You are on page 1of 1

Branch Circuit No.

4
Load: 1HP Air-Conditioning Unit
No. of Outlets: 1
Full-load Current: 8A
Ampacity of Wire: 1.25 x 8A = 10A
Size of Wire: 2 - 2.0 mm2/ THHW Cu wire
Size of Conduit: 15 mm PVC
Size of OPD: 8A x 250% = 20A
Use: 25AT, 30AF, 2P,230V,CB
Branch Circuit No. 5
Load: 1HP Air-Conditioning Unit
No. of Outlets: 1
Full-load Current: 8A
Ampacity of Wire: 1.25 x 8A = 10A
Size of Wire: 2 - 2.0 mm2 THHW Cu wire
Size of Conduit: 15 mm PVC
Size of OPD: 8A x 250% = 20A
Use: 25AT, 30AF, 2P,230V,CB
Branch Circuit No. 6
Load: 1.5HP Air-Conditioning Unit
No. of Outlets: 1
Full-load Current: 10A
Ampacity of Wire: 1.25 x 10A = 12.5A
Size of Wire: 2 - 2.0 mm2 THHW Cu wire
Size of Conduit: 15 mm PVC
Size of OPD: 10A x 250% = 25A
Use: 30AT, 30AF, 2P,230V,CB