made of it ?
Steam has a range of uses. It can be used for space heating of large areas, for complex processes
and for sterilisation purposes.
Using a hospital as an example, steam is ideal because it can be generated centrally at high
pressure, distributed over long distances and then reduced in pressure at the point of use. This
means that a single high pressure boiler can suit the needs of all applications around the hospital,
for example, heating of wards, air humidification, cooking of food in large quantities and sterilisation
of equipment.
It is not as easy to cater for all these needs with a water system.
1.2.2
Block 1 Introduction
Management level
A manager will consider steam as something that will provide a solution to a management problem,
as something that will benefit and add value to the business. The managers responsibility is to
implement initiatives ordered by senior executives. A manager would ask How will steam
enable successful implementation of this task ?
Managers tend to be practical and focused on completing a task within a budget. They will
choose to use steam if they believe it will provide the greatest amount of practicality and expediency,
at a reasonable cost.
They are less concerned with the mechanics of the steam system itself. A useful perspective
would be that the manager is the person who wants the finished product, without necessarily
wanting to know how the machinery that produces it is put together.
Managers need answers to the following questions:
Q. Will steam be right for the process ?
Steam serves many applications and uses. It has a high heat content and gives up its heat at a
constant temperature. It does not create a temperature gradient along the heat transfer surface,
unlike water and thermal oils, which means that it may provide more consistent product quality.
As steam is a pure fluid, it can be injected directly into the product or made to surround the
product being heated. The energy given to the process is easy to control using two port valves,
due to the direct relationship between temperature and pressure.
Fig. 1.2.2
1.2.3
Block 1 Introduction
At the operating level, the day-to-day efficiency and working life of individuals can be directly
affected by the steam plant and the way in which it operates. These individuals want to know
that the plant is going to work, how well it will work, and the effect this will have on their time
and resources.
Technical personal /operators need answers to the following questions:
Q. Will it break down ?
A well designed and maintained steam plant should have no cause to break down. The mechanics
of the system are simple to understand and designed to minimise maintenance. It is not unusual
for items of steam plant to enjoy 30 or 40 years of trouble-free life.
Q. When maintenance is required, how easy is it ?
Modern steam plant is designed to facilitate rapid easy maintenance with minimum downtime.
The modern design of components is a benefit in this respect. For example, swivel connector
steam traps can be replaced by undoing two bolts and slotting a new trap unit into place. Modern
forged steam and condensate manifolds incorporate piston valves which can be maintained
in-line with a simple handheld tool.
Sophisticated monitoring systems target the components that really need maintenance, rather
than allowing preventative maintenance to be carried out unnecessarily on working items of
plant. Control valve internals can simply be lifted out and changed in-line, and actuators can be
reversed in the field. Mechanical pumps can be serviced, simply by removing a cover, which has
all the internals attached to it. Universal pipeline connectors allow steam traps to be replaced in
minutes.
1.2.4
Block 1 Introduction
An important point to note is that when maintenance of the system is required, a steam system is
easy to isolate and will drain rapidly, meaning that repairs can be quickly actioned. Any minor
leaks that do occur are non-toxic. This is not always the case with liquid systems, which are
slower and more costly to drain, and may include toxic or difficult to handle thermal fluids.
Q. Will it look after itself ?
A steam system requires maintenance just like any other important part of the plant, but thanks
to todays modern steam plant design, manning and maintenance requirements and the lifetime
costs of the system are low. For example, modern boiler houses are fully automated. Feedwater
treatment and heating burner control, boiler water level, blowdown and alarm systems are all
carried out by automatic systems. The boiler can be left unmanned and only requires testing in
accordance with local regulations.
Similarly, the steam plant can be managed centrally using automatic controls, flowmetering and
monitoring systems. These can be integrated with a SCADA system.
Manning requirements are thus minimised.
Medium users
Light users
Electronics
Pharmaceuticals
Cooking
Horticulture
Oil refining
Curing
Air conditioning
Chemicals
Chilling
Humidifying
Plastics
Fermenting
Treating
Sugar refining
Cleaning
Textiles
Melting
Metal processing
Baking
Drying
Shipbuilding
Power generation
1.2.5
Block 1 Introduction
Shrink-wrapping meat.
o
o
Repairing underground pipes (steam is used to expand and seal a foam which has been pumped
into the pipe. This forms a new lining for the pipe and seals any cracks).
Keeping chocolate soft, so it can be pumped and moulded.
Making drinks bottles look attractive but safe, for example tamper-proof, by heat shrinking a
film wrapper.
Making condoms.
Peeling potatoes by the tonne (high pressure steam is injected into a vessel full of potatoes.
Then it is quickly depressurised, drawing the skins off).
Moulding tyres.
Ironing clothes.
Making carpets.
Corrugating cardboard.
Drying paper.
Sterilising wheelchairs.
Cooking pieces of food, for example seafood, evenly in a basket using injected steam for
heat, moisture and turbulence at the same time.
Cooking large vats of food by direct injection or jacket heating.
1.2.6
Block 1 Introduction
Size of consumer
2001
Small
Medium
Large
55.49
46.04
33.85
Small
Medium
Large
142.73
136.15
119.54
Small
Medium
Large
230.48
224.61
204.30
Small
Medium
Large
4.89
3.61
2.76
Small
Medium
Large
1.10
0.98
0.78
All figures exclude the Climate Change Levy (which came into force in April 2001) although the
oil prices do include hydrocarbon oil duty.
The cost of raising steam is based on the cost of raising one tonne (1 000 kg) of steam using the
fuel types listed and average fuel cost figures.
Table 1.2.3 UK steam costs - 2001 (provisional)
Average unit
Fuel
cost ()
Heavy
(3 500 s)
0.074 0
Medium oil (950 s)
0.091 8
Oil
Light oil
(210 s)
0.100 0
Gas oil
(35 s)
0.105 4
Firm
0.006 3
Natural gas
Interruptible
0.005 0
Coal
35.160 0
Electricity
0.036 7
Unit of supply
Per litre
Per litre
Per litre
Per litre
Per kWh
Per kWh
Per Tonne
Per kWh
Cost of raising
1 000 kg of steam ()
9.12
11.31
12.32
12.99
6.99
5.55
3.72
25.26
1.2.7
Block 1 Introduction
Boiler efficiency
A modern steam boiler will generally operate at an efficiency of
between 80 and 85%. Some distribution losses will be incurred
in the pipework between the boiler and the process plant
equipment, but for a system insulated to current standards, this
loss should not exceed 5% of the total heat content of the steam.
Heat can be recovered from blowdown, flash steam can be used
for low pressure applications, and condensate is returned to the
boiler feedtank. If an economiser is fitted in the boiler flue, the
overall efficiency of a centralised steam plant will be around 87%.
This is lower than the 100% efficiency realised with an electric
heating system at the point of use, but the typical running costs
for the two systems should be compared. It is clear that the
cheapest option is the centralised boiler plant, which can use a
lower, interruptible gas tariff rather than the full tariff gas or
electricity, essential for a point of use heating system. The overall
efficiency of electricity generation at a power station is
approximately 30 to 35%, and this is reflected in the unit charges.
Fig. 1.2.3
Components within the steam plant are also highly efficient. For example, steam traps only allow
condensate to drain from the plant, retaining valuable steam for the process. Flash steam from
the condensate can be utilised for lower pressure processes with the assistance of a flash vessel.
The following pages introduce some real life examples of situations in which a steam user
had, initially, been poorly advised and/or had access to only poor quality or incomplete
information relating to steam plant. In both cases, they almost made decisions which would
have been costly and certainly not in the best interests of their organisation.
Some identification details have been altered.
Case study: UK West Country hospital considers replacing their steam system
In one real life situation in the mid 1990s, a hospital in the West of England considered replacing
their aged steam system with a high temperature hot water system, using additional gas fired
boilers to handle some loads. Although new steam systems are extremely modern and efficient
in their design, older, neglected systems are sometimes encountered and this user needed to
take a decision either to update or replace the system.
The financial allocation to the project was 2.57 million over three years, covering professional
fees plus VAT.
It was shown, in consultation with the hospital, that only 1.2 million spent over ten years
would provide renewal of the steam boilers, pipework and a large number of calorifiers. It was
also clear that renewal of the steam system would require a much reduced professional input.
In fact, moving to high temperature hot water (HTHW) would cost over 1.2 million more
than renewing the steam system.
The reasons the hospital initially gave for replacing the steam system were:
o
With a HTHW system, it was thought that maintenance and operating costs would be lower.
The existing steam plant, boilers and pipework needed replacing anyway.
Maintenance costs for the steam system were said to include insurance of calorifiers, steam trap
maintenance, reducing valves and water treatment plant, also replacement of condensate pipework.
Operating costs were said to include water treatment, make-up water, manning of the boiler
house, and heat losses from calorifiers, blowdown and traps.
The approximate annual operating costs the hospital was using for HTHW versus steam, are
given in the Table 1.2.4.
1.2.8
Block 1 Introduction
Steam ()
HTHW ()
245 000
0
57 000
77 000
8 000
400
9 000
10 000
406 400
180 000
37 500
0
40 000
0
100
12 000
5 000
274 600
Additional claims in favour of individual gas fired boilers were given as:
o
The costings set out above made the HTHW system look like the more favourable option in
terms of operating costs.
The new HTHW system would cost 1 953 000 plus 274 600 per annum in operating and
maintenance costs. This, in effect, meant decommissioning a plant and replacing it at a cost in
excess of 2 million, to save just over 130 000 a year.
The following factors needed to be taken into account:
o
The 130 000 saving using HTHW is derived from 406 400 - 274 600. The steam fuel cost
can be reduced to the same level as for HTHW by using condensate return and flash steam
recovery. This would reduce the total by 65 000 to 341 400.
The largest savings claimed were due to the elimination of manned boilers. However, modern
boiler houses are fully automated and there is no manning requirement.
The 37 000 reduction in maintenance costs looked very optimistic considering that the HTHW
solution included the introduction of 16 new gas fired boilers, 4 new steam generators and
9 new humidifiers. This would have brought a significant maintenance requirement.
The steam generators and humidifiers had unaccounted for fuel requirements and water
treatment costs. The fuel would have been supplied at a premium rate to satisfy the claim that
stand-by fuel was not needed. In contrast, centralised steam boilers can utilise low cost
alternatives at interruptible tariff.
The savings from lower mains heat losses (eliminated from mains-free gas fired boilers) were
minimal against the total costs involved, and actually offset by the need for fuel at premium
tariff.
The proposal to change appeared entirely motivated by weariness with the supposed low
efficiency calorifiers however on closer inspection it can be demonstrated that steam to
water calorifiers are 84% efficient, and the remaining 16% of heat contained in the condensate
can almost all be returned to the boiler house. Gas fired hot water boilers struggle to reach the
84% efficiency level even at full-load. Unused heat is just sent up the stack. Hot water calorifiers
are also much larger and more complicated, and the existing plant rooms were unlikely to
have much spare room.
A fact given in favour of replacing the steam system was the high cost of condensate pipe
replacement. This statement tells us that corrosion was taking place, of which the commonest
cause is dissolved gases, which can be removed physically or by chemical treatment. Removing
the system because of this is like replacing a car because the ashtrays are full !
A disadvantage given for steam systems was the need for insurance inspection of steam /water
1.2.9
Block 1 Introduction
A further disadvantage given was the need to maintain steam pressure reducing valves. But
water systems contain three port valves with a significant maintenance requirement.
The cost of make-up water and water treatment for steam systems was criticised. However,
when a steam system requires maintenance, the relevant part can be easily isolated and quickly
drained with few losses (this minimises downtime). In contrast, a water system requires whole
sections to be cooled and then drained off. It must then be refilled and purged of air after
maintenance. HTHW systems also require chemical treatment, just like steam systems.
Presented with these explanations, the hospital realised that much of the evidence they had been
basing their decision on was biased and incomplete. The hospital engineering team reassessed
the case, and decided to retain their steam plant and bring it up to date with modern controls and
equipment, saving a considerable amount of money.
Trace heating
Trace heating is a vital element in the reliable operation of pipelines and storage /process vessels,
across a broad range of industries.
A steam tracer is a small steam pipe which runs along the outer surface of a (usually) larger process
pipe. Heat conductive paste is often used between the tracer and the process pipe. The two pipes
are then insulated together. The heat provided from the tracer (by conduction) prevents the contents
of the larger process pipe from freezing (anti-frost protection for water lines) or maintains the
temperature of the process fluid so that it remains easy to pump.
Tracing is commonly found in the oil and petrochemical industries, but also in the food and
pharmaceutical sectors, for oils, fats and glucose. Many of these fluids can only be pumped at
temperatures well above ambient. In chemical processing, a range of products from acetic acid
through to asphalt, sulphur and zinc compounds may only be moved through pipes if maintained
at a suitable temperature.
For the extensive pipe runs found in much of process industry, steam tracing remains the most
popular choice. For very short runs or where no steam supply is available, electrical tracing is
often chosen, although hot water is also used for low temperature requirements. The relative
benefits of steam and electric tracing are summarised in Table 1.2.5.
Table 1.2.5 The relative merits of steam and electric trace heating
Steam
Electric
trace heating
trace heating
Robustness - ability to resist adverse weather and physical abuse
Good
Poor
Flexibility - ability to meet demands of different products
Excellent
Poor
Safety - suitability for use in hazardous areas
Excellent
Cannot be used in all zones
Energy costs per GJ
0 to 2.14
8.64
System life
Long
Limited
Reliability
High
High
Ease by which the system can be extended
Easy
Difficult
Temperature control - accuracy of maintaining temperature
Very good /high
Excellent
Suitability for large plant
Excellent
Moderate
Suitability for small plant
Moderate
Good
Ease of tracer installation
Moderate
Requires specialist skills
Cost of maintenance
Low
Moderate
Specialised maintenance staff requirement
No
Yes
Availability as turnkey project
Yes
Yes
1.2.10
Block 1 Introduction
In 1998, a steam trace heating system was installed at one of the UKs largest oil refineries.
Background
The oil company in question is involved in the export of a type of wax product. The wax has
many uses, such as insulation in electric cabling, as a resin in corrugated paper and as a coating
used to protect fresh fruit.
The wax has similar properties to candle wax. To enable it to be transported any distance in the
form of a liquid, it needs to be maintained at a certain temperature. The refinery therefore required
a pipeline with critical tracing.
The project required the installation of a 200 mm diameter product pipeline, which would run
from a tank farm to a marine terminal out at sea a pipeline of some 4 km in length.
The project began in April 1997, installation was completed in August 1998, and the first successful
export of wax took place a month later.
Although the refinery management team was originally committed to an electric trace solution,
they were persuaded to look at comparative design proposals and costings for both electric and
steam trace options.
The wax application
The key parameter for this critical tracing application was to provide tight temperature control of
the product at 80C, but to have the ability to raise the temperature to 90C for start-up or
re-flow conditions. Other critical factors included the fact that the product would solidify at
temperatures below 60C, and spoil if subjected to temperatures above 120C.
Steam was available on site at 9 bar g and 180C, which immediately presented problems of
excessive surface temperatures if conventional schedule 80 carbon steel trace pipework were to
be used. This had been proposed by the contractor as a traditional steam trace solution for the oil
company.
The total tracer tube length required was 11.5 km, meaning that the installation of carbon steel
pipework would be very labour intensive, expensive and impractical. With all the joints involved
it was not an attractive option.
However, todays steam tracing systems are highly advanced technologically. Spirax Sarco and
their partner on the project, a specialist tracing firm, were able to propose two parallel runs of
insulated copper tracer tube, which effectively put a layer of insulation between the product pipe
and the steam tracer. This enabled the use of steam supply at 9 bar g, without the potential for
hot spots which could exceed the critical 120C product limitation.
The installation benefit was that as the annealed ductile steam tracer tubing used was available in
continuous drum lengths, the proposed 50 m runs would have a limited number of joints, reducing
the potential for future leaks from connectors.
This provided a reliable, low maintenance solution.
After comprehensive energy audit calculations, and the production of schematic installation
drawings for costing purposes, together with some careful engineering, the proposal was to use
the existing 9 bar g distribution system with 15 mm carbon steel pipework to feed the tracing
system, together with strainers and temperature controls. Carbon steel condensate pipework was
used together with lightweight tracing traps which minimised the need for substantial fabricated
supports.
The typical tracer runs would be 50 m of twin isolated copper tracer tubing, installed at the 4 and
8 oclock positions around the product pipe, held to the product pipeline with stainless steel
strap banding at 300 mm intervals.
The material and installation costs for steam trace heating were about 30% less than the electric
1.2.11
Block 1 Introduction
tracing option. In addition, ongoing running costs for the steam system would be a fraction of
those for the electrical option.
Before the oil company management would commit themselves to a steam tracing system, they
not only required an extended product warranty and a plant performance guarantee, but also
insisted that a test rig should be built to prove the suitability of the self-acting controlled tracer for
such an arduous application.
Spirax Sarco were able to assure them of the suitability of the design by referral to an existing
installation elsewhere on their plant, where ten self-acting controllers were already installed and
successfully working on the trace heating of pump transfer lines.
The oil company was then convinced of the benefits of steam tracing the wax product line and
went on to install a steam tracing system.
Further in-depth surveys of the 4 km pipeline route were undertaken to enable full installation
drawings to be produced. The company was also provided with on-site training for personnel on
correct practices and installation procedures.
After installation the heat load design was confirmed and the product was maintained at the
Lagging
Wax
Steam
Fig. 1.2.4
required 80C.
The oil company executives were impressed with the success of the project and chose to install
steam tracing for another 300 m long wax product line in preference to electric tracing, even
though they were initially convinced that electric tracing was the only solution for critical
applications.
1.2.12
Block 1 Introduction
Questions
1. How does the cost of upgrading a steam system compare with installing a decentralised
gas fired system ?
a| It costs the same to upgrade the steam system.
b| Sterilisation.
c| Cooking.
b| Steam gives up its heat at a constant temperature without a gradient along the
heat transfer surface, ensuring consistent product quality.
d| High temperature oils can be directly injected into the product to be heated.
4. A hot water calorifier can occupy much of a plant room. How much floor space does a
modern steam to hot water packaged unit need if it is rated at 1200 kW ?
a| 0.7 m
b| 7.0 m
c| 1.2 m
d| 12 m
c| A steam tracer is a small steam pipe which runs along the outside of a process pipe.
d| A tracer is a small water filled pipe which runs along the outside of a process pipe.
Answers
1: c, 2: d, 3: b, 4: a, 5: d, 6: c
The Steam and Condensate Loop
1.2.13
Block 1 Introduction
1.2.14
Block 1 Introduction
Module 1.3
Module 1.3
The Steam and Condensate Loop
1.3.1
Block 1 Introduction
Module 1.3
The boiler is the heart of the steam system. The typical modern packaged boiler is powered by a
burner which sends heat into the boiler tubes.
The hot gases from the burner pass backwards and forwards up to 3 times through a series of
tubes to gain the maximum transfer of heat through the tube surfaces to the surrounding boiler
water. Once the water reaches saturation temperature (the temperature at which it will boil at that
pressure) bubbles of steam are produced, which rise to the water surface and burst. The steam is
released into the space above, ready to enter the steam system. The stop or crown valve isolates
the boiler and its steam pressure from the process or plant.
Steam at 150C
200C
400C
Fig. 1.3.1 Typical heat path through a smoke tube shell boiler
If steam is pressurised, it will occupy less space. Steam boilers are usually operated under pressure,
so that more steam can be produced by a smaller boiler and transferred to the point of use using
small bore pipework. When required, the steam pressure is reduced at the point of use.
As long as the amount of steam being produced in the boiler is as great as that leaving the boiler,
the boiler will remain pressurised. The burner will operate to maintain the correct pressure. This
also maintains the correct steam temperature, because the pressure and temperature of saturated
steam are directly related.
The boiler has a number of fittings and controls to ensure that it operates safely, economically,
efficiently and at a consistent pressure.
Feedwater
The quality of water which is supplied into the boiler is important. It must be at the correct
temperature, usually around 80C, to avoid thermal shock to the boiler, and to keep it operating
efficiently. It must also be of the correct quality to avoid damage to the boiler.
1.3.2
Block 1 Introduction
Module 1.3
Ordinary untreated potable water is not entirely suitable for boilers and can quickly cause them
to foam and scale up. The boiler would become less efficient and the steam would become dirty
and wet. The life of the boiler would also be reduced.
The water must therefore be treated with chemicals to reduce the impurities it contains.
Both feedwater treatment and heating take place in the feedtank, which is usually situated high
above the boiler. The feedpump will add water to the boiler when required. Heating the water in
the feedtank also reduces the amount of dissolved oxygen in it. This is important, as oxygenated
water is corrosive.
Blowdown
Chemical dosing of the boiler feedwater will lead to the presence of suspended solids in the
boiler. These will inevitably collect in the bottom of the boiler in the form of sludge, and are
removed by a process known as bottom blowdown. This can be done manually - the boiler
attendant will use a key to open a blowdown valve for a set period of time, usually twice a day.
Other impurities remain in the boiler water after treatment in the form of dissolved solids. Their
concentration will increase as the boiler produces steam and consequently the boiler needs to be
regularly purged of some of its contents to reduce the concentration. This is called control of total
dissolved solids (TDS control). This process can be carried out by an automatic system which uses
either a probe inside the boiler, or a small sensor chamber containing a sample of boiler water, to
measure the TDS level in the boiler. Once the TDS level reaches a set point, a controller signals
the blowdown valve to open for a set period of time. The lost water is replaced by feedwater with
a lower TDS concentration, consequently the overall boiler TDS is reduced.
Level control
If the water level inside the boiler were not carefully controlled, the consequences could be
catastrophic. If the water level drops too low and the boiler tubes are exposed, the boiler tubes
could overheat and fail, causing an explosion. If the water level becomes too high, water could
enter the steam system and upset the process.
For this reason, automatic level controls are used. To comply with legislation, level control systems
also incorporate alarm functions which will operate to shut down the boiler and alert attention if
there is a problem with the water level. A common method of level control is to use probes which
sense the level of water in the boiler. At a certain level, a controller will send a signal to the
feedpump which will operate to restore the water level, switching off when a predetermined level
is reached. The probe will incorporate levels at which the pump is switched on and off, and at
which low or high level alarms are activated. Alternative systems use floats.
1.3.3
Block 1 Introduction
Module 1.3
Controllers
Boiler shell
High alarm
Pump off
Pump on
Second low alarm
Protection
tubes
It is a legal requirement in most countries to have two independent low level alarm systems.
Steam quality
Block 1 Introduction
Module 1.3
Air to atmosphere
via an air vent
Steam out
Steam in
Condensate to drain
via a float trap
Fig. 1.3.5 Cut section of a separator
showing operation
Condensate does not transmit heat effectively. A film of condensate inside plant will reduce
the efficiency with which heat is transferred.
A device known as a steam trap is used to release condensate from the pipework whilst preventing
the steam from escaping from the system. It can do this in several ways:
o
o
o
A float trap uses the difference in density between steam and condensate to operate a valve. As
condensate enters the trap, a float is raised and the float lever mechanism opens the main valve
to allow condensate to drain. When the condensate flow reduces the float falls and closes the
main valve, thus preventing the escape of steam.
Thermodynamic traps contain a disc which opens to condensate and closes to steam.
In bimetallic thermostatic traps, a bimetallic element uses the difference in temperature between
steam and condensate to operate the main valve.
In balanced pressure thermostatic traps, a small liquid filled capsule which is sensitive to heat
operates the valve.
Once the steam has been employed in the process, the resulting condensate needs to be drained
from the plant and returned to the boiler house. This process will be considered later in this Module.
Pressure reduction
As mentioned before, steam is usually generated at high pressure, and the pressure may have to
be reduced at the point of use, either because of the pressure limitations of the plant, or the
temperature limitations of the process.
This is achieved using a pressure reducing valve.
The Steam and Condensate Loop
1.3.5
Block 1 Introduction
Module 1.3
o
o
Jacketed pan - Large steel or copper pans used in the food and other industries to boil
substances - anything from prawns to jam. These large pans are surrounded by a jacket filled
with steam, which acts to heat up the contents.
Autoclave - A steam-filled chamber used for sterilisation purposes, for example medical
equipment, or to carry out chemical reactions at high temperatures and pressures, for example
the curing of rubber.
Heater battery - For space heating, steam is supplied to the coils in a heater battery. The air to
be heated passes over the coils.
Process tank heating - A steam filled coil in a tank of liquid used to heat the contents to the
desired temperature.
Vulcaniser - A large receptacle filled with steam and used to cure rubber.
Corrugator - A series of steam heated rollers used in the corrugation process in the production
of cardboard.
Heat exchanger - For heating liquids for domestic /industrial use.
Any steam using plant will require some method to control the flow of steam. A constant flow of
steam at the same pressure and temperature is often not what is required a gradually increasing
flow will be needed at start-up to gently warm the plant, and once the process reaches the
desired temperature, the flow must be reduced.
Control valves are used to control the flow of steam. The actuator, see Figure 1.3.6, is the device
that applies the force to open or close the valve. A sensor monitors conditions in the process, and
transmits information to the controller. The controller compares the process condition with the
set value and sends a corrective signal to the actuator, which adjusts the valve setting.
Springs
Actuator
Diaphragm
Valve stem
Movement
Valve
Valve plug
1.3.6
Block 1 Introduction
Module 1.3
o
o
Steam
Heated medium
Plant
Condensate
Air
Steam
Condensate
Mechanical pump
Fig. 1.3.7 Condensate recovery and return
Energy monitoring
In todays energy conscious environment, it is common for customers to monitor the energy
consumption of their plant.
Steam flowmeters are used to monitor the consumption of steam, and used to allocate costs to
individual departments or items of plant.
1.3.7
Block 1 Introduction
Module 1.3
Questions
1. What is the purpose of the multi-flue passes in a boiler ?
a| To reduce the amount of flue gases exhausted
b| 20C
c| Steam temperature
c| A strainer
d| A reducing valve
Answers
1: d, 2: d, 3: a, 4: d, 5: a, 6: b
1.3.8