Heat gain from people
ROOM DB TEMPERATURE
28 C
W

27 C
W

26 C
W

24 C
W

21 C
W

typical application

Degree of activity

Bank
Factory + Bowling alley
Dance hall

Standing,Walking slowly
Heavy work
Moderate dancing

53
132
64

94
293
185

59
136
72

88
289
177

64
142
81

82
283
169

75
154
95

72
271
154

85
177
117

62
248
132

Apartments+College+Hotels+Offices,Dept.,Retail,or Variety store

Standing,Walking slowly,Office worker

53

79

59

73

63

69

72

60

84

48

Drug store
Factory
Factory
High school
Restaurant
Theater+grade school

Walking,seated
Light bench work
Fairly heavy work,Walking,3mph
Seated,Very light work
Sedentary work
Seated at rest

53
56
79
53
56
51

94
164
214
64
106
51

59
64
88
57
64
57

88
155
205
60
97
45

64
72
97
63
70
62

82
148
196
54
91
41

75
86
111
70
82
67

72
133
182
47
79
35

85
107
135
81
94
76

62
113
158
37
67
26

Sens latent Sens latent Sens. latent Sens. latent Sens. latent

*** RESTAURANT VALUES INCLUDE 60BTU/H FOR FOOD/INDIVIDUAL (30BTU SENS. + 30BTU LATENT HEAT/HOUR
***METAB. RATE ADULT FEMALE = METAB. RATE ADULT MALE X 0.85