Professional Documents
Culture Documents
Current Transformer: Performance Analysis
Current Transformer: Performance Analysis
TO
CURRENT TRANSFORMER
PERFORMANCE ANALYSIS
INTRODUCTION
DEFINITIONS
PERFORMANCE CALCULATIONS
RATIO SELECTION CONSIDERATIONS
VARIOUS TOPICS
TEST
INTRODUCTION
IEEE Standard Requirements for Instrument
Transformers C57.13
IEEE Guide for the Application of Current
Transformers Used for Protective Relaying
Purposes C37.110
INTRODUCTION
Bushing, internal to Breakers and
Transformers
Free standing, used with live tank breakers.
Slipover, mounted externally on
breaker/transformers bushings.
Window or Bar - single primary turn
Wound Primary
Optic
MAGNETO-OPTIC CT
Light polarization passing through an
optically active material in the presence of a
magnetic field .
Passive sensor at line voltage is connected
to substation equipment by fiber cable.
Low energy output used for microprocessor
relays
Eliminates heavy support for iron.
DEFINITIONS
EXCITATION CURVE
EXCITATION VOLTAGE
EXCITATION CURRENT
EXCITATION IMPEDANCE
DEFINITIONS
EQUIVALENT CIRCUIT/DIAGRAM
POLARITY
BURDEN
TERMINAL VOLTAGE
CLASSIFICATIONS T AND C
DEFINITIONS
KNEE POINT
RELAY ACCURACY CLASS
MULTI-TAPS ACCURACY
SATURATION ERROR - RATIO/ANGLE
EXCITATION CURVE
EQUIVALENT DIAGRAM
Ip
Rp
Xp
Rs
Is
g
c
Pri
Ie
Ze
Sec
h
next
Ie(amps)
0.004
0.007
0.011
--------------------0.25
----------5.0
10.0
Ze(ohms)
750
1071
1364
-------------3100
1600
----------100.0
52.0
CURRENT vs VOLTAGE
V (volts)
3.0
7.5
15
42
85
180
310
400
425
450
500
520
Ie(amps)
0.004
0.007
0.011
0.02
0.03
0.05
0.1
0.25
0.5
1.00
5.0
10.0
Ze(ohms)
750
1071
1364
2100
2833
3600
3100
1600
850
450
100.0
52.0
I1
Rsec
Zint
Ie+I2
N1 I1
N2
I2
Ie
RB
Ze
EXTERNAL
BURDEN
POLARITY
LB
DEFINITIONS
EXCITATION CURVE
EXCITATION VOLTAGE
EXCITATION CURRENT
EXCITATION IMPEDANCE
EQUIVALENT CIRCUIT/DIAGRAM
BURDEN - NEXT
BURDEN
The impedances of loads are called BURDEN
Individual devices or total connected load,
including sec impedance of instrument
transformer.
For devices burden expressed in VA at
specified current or voltage, the burden
impedance Zb is:
Zb = VA/IxI
or VxV/VA
EXTERNAL BURDEN
Burden:
0.27 VA @ 5A = .. Ohms
2.51 VA @ 15A = .. Ohms
BURDEN
=
VA / I
RB
LB
QUIZ
I2
RB
DEFINITIONS
CLASSIFICATIONS T AND C
CLASS C
CTs with very minimal leakage
flux in the core, such as the
through, bar, and bushing types.
Performance can be calculated.
KNEE POINT
DEFINITIONS
KNEE POINT IEEE IEC - effective
saturation point
Quiz- read a few knee point voltages and also
at 10 amps Ie.
Excitation Volts
45 LINE
ANSI/IEEE
KNEE POINT
DEFINITIONS
EQUIVALENT CIRCUIT/DIAGRAM
EXCITATION VOLTAGE, CURRENT,
IMPEDANCE
TERMINAL VOLTAGE
BURDEN
CLASSIFICATIONS T AND C
EXCITATION CURVE
KNEE POINT IEEE IEC
ACCURACY CLASS
CT ACCURACY CLASSIFICATION
The measure of a CT performance is its
ability to reproduce accurately the primary
current in secondary amperes both is wave
shape and in magnitude. There are two
parts:
Performance on symmetrical ac component.
Performance on offset dc component. Go over the
paper
ACCURACY CLASS C
STANDARD BURDEN
ACCURACY CLASS: C100, C200, C400, & C800 AT POWER
FACTOR OF 0.5.
STANDARD BURDEN B-1, B-2, B-4 AND B-8 THESE
CORRESPOND TO 1, 2, 4 AND 8.
EXAMPLE STANDARD BURDEN FOR C100 IS 1 , FOR C200
IS 2 , FOR C400 IS 4 AND FOR C800 IS 8 .
ACCURACY CLASS APPLIES TO FULL WINDING, AND ARE
REDUCED PROPORTIONALLY WITH LOWER TAPS.
EFFECTIVE ACCURACY =
TAP USED*C-CLASS/MAX RATIO
AN EXERCISE
2000/5 MR
C800
TAPS
KNEE POINT
EFFECTIVE ACCURACY
2000/5
..
...
1500/5
..
...
1100/5
..
...
500/5
..
...
300/5
..
...
AN EXERCISE
2000/5 MR
C800
TAPS
KNEE POINT
EFFECTIVE ACCURACY
2000/5
590
800
1500/5
390
600
1100/5
120
440
500/5
132
200
300/5
78
120
AN EXERCISE
2000/5 MR
C400
TAPS
KNEE POINT
EFFECTIVE ACCURACY
2000/5
..
...
1500/5
..
...
1100/5
..
...
500/5
..
...
300/5
..
...
AN EXERCISE
2000/5 MR
C400
TAPS
KNEE POINT
EFFECTIVE ACCURACY
2000/5
220
400
1500/5
170
300
1100/5
125
220
500/5
55
100
300/5
32
60
CT SELECTION
ACCURACY CLASS
ANSI/IEEE ACCURACY
CLASS C400
I1
Rsec
Zint
Isec = 100
Ie+Isec
Ie <10
N1 I1
N2
Ze
RB
EXTERNAL
BURDEN
LB
PERFORMANCE
CALCULATIONS
BUT
THE REST OF US
SHOW US THE DATA
PERFORMANCE CRITERIA
THE MEASURE OF A CT
PERFORMANCE IS ITS ABILITY TO
REPRODUCE ACCURATELY THE
PRIMARY CURRRENT IN SECONDARY
AMPERES - BOTH IN WAVE SHAPE
AND MAGNITUDE . CORRECT
RATIO AND ANGLE.
PERFORMANCE CALCULATION
STEPS:
CT Ratio selection
Relay Tap Selection
Determine Total Burden (Load)
CT Performance using ANSI/IEEE Standard
CT Performance using Excitation Curve
STEPS:
CT Ratio selection
- within short time and continuous current thermal limits
- max load just under 5A
Load Current= 90 A
CT ratio selection : 100/5
PERFORMANCE CALCULATION
STEP: Relay Tap Selection
O/C taps min pickup , higher than the max. load
167%, 150% of specified thermal loading.
Load Current= 90 A for 100/5 CT ratio = 4.5 A sec.
Select tap higher than max load say = 5.0
How much higher relay characteristics, experience and
judgment.
Fault current: min: 350/20 = 17.5
Multiple of PU = 17.5/5 = 3.5
Multiple of PU = 17.5/6 = 2.9
PERFORMANCE CALCULATION
STEP: Determine Total Burden (Load)
Relay: 2.64 VA @ 5 A
Lead: 0.4 Ohms
and
580 VA @ 100 A
Total to CT terminals:
(2.64/5*5 = 0.106) + 0.4 = 0.506 ohms @ 5A
(580/100*100 = 0.058) + 0.4 = 0.458 ohms @ 100 A
PERFORMANCE CALCULATION
STEPS:
CT Ratio selection
Relay Tap Selection
Determine Total Burden (Load)
CT Performance using ANSI/IEEE
Standard
CT Performance using Excitation
Curve
PERFORMANCE CALCULATION
STEP: CT Performance using ANSI/IEEE Standard
Ip
Rp
Xp
Rs
Is
g
c
Pri
Ie
d
Ze
Sec
h
PERFORMANCE CALCULATION
STEP: Performance ANSI/IEEE Standard
Vgh = 2500/20 * 0.458 = 57.25
600/5 MR C100 CT used at tap 100/5 -- effective
accuracy class
(100/600) x 100 = ?
CT is capable of developing 16.6 volts.
Severe Saturation. Cannot be used.
PERFORMANCE CALCULATION
STEP: Performance ANSI/IEEE Standard
For microprocessor based relay:
Burden will change from 0.458 to o.4
Vgh = 2500/20 * 0.4 = 50.0
600/5 MR C100 CT used at tap 100/5 -- effective
accuracy class
(100/600) x 100 = ?
CT is capable of developing 16.6 volts.
Severe Saturation. Cannot be used.
PERFORMANCE CALCULATION
STEP: Performance ANSI/IEEE Standard
Alternative: use 400/5 CT tap:
Max Load = 90 A
Relay Tap = 90/80 = 1.125 Use: 1.5 relay tap.
Min Fault Multiples of PU=(350/80=4.38, 4.38/1.5= 2.9)
Relay burden at this tap = 1.56 ohms
Total burden at CT terminals = 1.56 + 0.4 = 1.96
Vgh = 2500/80 * 1.96 = 61.25
600/5 MR C100 CT used at tap 400/5-- effective accuracy
class is = (400/600) x 100 = ?
CT is capable of developing 66.6 volts. Within CT
capability
PERFORMANCE CALCULATION
STEP: CT Performance using Excitation Curve
ANSI/IEEE ratings ballpark. Excitation curve method provides relatively exact
method. Examine the curve
PERFORMANCE CALCULATION
STEP: CT Performance using Excitation Curve
For max fault current
Burden = CT secondary resistance + lead resistance + relay burden
Burden = 0.211 + 0.4 + 1.56 = 2.171
Fault current 2500/80 = 31.25 A:
Vgh = 31.25 * 2.171 = 67.84 V
Ie = 0.16
Beyond the knee of curve, small amount 0.5% does not significantly
decreases the fault current to the relay.
TEST
I2
RB
Determine CT performance using Excitation Curve
method:
CT winding resistance = 0.3 ohms
Lead length = 750 ft # 10 wire
Relay burden = 0.05 ohms as constant
Fault current = 12500A/18000A
CT CLASS = C400/C800
2000/5 MR current transformer
CT RATIO = 800/5
AN EXAMPLE C400
CT RESISTANCE
0.3 OHMS
LEAD RESISTANCE
1.5 OHMS
IMPEDANCE OF VARIOUS DEVICES 0.05
OHMS
FAULT CURRENT 12500 AMPS
CT RATIO 800/5
ACCURACY CLASS
C400
FAULT CURRENT
MAGNITUDES
25 -33 KA
20 - 25 KA
12.5 -20 KA
20 - 25 KA
10 -12.5 KA
<10 KA
8
10
46
35
35
+150
REFER TO PAGE 6 OF PAPER
RED DELICIOUS
C400
ZONE1
Z = V/A
DISTANCE
~Z
RATIO CONSIDERATIONS
CURRENT SHOULD NOT EXCEED
CONNECTED WIRING AND RELAY
RATINGS AT MAXIMUM LOAD. NOTE
DELTA CONNECTD CTs PRODUCE
CURRENTS IN CABLES AND RELAYS
THAT ARE 1.732 TIMES THE
SECONDARY CURRENTS
RATIO CONSIDERATIONS
SELECT RATIO TO BE GREATER THAN
THE MAXIMUM DESIGN CURRENT
RATINGS OF THE ASSOCIATED
BREAKERS AND TRANSFORMERS.
RATIO CONSIDERATIONS
RATIOS SHOULD NOT BE SO HIGH AS
TO REDUCE RELAY SENSITIVITY,
TAKING INTO ACCOUNT AVAILABLE
RANGES.
RATIO CONSIDERATIONS
THE MAXIMUM SECONDARY
CURRENT SHOULD NOT EXCEED 20
TIMES RATED CURRENT. (100 A FOR
5A RATED SECONDARY)
RATIO CONSIDERATIONS
HIGHEST CT RATIO PERMISSIBLE
SHOULD BE USED TO MINIMIZE
WIRING BURDEN AND TO OBTAIN
THE HIGHEST CT CAPABILITY AND
PERFORMANCE.
RATIO CONSIDERATIONS
TESTING
Core Demagnetizing
The core should be demagnetized as the final
test before the equipment is put in service.
Using the Saturation test circuit, apply enough
voltage to the secondary of the CT to saturate
the core and produce a cecondary currrent of 35 amps. Slowly reduce the voltage to zero
before turning off the variac.
TESTING
Saturation
The saturation point is reached when there is a rise
in the test current but not the voltage.
TESTING
Flashing
This test checks the polarity of the CT
Ratio
Insulation test