You are on page 1of 2

CSENEX

Current / Voltage / Frequency / Motor Protection


CSENEX Family

Application

Customer Benefits

Comprehensive protection solutions at power system levels.


n
Generation

1A/5A rated CT (site selectable)


n
110V/230V/400V rated PT (site selectable)
n

n
Distribution

50/60 Hz nominal frequency (site selectable)


n

l
Overcurrent

Wide range auxiliary supply (no option required while ordering)


n

l
Voltage & Feeder protection

Self CT shorting modular design


n

l
Feeder management

DI/DO matrix programmability


n

n
Industrial
l
Motor protection

Technical Data

Records

Auxiliary voltage Uaux

24-260V AC/DC

Event recorder

50 (non volatile with time stamp)

Rated phase current Ip

1A & 5A (site selectable)

Fault recorder

10 (non volatile with time stamp)

Current measuring range

30xIp

Rated phase voltage

110/230/400V (site selectable)

Voltage measuring range

1.5xUn

Rated neutral current In

1A & 5A (site selectable)

Thermal withstand

At Ip=1A

capability in current

Continuous=4xIp

circuit

for 10 Sec=30xIp
for 1 Sec=100xIp

Tests and Environment


(EMC Emission / Emmunity / IEC 60255 / 60068
Mechanical / EMI)
Operating temperature

700C

Rated frequency Fn

50/60 Hz

Degree of protection

IP54

Digital inputs

6 programmable

Weight

1.0 kg

Trip contacts

4 programmable

Dimension (WxHxD)

125.0x156.0x158.5 mm

C&S Electric Limited


44, Okhla Industrial Estate, Phase III, New Delhi - 110020 (India) Phone : +91 11 - 66602414, 30883745/54/64 Fax : +91 11 6660 2413
E-mail : marketing.cspc@cselectric.co.in Web : www.cselectric.co.in

CSENEX
Selection Chart

ANSI

CSENEX Series

U-4xx

I-2xx

U-3xx

(Voltage)

(Current)

(Frequency)

M-1xx
(Motor)

CT Inputs

VT Inputs

4
-

Opto Inputs (max)

Output Contacts (max)

Protection
3 Phase overcurrent

50/51P

Ground fault

50/51N

Negative sequence overcurrent

46

Thermal overload

49

Over/Under voltage

27/59

Residual over voltage

59N

Negative sequence overvoltage

47

Over/Under frequency

81O/U

Rate of change of frequency

87R

Circuit breaker failure

50BF

Autoreclose

79

Broken conductor

46BC

Inrush blocking

51H

Trip Circuit Supervision

74TC

Neutral displacement

59N

Locked rotor

50LR

Stall

50S

Under current

37P

Phase Loss

37

Communication
Front (USB)

RS-485 Modbus