You are on page 1of 1

We take care of it.

General information about the connection


technology
The regulator has three printed circuit boards or connection
levels.

Optical Serial Protocol Interfaces


For fibre optic serial connections up to a baud rate of 19200
(e.g. DNP, IEC 60870-5-101 or 103), ST or FSMA connectors
are directly mounted on the flange plate for access without
opening the REG-DA door.
Please refer to the list of characteristics for an overview of
the available options.

The auxiliary voltage, the VT & CT inputs, as well as the relay


outputs, binary inputs etc., are all connected on Level I.
The hardware for all SCADA connectivity is on Level II.
When working with an Ethernet connection (such as for IEC
61850, IEC 60870-5-104 or DNP 3.0 over Ethernet), the
corresponding plug connection is also accessible on Level II
(RJ45 and/or ST/LC fibreglass).
Additional binary inputs and outputs, and mA inputs and
outputs can also be installed on Level II.
There are two slots available, each of which can be equipped
with the following modules:
Module 1 :
6 binary inputs AC/ 48 V...250 V
Module 2 :

6 relay outputs

Module 3 :

2 mA inputs

Module 4 :

2 mA outputs

Module 5 :

PT100 input

Module 6 :

Standalone monitoring unit PAN-A2


occupies both slots

Fibre optical connection (ST-connector, V17, V19)

The connections for the REG-DA COM ports, the E-LANs,


additional analogue inputs and outputs, as well as for the
PT100 direct input (E91 + E94) or resistance input (E97 +
E98) cards, are located on Level III.

Fibre optical connection (FSMA-connector, V13, V15)

Fibre optical connection (1 x Ethernet-ST, XW93) at


Level II; REG-DA Com ports at Level III