Transformer Stability Test: Transformer Details % Impedance 30 mVA Base
Transformer Stability Test: Transformer Details % Impedance 30 mVA Base
Transformer
Details
Rated Power
Vector Group
Rated Voltage HV
Rated Current HV
CT Ratio HV
Rated Voltage LV
Rated Current LV
CT Ratio LV
30 Mva
Dyn1
115 Kv
150.61
Amp.
400/5
13.8 kV
1255.1
Amp.
2000/5
HV Voltage
At Tap-1
At Tap-9
126.5 Kv
115 kV
At Tap-21
97.75 kV
380 x 150.61
0.14 x 115000
3.554 Amps.
0.044 Amps.
380 x 1255.1
0.14 x 115000
=
29.62 Amps.
Expected Secondary Current of Low side CT
=
29.62 x 5
2000
=
0.0740 Amps.
Now, for checking of Transformer STABILITY, you have to create a fault on outside of the
Differential CTs.
R
Y
B
High Side
CTs
HV
Breaker
Transformer
Neutra
l
CT
LV Breaker
Low Side
CTs
After this, measure the current of High Side CTs and Low Side CTs in all the measurable points like
FTs, Ammeter, Diff. Relay, REF Relay etc.
Result,
1. Diff. Relay should not operate.
2. REF Relay should not operate.
Differential as well as REF Sensitivity Test
R
Y
B
High Side
CTs
HV
Breaker
Create a FAULT here.
Transformer
Neutra
l
CT
LV Breaker
Low Side
CTs
After this, measure the current of High Side CTs and Low Side CTs in all the measurable points like
FTs, Ammeter, Diff. Relay, REF Relay etc.
Result,
1. Diff. Relay should show Differential Current.
2. REF Relay should show Differential Current.
REF Stability
We already checked while doing Transformer Differential Stability, but I am displaying here
another way to do REF stability Phase by Phase.
R
Y
B
High Side
CTs
HV
Breaker
Transformer
Neutra
l
CT
LV Breaker
Create a FAULT here.
Low Side
CTs
Result,
1. REF Relay should not operate.