approval along with this submission as per TCE comments through LOT no. 297, comments sheet no 5946A-811-ETA-35.R5 dated 26-11-2013
2. Kindly provide ETAP Software File along
with relay setting calculation
3.Page no-6- Kindly cross check transformer
bus no. & correct the same
3. Page 8- few loads are not matching with
loads mentioned in Revision 5 SLD dated26.9.2013. Kindly correct the same as per updated SLD and submit the same SLD
4. Page 14- cooling pump other eqiupments
are shown 230v(1ph) where as in Revision 5 SLD dated 26.9.2013. it is mentioned 415V(3Ph) Kindly correct the same as per updated SLD and same SLD for our approval. 5.custmised detailed relay settings p-1, few loads are not matching with SLD R5 as well as table provided on page no8 of report