PRIME
275 ekW 343 kVA
60 Hz 1800 rpm 480 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.
FEATURES
Fuel Strategy
Low fuel consumption
UL 2200
UL 2200 Listed packages are available. Certain
restrictions may apply. Consult with your
Caterpillar dealer
FULL RANGE OF ATTACHMENTS
Wide range of bolt-on system expansion
attachments, factory designed and tested
ENCLOSURES (optional)
Weather protective and sound attenuated
SINGLE SOURCE SUPPLIER
Factory-designed systems built at Caterpillar ISO
9001:2000 certified facilities
Fully prototype tested with certified torsional
vibration analysis available
WORLDWIDE PRODUCT SUPPORT
Caterpillar dealers provide extensive post sale
support including maintenance and repair
agreements
Caterpillar dealers fill 99.7% of parts orders within
24 hours
Caterpillar dealers have over 1,600 dealer branch
stores operating in 200 countries
The Cat SOSSM program cost effectively detects
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products
Standard
Service Indicator
Regular-duty panel type air cleaner
Cooling
Exhaust
Fuel
Generator
Self excited
Class H insulation
Class F temperature rise (105C pr ime/130C standby)
VR3F Voltage Regulator, 3-phase sensing, 2:1 Volts/Hz
Generator
Self excited
Class H insulation
Class F temperature rise (105C pr ime/130C standby)
VR3F Voltage Regulator, 3-phase sensing, 2:1 Volts/Hz
Governor
Hydra-mechanical
Control Panels
EMCP II
Lube
Mounting
Starting/Charging
General
Optional
Dual element air cleaner
Light-duty air cleaner
Heavy-duty air cleaner & muffler
Precleaner
Low coolant level alarm or shutdown
Heat exchanger and expansion tank
Jacket water heater
Oversize radiator
Caterpillar Extended Life Coolant
Industrial muffler
Residential muffler
Critical muffler
Muffler mounting kit
Flexible fitting
Water separator
Day tanks
Flexible fuel lines
Fuel pressure gauge
Permanent magnet excited
Anti-condensation space heater
Terminal strip connection
Extension box
Oversize generator
Circuit breaker, UL Listed, 3 & 4-pole with shunt trip
Multiple breaker capability
Permanent magnet excited
Anti-condensation space heater
Terminal strip connection
Extension box
Oversize generator
Circuit breaker, UL Listed, 3 & 4-pole with shunt trip
Multiple breaker capability
Woodward 1724
Woodward 2301A
Woodward 2301A Load Sharing
Load sharing module
EMCP II+
Customer Communication Module
Local alarm and remote annunciator modules
Manual sump pump
27 November 2006
10:29 AM
SPECIFICATIONS
CAT GENERATOR
27 November 2006
10:29 AM
TECHNICAL DATA
Open Generator Set - - 1800 rpm/60 Hz/480 Volts
Low Fuel Consumption
DM2266
343.75 kVA
275 ekW
Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Heat rejection to aftercooler
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)
Heat rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
Alternator2
Motor starting capability @ 30% voltage dip
Frame
Temperature Rise
Lube System
Sump refill with filter
79.6 L/hr
61.6 L/hr
44.7 L/hr
21.0 Gal/hr
16.3 Gal/hr
11.8 Gal/hr
58 C
0.12 kPa
684 m/min
57.8 L
20.8 L
37.0 L
136 F
0.48 in. water
24155 cfm
15.3 gal
5.5 gal
9.8 gal
23.1 m/min
815.8 cfm
529.1 C
64.6 m/min
22 kW
152.4 mm
6.7 kPa
984.4 F
2281.3 cfm
1251 Btu/min
6.0 in
26.9 in. water
185 kW
298 kW
61 kW
19.7 kW
10521 Btu/min
16947 Btu/min
3469 Btu/min
1120.3 Btu/min
682 skVA
LC5014J
125 C
225 F
38.0 L
10.0 gal
Emissions3
NOx g/hp-hr
8.02 g/hp-hr
CO g/hp-hr
1.08 g/hp-hr
HC g/hp-hr
.09 g/hp-hr
PM g/hp-hr
.324 g/hp-hr
1
Ambient capability at 200 m (660 ft) above sea level. For ambient capability at other altitudes consult your Caterpillar dealer.
2
Generator temperature rise is based on a 40 C (104 F) ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77F, 28.42 in HG and number 2 diesel fuel
with 35 API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and
engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use
values based on a weighted cycle.
27 November 2006
10:29 AM
27 November 2006
10:29 AM
DIMENSIONS
Package Dimensions
Length
Width
Height
Weight
4182.0 mm
1110.0 mm
2100.1 mm
2843 kg
164.65 in
43.7 in
82.68 in
6,268 lb
www.CAT-ElectricPower.com
2006 Caterpillar
All rights reserved.
8789053