12.4. An isolated power station has the LFC system as shown in Figure 97 with the
following parameters
Turbine time constant rr
Govemor time constant 7,
Generator inertia constant H = § sec
Govemor speed regulation = R per unit
The load varies by 1.6 percent for a 1 percent change in frequency, ie, D = 1.6.
(a) Use the Routh-Hurwitz array (Appendix B.2.1) to find the range of R for control
system stability.
(0) Use MATL4B rlocus function to obtain the root-locus plot.
AP1(s)
APres(s) APs AP APn |
1 i ~
i
is ters THs+D
‘Governor Turbine Rojating mass
and Ic
AQ(s)
1
RE
FIGURE 97
‘LEC system block diagram of Problem 12.4.
Redrawing the block diagram of Figure 97 with the load change — AP; (s)
as the input and the frequency deviation AQ(s) as the output and substituting the
system parameters results in the block diagram shown in Figure 98. The open-loop
transfer function is
K
KGO)H() = Tes Twas oss +055)
MOY 1 Aw(s)
TessTB
FIGURE 98
LFC block diagram for Problem 12.4.K
283 + 12.28? + 17.25 + 1.6
1
where K = 7
(a) The characteristic equation is given by
K
1+KG(3)H(8)=14 Saya 3e 4170416 ~°
which results in the characteristic polynomial equation
283 + 12.28? +17.2s+16+K =0
The Routh-Hurwitz array for this polynomual is then (see Appendix B.2.1)
2 17.2
s? | 12.2 164+K
si 206.64—2K 0
. 12.2
sS]16+K 0
From the s! row, we see that for control system stability, A must be less than
103.32. Also from the s° row, K’ must be greater than —1.6. Thus, with positive
values of K’, for control system stability
K < 103.32
, for control system stability, the governor speed regulation must be
1
103.32
(b) Use the following commands to obtain the root-locus plot.
R> R > 0.009678
g
num=1;
den = [2 12.2 170.2 1.6];
figure(1), rlocus(num, den)