CONSIDERATIONS IN THE SELECTION OF PRIMARY OVERCURRENT
PROTECTION FOR THREE-PHASE TRANSFORMERS
Copyright Material EEE
Paper No. PciC-94.08
ML. Bishop SR. Mendis
‘Senior Member, IEEE ‘Member, IEEE
Cooper Power Systems
Systems. ring Group
Franksville, Wisconsin
Abarat; Teansormer prvi he lta power tat dies
tort industrial proceso ‘continuous service &
ipietiot steatian may octer utroetre teen be
Tehoved from service fo preveat damage to the transformer
Sndlor connected equipment. Proper avercurrent protective
devious are essential for the reliable operation ofthe plant. This
fr dacosoes protective system phicsophies, and iastrates
{he telectionalteraatives through examplee’ Transformer inrush
Brn overond capably, the protective erie performance
far diferent faut types, winding connections, and tre impact o»
aperating concer wi be duce, "Thy capbaus wil be ot
anstormers applied within an Industrial facility that are rated
43500 KVA and below, where the overcurrent device ls wormally a
fase
‘Key_Words: Three-phase Transformer Protection,
Current Limiting Fuse Application
1, INTRODUCTION
A typical industrial facility normally serves a majority of
the process loads through three-phase transformers. The
protection devices used with the transformers have @ major
effect on the operation and reliability of the system. The
protection of these three-phase transformers involves the
careful balancing of many protection and operating concerns.
The transformer protection scheme used must allow the
normal range of currents due to energization and heavy
temporary loading periods, while protecting the transformer
from extended periods of heavy overloads, and the system
from a failed transformer. Limiting the It let-through levels
for internal faults and minimizing the risk of tank failures in
high available fault current areas on the system is very
desirable. For safety reasons, some utilities or industrials have
standardized on a current limiting (CL) fuse at every
‘transformer location,
£. THREE-PHASE TRANSFORMER OVERCURRENT PROTECTION,
‘OBIECTIVES
‘The selection of overcurrent protection equipment for
three-phase transformers serving industrial loads is performed
by power system engineers considering various objectives.
Some common objectives are:
JF. Witte
Member, IEEE
KL. Leix
‘Member, IEEE
Componeat and Bote Ea
ponent ve Equipment
Pewaukee, Wisconsin
1) Protecting the transformer from damage due to
Jong time overloads and secondary faults as defined
2) Removing a faulty transformer from the power
system, with minimal effects on the rest of the system
‘by maintaining and enhancing proper coordination
With upstream protective devices.
3) Bo 1g a disruptive failure of the transformer
due to high current faults inthe transformer.
4) Proper fuse selection to prevent fuse damage from
high energization inrush currents.
5) Selection of secondary overcurrent devices to
prevent transformer damage due to secondary faults
and excessive overloads.
In the case of a pad-mounted distribution transformer,
fuses are the principal devices used for primary overcurrent
protection. Different types of fuses are available from a
variety of manufacturers in designs suited for various
applications. The fuse type selected considers the degree to
which the fuse performance meets the overall protection
system objectives,
One of the objectives of overcurrent protection is to
protect the transformer from damage due to long time
overloads by removing the transformer from service after a
severe overload of a significant time duration. Secondary
faults producing winding currents that are many times full
Joad magnitude should also result in operation of the primary
fuse before thermal or mechanical damage occurs to the
‘transformer. The time limits for winding current as a multiple
of full load current are established in ANSVIEEE C57.109-
1993, IEEE Guide For Liquid-lmmersed Transformer
Through Fault-Current Duration.{4] As a general guideline,
the fuse Time Current Characteristic (TCC) curve should be
below and to the left of the transformer through-fault-current
protection curve, to minimize the loss of transformer life due
to the mechanical and thermal effects of sustained through
faults
‘The primary fuse is also expected to disconnect the
transformer from the system in the event of an internal fault in
the core/coil assembly of the transformer. Faults that may
1994 TEER
'94-CH3451-2/94/0000-0087 $03.00develop in the transformer primary windings might result in
arcing that causes high pressures due to the energy released by
the arc, This energy must be contained by the transformer
tank. Depending on the fault current available, an expulsion
fuse may be abie to clear an intemal fault. However, due to
the operation of current limiting fuses in less than one-half
ceycle for high fault currents, a current limiting fuse isthe only
protection scheme that can minimize the energy input to the
failed unit. Therefore, another objective in the selection of a
primary fuse is that high current fauls are cleared in the
shortest amount of time possible, minimizing the pressure that
‘must be contained by the transformer tank.
The capability of a distribution transformer to withstand.
an internal fault is @ function of many variables. An internal
fault that establishes an arc under oil breaks the oil down into
a variety of gases. ‘The generation of gases and the sudden
pressure build-up caused by the arc can exceed the ability of
the tank to contain the event. The pressure generated by the
arc in the transformer tank during a fault is @ function of the
energy delivered to the fault by the system. The energy
delivered during an intemal fault is a function of the fault
‘current, the arc resistance (or arc voltage), arc length, and the
fault time duration. The energy absorbed can be expressed as
4 value in kilowatt-seconds or kilojoules, In the case of a pad-
‘mounted distribution transformer, the tank is the mechanical
system that must withstand the increased internal pressure
‘Benerated by the fault. The task of the protection engineer isto
specify a protection scheme that will interrupt the source
circuit before the fault results in a tank feture,
ANSI C57.12.26-1987, Pad-Mounted, Comparimental-
Type, Self-Cooled, Three-Phase Distribution Transformers for
Use with Separable Insulated High-Voltage Connectors,
High-Voltage, 34 500 Grd ¥/ 19 920 Volts and Below; 2500
AVA and Smaller (4), specifies that "the tank shall be of
sufficient strength to withstand a pressure of 7 psig without
Permanent distortion and 12 psig without rupturing or
displacing other components of the transformer or affecting
ity." A second standard, ANSI C57.12.25-1990,
has similar ratings for smaller single phase units up to 167
KVA specifying 7 and 15 psig pressures respectively. No
arcing short circuit tests are specified in these standards a5
‘compared to the standards for pole-type transformer tanks.
‘The ultimate goal i the selection of a protection system
that prevents eventful failures of pad-mounted transformers.
Although let-through 1, 2 common unit of measure for a
‘current limiting fuse, is nota direct measure of energy into the
‘arc at the point of fault, let-through It is proportional to the
fault energy, and the’ proportionality constant is R, the
resistance of the arc. The arc resistance isa variable, typically
a function of the arc length and the current itself, and is not a
parameter effecting the fuse clearing time. One reference [1]
includes test data showing the variation in arc energy as a
function of 1%. The industry has relied on testing and
operating experience to develop 1% thresholds for the
application of current limiting fuses to minimize the risk of a
pad-mounted transformer tank failure. These levels have
‘proven to be representative,
‘Another reference [2] studied industry test data and
developed It limits based on the energy sbsorption
capabilities of the transformers. Energy limits were
established at 15 KWs asthe low risk category and 50 kWs as
the moderate risk category. Based on typical arc resistance
values from test data resulted in total clearing 1% values of
150,000 A%s at 15 kV for low risk and 500,000 A%s for
moderate risk.
‘This is consistent with another reference [3] that, citing
the results of tests, reported the I maximum value without
“excessive transformer movement, oil spill, seam rupture,
te." was 500,000 As for 15-KV_ class pad-mounted
transformers rated 75 KVA and below. Severe deformation of
the tank, evidenced by bulging might be a result of internal
faults demonstrating these let through 1% values.
‘Another series of tests performed on pad-mounted
transformer units resulted in a tabulation of It le-throvgh
limits for CL. fuses protecting three-phase transformers (5].
Pressure relief devices are required to relieve pressures
generated by low current faults. The tests resulted in UL.
classification of R-TEMP® fluid-filled units and specifies It
let-through values for three-phase units up to 10,000 kVA.
‘The smallest size, a 45 KVA unit, requires a CL fuse with a
maximum I let-through of $00,000 A%s. A250 kVA pad-
mounted distribution transformer requires a CL fuse with a
maximum clear Jt of 2,000,000 A%s according to this
reference [5].
These same studies have also looked at the withstand
capabilities of other voltage class transformers. They suggest
that, at best the limits stay about the same [2], or go down as,
the voltage increases [3]. This may be a result of higher
voltages driving longer, higher resistance arcs. This would
result in higher arc energy being released inside the tank, from
the same current and duration ata higher voltage.
Pressure relief devices play a role in controlling this
energy release. ‘They allow a controlled reduction in the total
pressure in the tank. This allows protective devices to clear
the fault, while the valve is venting, keeping the pressure
within acceptable limits. In addition, the valve can reduce the
total pressure in the tank before and during a primary fault.
However, in the event of a low impedance primary fault, che
pressure build-up can be so sudden, or so much pressure canbbe generated that the valve cannot vent the gases rapidly
‘enough to prevent the tank from failing. CL fuses control this
‘energy release, and when used with pressure relief devices
effectively reduce the risk of tank failure.
‘This brief overview provides some background and
supporting information conceming the significance of the 12
Jet-through values of current limiting fuses and the impact on
transformer protection. For the purposes of this paper, an 1%
‘value of 500,000 As will be used as the limiting vaiue for the
protection of three-phase pad-mounted transformer units
against eventful failure forthe smaller kVA ratings.
In all applications, the primary fuse of a pad-mounted
three-phase transformer should maintain proper coordination
with upstream protective devices, such as other fuses,
reclosers, or relayed circuit breakers. If the distribution
transformer fuse is not selected properly, or is expected to
interrupt fault currents beyond it's rated interrupting current,
then operation of an upstream device can result, which may
‘cause an outage to large number of plant loads.
IML INRUSH CURRENT CONSIDERATIONS,
‘A primary fuse for a pad-mounted transformer is subject
to energizing inrush transient currents, which should be
accounted for so that the fuse is not damaged during these
events, Typical inrush current magnitudes for three-phase
transformers are 12 times full load at the 0.1 second point and
25 times full load atthe 0.01 second point. The application of
three-phase transformers in the industrial environment, unlike
the utility environment, may not consider cold load pick-up
values in the selection of # protective device. Transformers
applied to serve an industrial process normally would not be
sized based on a certain amount of load diversity. Motor
ssariing currents may be 2 consideration in the industrial
application. ‘The protective device may need to pass current
‘magnitudes that are higher than normal fall load for many
‘eycles or seconds to start induction motors. General time-
‘current points for these situations need to be evaluated for
individual situations. The inrush points and motor starting
time-current point pairs form a TCC curve that should fall
below and to the left of the primary fuse minimum melting
TOC curve.
1V, WINDING CONNECTION CONSIDERATIONS
‘The transformer connection has an impact on the
performance of the protective device for the different types of
faults. As an example, consider a 20,000 ampere secondary
fault ona grounded-wye-grounded-wye, versus a delta-
grounded wye connected transformer as shown in Fig.1. With
‘a wye-wye connected unit the primary fault current magnitude
is 696 amperes regardless of fruit type. With a delta-
‘grounded-wye connected unit the primary fault current
‘magnitude is 401 (14-gnd), 696 (38), or 802 (4-4) amperes
depending on the type of secondary fault experienced. These
values are 0.57, 1.0, and 1.15 times the three phase fault
current magnitudes, respectively. The impact of the
connection involves’ the fact that a fuse or other primary
overcurrent protective device is sensing line current, not
‘winding current. The result is that a fuse will operate faster
for a line-to-line fault, and slower for a line-to-ground fault
for the same secondary fault current, if the transformer is
‘connected in delta-grounded-wye. This must be taken into
account to properly coordinate a primary and secondary
device, and should be considered in the protection of the
transformer against damage due to sustained through fault
snacone a ete vn even ras de
oes EVA 5 Taaee-000/277 WTS
Fig. 1, Fault Current Transformation Through Delt-Wye Versus Wye-Wye
Connected transformers
\V. TRANSFORMER OVERLOAD CAPABILITY
Overload capability of the transformer must also be
considered in the selection of the overcurrent devices.
Electric utility applications normally consider fusing
‘transformer so that an overload capability of 140% to 300% of
the nameplate KVA can be served. Industriel applications
normally specify protective devices to allow overloadcapability of 100% to 150% of nameplate KVA. The
allowable overload must be compared against the continuous
‘current capability ofthe fuse that is selected, considering any
erating due to high ambient temperatures.
VL. APPLICATION EXAMPLES
The following application examples review different
‘ways to provide overcurrent protection for three-phase pad-
mounted distribution transformers. Current limiting fuses are
specified due to their ability to minimize the energy input to 2
failed transformer and, thus, increase the probability that the
tank will safely contain the event. Following the examples is
1 discussion on the protection scheme tradeoffs for one
application over another.
The application examples discuss the selection of the
primary overcurrent devices for three-phase pad-mounted
transformers. Several transformer sizes that are typical
industrial applications will be examined to explore the variety
of options in the selection of overcurrent protection. In
general, the larger size units result in fewer options for the
protection engineer due to the availability of suitable
protective equipment ratings. ‘The transformer withstand
curves were developed using the category I or Il through-fault
duration curves in ANSI C57.109-1985, previously discussed,
The inrush points forthe transformer are shown in each of the
figures along with the selected fuse TCC curves.
Fig. 2, TCC Cures for» 1000 kVA Three-Phase Pad-Mounted Transformer
Boles y 8 Bay-O-Ne Spl Expulsion Fase wit mn neal Bakcp
‘The first application considers the protection of a 1000
KVA three-phase pad-mounted transformer that is connected
in delta on the primary side and grounded wye on the
secondary side. The primary winding is served by a
13.8Y/7.96 kV four-wire system. ‘The full load rated current
is 41.8 amperes. From ths value the inrush points are created
‘asshown in Fig. 2. Assuming a 5% nameplate impedance the
‘maximum primary fault current for a bolted three phase
secondary fault is approximately 837 amperes.
For this application an expulsion fuse was selected in
‘order to protect the transformer from secondary faults and
long time overload currents. A Bay-O-Net style current
sensing link was selected as shown in Fig. 2, A C14 link was
selected for this application, which has a rating of 60 amperes.
‘The expulsion link bas a maximum interrupting rating of 2500
amperes symmetrical, when mounted in the Bay-O-Net
holder. Fig. 2 shows two through-fault protection curves.
‘One is for three-phase secondary faults and one is for
secondary single-line-to-ground faults. As shown in Fig. 1 a
secondary ground fault results in lower primary currents as
‘compared to the same magnitude three-phase fault. shifted
‘curve for single-line-to-ground faults reflects the stress on the
transformer that is created by the fault as viewed from the
primary side.
In order to limit the energy delivered to a fault that might
oceur in the core/coil assembly a back-up under-oil current,
Timiting fuse has also been selected. For this application the
175 ampere type ELSP fise was selected. The 15.5 kV rated
175 ampere back-up CL fuse has a minimum interrupting
current of 1000 amperes. The maximum clear 1% is 368,000
As, which is below the 500,000 A?s value desired for even
‘the smallest pad-mounted transformers.
application the Bay-O-Net mounted expulsion
fuse provides load break/load make capability in an
economical field replaceable unit. The expulsion link does
not limit energy delivered to an internal transformer fault.
‘The back-up current limiting fuse provides that function. The
intersection of the expulsion fuse clearing curve and the CL.
fuse minimum melting curve is to the right of the maximum
transformer through fault current. This provides fault
differentiation and insures thatthe CL fuse will not operate for
any faults occurring downstream of the transformer. The CL
fuse also prevents the re-energization of a faulted unit with the
expulsion link.
Another altemative to this combination is an internal
‘expulsion link with the internal back-up current limiting fuse.
‘This application functions the same way as far as fault
clearing is concemed. It does not offer the field replaceability
of the expulsion link however. The TCCs for this application
‘would be similar to Fig. 2.
‘The second application is a 1500 kVA three-phase pad-
‘mounted transformer that is connected in delta on the primary
side and grounded-wye on the secondary side. In this
—o0—application the selection of a full-range current limiting fuse
will be explored. A full range current limiting fuse, according,
to the proposed ANSI definition is “a fuse capable of
interrupting all currents from the maximum rated interrupting
‘current down to the minimum continuous current that causes
‘melting of the fusible elements), when the fuse is applied at
the maximum cmbient temperature specified by the fuse
‘manifacturer.*
Full range curreat limiting fuses interrupt low current
fauits in different ways depending on the design of the fuse.
One type utilizes a gassing spider to build up sufficient
dielectric strength inside the fuse to clear the fault current.
‘The spider aids in clearing low current faults and is a support
mechanism to wind the high current silver element.
Depending on the fault current level, some gassing may be
released outside of the housing during operation of the fuse.
‘This design is suitable for clip mount applications, however, is
not recommended for drywell canister mounting. Another
design utilizes a separate low current element and a non-
gassing spider. The spider’s sole purpose is to provide a
support mechanism to the element. During a low current
operation, minimal gassing is expelled from the low current,
element into the sand. The gassing for all fault current levels
is minimal and is self-contained in the fuse housing. The
second example for a 1500 KVA transformer uses @ non-
gassing design,
‘A 1500 KVA three-phase pad-mounted transformer
served by a 13.8 KV system has a rated fll load curent of
628 amperes. The 100A (parallel SOA. fuses) full-ange type
ELX current limiting fuse selected allows a continuous
overload of 116%, due to the derating ofthe fuse continuous
current rating in this drywell canister application, The fuse
TCC curves are developed through testing in air at a 25°C
ambient temperature. Placing the fuse in a drywell canister
requires derating the fuse by 12% plus 0.2% per degree C
above 25°C. The TCC curves forthe application are shown
in Fig. 3. If the unit has a nameplate impedance of 5%, 20
times full load current will flow during a bolted three-phase
fat on the secondary terminals. This fault will result in 1255
amperes of primary curent through the use, resulting in fuse
clearing in approximately 0.8 seconds. High current faults are
interrupted in the current limiting mode, limiting the It let-
though to 327,000 A%s inthis aplication,
Fig. 3 displays two through-fault duration curves for the
particular transformer application. This is due to the nature of
fault current propagation through a delts-grounded-wye
connected transformer. ‘The through-fault duration curve is
plotted for three phase faults on the secondary of the
‘transformer as shown in the figure. A single-line-to-ground
fault on the secondary will only produce 57.7 % of the
‘transformer rated winding current through the fuse on the
Primary side of the transformer. This results in the fuse
‘operating more slowly for ground faults than for three phase
faults on the secondary of the transformer. From the primary
side, this effect can be viewed as a shift of the damage curve
to the'left as shown for single-line-to-ground faults. This
makes it more difficult to provide overload capability and
‘ground fault protection with fusing from the primary side of a
delta-grounded-wye transformer. This problem is well
documented in transformer protection literature.
a = I
on sss
Fig. 3. TCC Cures for & 1500 kVA Thres-Phase Pad Mounted Transformer
Froected by a Fullfunge Curent Lining Fuse Mounted fa Doel
The full range current limiting fuse type applied in this
application is available in ratings suitable for transformer
protection up to 1500 kVA at 15 kV, and up to 3000 kVA at
34.5 KV. Fuse selections can allow 140% up to 300% loading,
of the transformer. Derating factors should be applied to the
‘TCC curves due to operation in transformer oil that is greater
than 25°C,
A third application of a larger three-phase pad-mounted
transformer, 2500 kVA , served by a 13.8 kV system with a
full load rated current of 104.6 amperes, will be used in the
next example, The delta primary ‘and grounded-wye
secondary connection of the transformer will be assumed. A
nameplate impedance of 5% will produce primery fault
current of approximately 2092 amperes for a bolted three-
phase secondary fault timited only by the transformer
impedance. ‘The inrush points are not shown for this
application in Fig. 4, since the plot is made on a secondary
fault current basis. The primary fuse minimum melt curve is
shown in Fig. 4, and is shifted to the secondary side for the
three-phase, phaseo-phase, and single-line-to-ground fault
‘types.
aFig. 4. TOC Curves for 22500 KVA Three Phase Pad-Mounted Transformer
Proiecied by « Cip Mounted Full Range Curent Liming Fuse.
One selection available to the distribution engineer is a
full range air insulated current limiting fuse, capable of
interrupting low fault currents without the need for an
additional device. In this example, elip-style mounting in air
will be assumed. In the most common application, a separate
fuse compartment is mounted on the side of the transformer,
with the door interlocked with a disconnecting device. The
fuse compartment is connected to the primary bushings of the
transformer through insulated cables, resulting a deadfront
transformer primary terminal compartment.
For the 2500 kVA application a 15.5 KV, 160A (parallel
80A fuses) type NX fuse was selected. To determine the
overload capability the fuse continuous current rating must be
determined based on the expected ambient temperature in the
enclosure. 1f 75°C is assumed a 20% derating factor would be
applied, resulting in a continuous current capability of 128
amperes. This is 122% of transformer nameplate. Higher
ambient temperatures would result in less overload capability
for this application. The maximum let-through It for this
fuse application is 1,380,000 As,
Fig. 4 shows the TCC curves for the low voltage main
overcurrent protective device on the secondary side of the
‘transformer. In addition, the primary fuse minimum melt and
total clear curves are drawn far to the left of the low voltage
breaker. The primary fuse curves must be shifted to a
secondary current basis to perform the coordination with the
low voltage secondary breaker and the transformer through-
fault duration withstand curve. A different multiplier is used
to shift the fuse from the primary to the secondary depending,
‘upon the fault type. The shift factor is 0.866 times the
transformer line-to-line voltage ratio (13,200/480 = 27.5) for
Jine-to-line faults, the transformer line-to-Hne voltage ratio for
three-phase faults, and 1.732 times the transformer lineto-line
voltage ratio for line-to-ground faults, The total clearing
‘curve has been shifted and plotted for each fault type in Fig. 4.
Note that the total clearing curve is completely above the
‘through-fault duration withstand curve for line-t-ground
faults. The fuse does not adequately protect the delta-
‘grounded-wye transformer for line-to-ground secondary
faults. Selection of a lower ampere rated fuse to accomplish
this objective would result in the possibly of fuse blowing
for heavy overloads. The secondary device must be selected
to provide adequate overload and secondary fault protection.
Since the secondary device is sensing fault current and
‘winding current it can be selected to beuer accomplish these
objectives. The primary device is relied upon to provide &
backup function and clear faults upstream of the secondary
device.
IV, PROTECTION SCHEME TRADEOFFS,
Each application example offers tradeoffs for_the
distribution engineer to consider. All ofthe selections offer a
high maximum interrupting rating, ie., $0,000 amperes. Very
I any distribution system require fault clearing
capabilities above this level. However, if properly selected,
all applications can limit the let-through 1% levels and
therefore limit the probability of a three-phase pad-mounted
‘transformer tank failure due to an internal fault. Current
limiting fuses which fimit the let-through I% levels also serve
to limit the probability that upstream overcurrent devices will
‘operate due to an individual pad-mounted transformer filure,
The first application is an expulsion fuse in series with
an under oil back-up current limiting fuse. The under oil Bay-
(O-Net provides an economical, field replaceable expulsion
fuse that is available ina variety of sizes. Current sensing and
currenthhigh oil temperature fuse links are available,
Deadtront construction is maintained with a device that offers
load break/load make capability. The under-oil back-up
current limiting fuse provides fault differentiation since it is
coordinated to operate for internal, high current faults only.
The CL fuse is not field replaceable, but does not need to be
since it will only operate on intemal fauks which will require
‘transformer replacement.
‘The second and third applications involve the selection
of full range current limiting fuses. Two selections wore
examined offering different TCC curve shapes and mounting
styles, Full range current limiting fuses can be mounted in a
live front style with a clip mounted fuse, or in a dead front
style in a drywell canister. This application provides both
hhigh and low fault current clearing in one fuse unit. The high
‘current element provides fault current interruption through 50
KA. The entire fuse unit is replaced afer an interruption
-2-climinating the concern of expulsion fuse/current limiting fuse
coordination. The application does sacrifice the fault
differentiation that exists with the first application
V. CONCLUSIONS
‘There are many considerations in the selection of the
protective devices fora three-phase pad-mounted transformer.
In response to these convems, the industry has developed a
variety of protective devices. Current limiting fuses were
developed in response to high available fault current levels,
produced by power systems and the need to limit fault current
levels, specifically in pad-mounted transformers to prevent the
tank from rupturing, Expulsion links are available as under-
cil, weak link designs, or as Bay-O-Net mounted units. The
‘current limiting fuse designs are available for clip mounting or
ddrywell canister mounting.
A careful itemization of the protection objectives allows
the selection and rating of pad-mounted three-phase
distribution transformer fuses to meet the specified objectives.
Under-oil back-up current limiting fuses sized for specific
applications allow a minimum size fuse to be selected and thus
makes upstream overcurrent device coordination easier while
allowing for fault differentiation. The application of back-up
current limiting fuses to work with expulsion fuses offers the
protection engineer an avenue for a complete three-phase pad-
‘mounted transformer protection package.
REFERENCES
[1] WRHenning, A.D-Hemandez, W.W-Lien, “Fault Curent
Capability of Distribution Transformers With Under-Oil