Professional Documents
Culture Documents
Chapter-8
Initiating Devices: Smoke Detectors
Smoke detector
Smoke-sensing fire detector
fire alarm system
smoke detector
Smoke detector
() (able to detect fire early)
()
(allows emergency personnel to respond)
()
(life safety)
() (highly reliable)
smoke detector ionization spot-type smoke detector photoelectric spottype smoke detector liner beam-type smoke detector air-sampling smoke detector duct-type
smoke detector
H.
than 0.4 H.
- (smoke) (stratification)
..
smoke detector
(ambient conditions exist)
() () (temperature below 32F (0C))
() () (temperature above 100F (38C))
() (relative humidity above 93 percent)
() 300 ft/min (300 ft/min or 1.5 m/sec)
.. Smoke detector
Smoke
detector
Altitude
>300 ft/min
>3000 ft
Humidity
Color of
(>91.44m/min)
(>914.4 m)
>93% RH
(<0C>37.8C)
Smoke
Ion
Photo
Beam
Air sampling
Protection
Temperature
X: Can affect detector response. O: Generally does not affect detector response.
.. Smoke Detector
Smoke detector ()
() Photoelectric
() Ionization
Smoke detector heat detector alarm activate
(very early in a fires development or incipient stage)
Photoelectric smoke detector (smoldering fire)
. Ionization Detectors
() Ionization detector ionization chamber ionizing radiation (source)
Ionizing radiation Americium-241
Ionization chamber Alpha particles(helium nuclei) ()
(+ve plate) (-ve plate) ()
(+ve plate)
(-ve plate)
()
(ionization
chamber) () current
smoke detector activate
8-3
-() Multi-criteria
detector
smoke detector.
- Device programming
duplicate terminals.
- Technician using a
- Compressed-air
detector
(radioactive
material)
radiation
particles)
chamber
8-6
- Fire operation
Ionisation
type
smoke
detector
()
(quick acting)
()
current
fire
alarm signal
ionization smoke detector
photoelectric smoke detector
System
smoke detector Ionization smoke detector
Photoelectric smoke detector
Photoelectric smoke detector smoldering fire sensitive
- Smoke detector
Smoke alarm
()
(provide early warning)
()
(diffusing the projected light beam by a specified percentage of obstruction)
beam detector alarm Beam blockage trouble signal
8-12
Building movement
Multi-level detection
Aesthetics
Cooking smoke
() Spray paint
()
() Sanding dust
()
() Solder smoke
oversensitive
(ionization )
() Photo Detectors
Photo smoke detector chamber smoke particle
(reflection) Photo smoke detector
smoldering fire (larger smoke particle)
(flaming fire)
(small particles) smoldering fire
sensitivity (large particles)
oversensitive
8-13
smoke detector
Ion Photo combined smoke detector (enclosure)
ion smoke detector photo smoke detector Combined
smoke detector smoldering fire (large
particles) flaming fire (small particles)
Combination smoke detector less sensitive
false alarm
(underside)
detection
chamber
(particle)
Air-sampling system
() Detector
()
Aspiration system
() Control system
()
Filter assembly
- Use of Sampling Tubes to Convey Smoke-Laden Air to the Central Detection Unit of an AirSampling Detector.
Detectors
Removed
8-15
- Duct detectors
.. Duct Detectors
() Duct detector photoelectric detector Duct
(outside the ductwork) Duct (sample the air
inside the duct) duct probe
()
Altitude >
Temperature
Detection
>91.44 m/min
9.4.4 m (>
Humidity >
<0C>37.8C
Color of
Protection
(>300 ft/min)
3000 ft)
93% RH
(<32F>100F)
Smoke
Ion
Photo
Beam
Air sampling
8-16
in. (100 mm) joist would place the detector in the center of the ceiling jet, an ideal location for
undelayed response.)
detector
() (space is not accessible
for storage purposes)
() (steam pipes) (electric wiring) (conveyors) equipment
() (floor over the space is tight)
()
. Detector (Coverage)
Detector detect (range) Smoke
detector
(construction
characteristics)
()
Corridors
() Pitched ceilings
()
Flat ceilings
() Shafts/Flues
()
Honeycomb ceilings
() Stairways
8-19
Spacing and Siting of Detectors for Honeycomb Ceilings(Horizontal ceiling comprising a series of
small cells)
. Detector
Conventional addressable analog addressable fire alarm system
detector
(full
coverage) detector
(environment)
(potential
fire
hazards)
detector
- Joists: 3 ft (0.9 m) or less on center, more than 4 in. (100 mm) deep Beams: More than 3 ft
(0.9 m) on center, more than 4 in. (100 mm) deep Effect of Joists and Beams on the Ceiling Jet.
(combustible
materials)
detector
(combustible materials) detector
(areas with materials that overheat, smolder, or
ignite) (electrical equipment) (paper) (wood)
(visible smoke is the first indicator a fire has started) optical
(photoelectric) smoke detector (best protected)
flame detector
Plant Area
Type of Detector
outlying areas.
Switchgear rooms in main
Plant and outlying areas,
2
Cable gallery
8-21
. Smoke Detector
Smoke detector (power sources)
() (can be batteries or household power)
() smoke detector
(battery operated are easy to install and are economical to purchase)
() (independent of house
power so they will operate during power failures)
()British Standard fire code smoke detector
(British Standard fire code will permit battery operated units (existing buildings))
() hard wired smoke detector
(British Standard building code requires hard wired smoke alarms for new construction)
() (should install both on every level of home
plus in the sleeping rooms.)
() smoke alarm (British Standard
fire code (British Standard fire code requires hard wired smoke alarms for
new construction)
() (lack of maintenance (ie. not replacing batteries) is greatest
concern)
operation
(the zones of individual detectors should overlap and no blind zone should
be left. )
()
(Areas above false ceiling and below false flooring shall be considered as
8-22
separate zones.)
() detector
(Under ideal conditions of smooth ceiling and average room
size, one detector is recommended to protect the area.)
() (largest combustible gas concentration)
ionisation detector
()(air conditioned areas) ionization optical type
smoke detectors
()Detector (highest point of the ceiling)
(manufacture) minimum coverage
()Complete coverage
detector (location)
() smoke detector () () () (35
to 40 sq.m per detector for general application.)
()Main control room electronic cubicle room computer room ()
()(20 to 25 sq.m per detector)
() IS/NFPA (the exact requirement
shall calculated based on relevant IS/NFPA standard)
Table 8-5 Common sources of aerosols and particulate matter moisture
Moisture
Atmospheric
Corrosive atmospheres
Humidifiers
contaminants
Dust or lint
Live steam
Showers
Heat treating
Slop sink
Steam tables
Pneumatic transport
Water spray
Textile
and
agricultural
processing
Combustion
Chemical fumes
Engine
products
Cleaning fluids
exhaust
and fumes
Cooking equipment
Curing
not
vented
to
the
outside
8-23
brazing
Heating
Dryers
element
Exhaust hoods
abnormal
Fireplaces
conditions
Machining
Ovens
Paint spray
with
Dust
accumulations
Improper
exhaust
Incomplete combustion
Airflow
Vibration or shock
Gusts
Radiation
Excessive velocity
Radio frequency
Electrostatic discharge
Power supply
cover.
()
(ambient temperature, pressure,
altitude, humidity, and atmosphere)
Table 8-x Comparison of combination, multi-criteria, and multi-sensor detectors
Detector Type
Features
Multiple sensors
Combination
Multi-criteria
Multi-sensor
. Mounting
. (Detector Spacing)
beam detector
(for sloping ceilings with beams running perpendicular across slope, the following shall apply)
8-25
() (spacing
shall be measured along a horizontal projection of the ceiling)
() Beam
(smooth ceiling spacing shall be permitted within beam pockets)
() % beam spot type detector
(For beam depths less than or equal to 10 percent of the
ceiling height (0.1 H), spot-type detectors shall be located with smooth ceiling spacing.)
() 0.4H % % beam
spot-type detector (For beam depths greater than 10 percent of the
ceiling height (0.1 H), spot-type detectors shall not be required to be located closer than (0.4 H)
and shall not exceed 50 percent of smooth ceiling spacing.)
beam
(for sloping ceilings with beams running parallel up slope, the following shall apply)
() Spot-type detector(s) shall be located on the ceiling within beam pocket(s).
() The ceiling height shall be taken as the average height over slope.
() Spacing shall be measured along a horizontal projection of the ceiling.
() Smooth ceiling spacing shall be permitted within beam pocket(s) parallel to the beams.
() For beam depths less than or equal to 10 percent of the ceiling height (0.1 H), spot-type detectors
shall be located with smooth ceiling spacing perpendicular to the beams.
() For beam depths greater than 10 percent of the ceiling height (0.1 H), the following shall apply
for spacing perpendicular to the beams.
() For beam spacing greater than or equal to 40 percent of the ceiling height (0.4 H), spot-type
detectors shall be located in each beam pocket.
() For beam spacing less than 40 percent of the ceiling height (0.4 H), spot-type detec-tors shall not
be required in every beam pocket but shall be spaced not greater than 50 percent of smooth
ceiling spacing.
beam (for sloped ceilings with beam pockets formed by intersecting
beams, the following shall apply)
() Spot-type detector(s) shall be located at the bottom of the beams.
() The ceiling height shall be taken as the average height over slope.
() Spacing shall be measured along a horizontal projection of the ceiling.
() For beam depths less than or equal to 10 percent of the ceiling height (0.1 H), spot-type
8-26
detectors shall be spaced with not more than three beams between detectors and shall not
exceed smooth ceiling spacing.
() For beam depths greater than 10 percent of the ceiling height (0.1 H), spot-type detectors shall
be spaced with not more than two beams between detectors, but shall not be required to be
spaced closer than (0.4 H), and shall not exceed 50 percent of smooth ceiling spacing.
- High Air Movement Areas (Not to Be Used for Under-Floor or Above-Ceiling Spaces).
Air
Changes
per Hour
ft2
m2
60
125
12
30
250
23
20
375
35
15
500
46
12
625
58
10
750
70
8.6
875
81
7.5
900
84
6.7
900
84
10
900
84
8-27
Detectors.
effects on detection
- Four-Wire Smoke Detectors Supervised for the Absence of Operating Power by an End-ofLine Power Supervision Relay.
8-28
8-29
- Inclined Manometer for Velocity Pressure Readings in Low Velocity Ducts, 400 ft/min to 2000
ft/min (2.0 m/sec to 14.2 m/sec).
Notification Appliance.
Impaired.
If appropriate, the Plans and Specifications addressed in D.3.3 should be updated based on the results
of the test.
8-30
- Hard-Wired Multiple-Station
Battery Backup.
8-31
Table 8-6 Ceiling height limits (category P systems and 5 minute fire service attendance).
8-32
Table 8-7 Ceiling height limits (category P systems and 5 minute fire service attendance).
-EndContents
.. ............................................................................................
8-34
8-35