GENEL HKMLER
HER YAPI YETERL KAI YOLLARI LE DONATILMALI
ISI, DUMAN VE PANKTEN KORUYACAK EKLDE
TASARLANMALI
YAPININ KULLANIM SINIFINA, KULLANICI YKNE,
YANGIN KORUNUM DZEYNE, YAPISINA VE
YKSEKLN UYGUN TP, AYNI KONUM VE KAPASTEDE
KAI YOLLARI
KAI YOLLARININ DZENLENMES VE BAKIM HALNDE
OLMASI. ENGELLERDEN ARINDIRILMASI
HER IKIIN AIKA GRNECEK EKLDE YAPILMASI
KAI YOLLARI
BR YAPININ HER HANG BR NOKTASINDAN
YER SEVYESNDEK CADDEYE KADAR OLAN
DEVAMLI VE ENGELLENMEM YOLUN
TAMAMINA DENR.
ODALAR, HER KATTAK KORDOLAR, KAT
IKILARI, MERDVENLER SON IKI KAI
YOLLARINA DAHLDR
ASANSRLER KAI YOLU OLARAK KABUL
EDLMEZLER.
RNEK 1
Toplam kapal alan 1000 m2 olan ekildeki gibi 3
katl, splinkler sistemi mevcut bir imalathanede
klar nasl hesaplanr? (a+c=53, b+c=55)
ZM
YNETMELK Ek-5/B YE BAKILACAK.
RNEK 2
AYNI SORUDA KULLANICI YKN
HESAPLAYALIM?
ZM
EK-5/A TABLOSUNDA PAKETLEME YER,
FABRKA RETM ALANLARI KISMINDA 10M2
DEN K SAYISI 1 OLARAK
GRLMEKTEDR. RNEK PROJEMZDE
RETM KISMI 1000M2 D. O HALDE,
1000M2 / 10M2/K = 100 K OLDUU
GRLR. YNETMELK GERE 50 K YKN
AAN YERLERDEN 2. ACL IKI GEREKR.
RNEK 3
KAI MERDVENLER
YANGIN VE DER ACL DURUMLARDA
KULLANILABLECEK ZELLKTE OLAN
KAI YOLLARINDAN BAIMSIZ
TASARLANAMAZ
DUVAR, TAVAN VE TABANINDA YANACI
MADDE KULLANILAMAZ
YANGINA EN AZ 120 DAYANIKLI DUVAR VE EN
AZ 90 DAKKA DUMAZ SIZDIRMAZ KAPI LE
DER BLMLERDEN AYRILIR
DARESEL MERDVEN
YANMAZ MALZEMEDEN YAPILMALI
EN AZ 100 CM GENLKTE OLMALI
HER HANG BR KATTA KULLANICI YK 25 KY
AMAMALI
9.50 M DEN YKSEK OLAMAZ
BASAMAK N KOVA MERKEZNDEN 50 CM
UZAKLIKTA BASI GENL 250 MM DEN AZ OLAMAZ
BASAMAK YKSEKL 175 MM DEN OK OLAMAZ
BA KURTARMA YKSEKL 2.50 DEN AZ OLAMAZ
KAI RAMPALARI
EM %10 DAN DAHA DK OLAMAZ
DZ KOLLU OLUR
DORULTU DEKLKLER SADECE SAHANLIKTA
YAPILIR
BALANGI VE BT YZEYLERNDE SAHANLIK
BULUNMALI
SAHLIK GENL RAMPA GENLNDEN AZ OLAMAZ
MERDVENLER LKN UYGUNLUKTA DUVAR,
KORKULUK VEYA KPETE YAPILMALIDIR
KAYMAZ YZEY KAPLAMA