Professional Documents
Culture Documents
Using High-Speed Grounding Switches - EEP
Using High-Speed Grounding Switches - EEP
Protectionofpowertransformers//
Automatichighspeedgroundingswitchesareappliedforprotectionofpowertransformers
whenthecostofsupplyingotherprotectiveequipmentisdeemedunjustifiableandtheamountof
systemdisturbancethatthehighspeedgroundingswitchcreatesisjudgedacceptable.
Theswitchesaregenerallyactuatedbydischargingaspringmechanismtoprovidethehigh
speedoperation.
Thegroundingswitchoperatestoprovideadeliberategroundfaultononephaseof
thehighvoltagebussupplyingthepowertransformer,disruptingthenormally
balanced120phaseshiftedthreephasesystembyeffectivelyremovingonephase
andcausingtheothertwophasestobecome180phaseshiftedrelativetoeachother.
Thissystemimbalanceisremotelydetectedbyprotectiverelayingequipmentthatoperates
thetransmissionlinebreakersattheremoteendofthelinesupplyingthepower
transformer,trippingthecircuitopentoclearthefault.
Thisschemealsoimposesavoltageinterruptiontoallotherloadsconnectedbetweentheremote
circuitbreakersandthepowertransformeraswellasatransientspiketotheprotectedpower
transformer,effectivelyshorteningthetransformersusefullife.
Cleaveland/Prices High speed grounding switch 115 kV 230 kV, 120 kA momentary / 71kA, 3 sec.
(cleavelandprice.com)
Frequently,asystemutilizingahighspeedgroundswitchalsoincludestheuseofamotor
operateddisconnectswitchandarelaysystemtosensebusvoltage.
Therelaysystemslogicallowsoperationofthemotoroperateddisconnectswitchwhenthere
isnovoltageonthetransmissionlinetoprovideautomaticisolationofthefaultedpower
transformerandtoallowreclosingoperationsoftheremotebreakerstorestoreservicetothe
transmissionlineandtoallotherloadsfedbythisline.
Thegroundingswitchschemeisdependentontheabilityofthesourcetransmission
linerelayprotectionschemetorecognizeandclearthefaultbyopeningtheremote
circuitbreaker.
Clearingtimesarenecessarilylongersincethefaultlevelsarenotnormallywithinthelevels
appropriateforaninstantaneoustripresponse.
500kVMotorOperatedDisconnectSwitch(VIDEO)
Cantseethisvideo?ClickheretowatchitonYoutube.
Thelengtheningofthetriptimealsoimposesadditionalstressontheequipmentbeing
protectedandshouldbeconsideredwhenselectingthismethodforpowertransformerprotection.
Highspeedgroundingswitchesareusuallyconsideredwhenrelativefaultlevelsarelowsothat
theriskofsignificantdamagetothepowertransformerduetotheextendedtriptimesismitigated.
Resource:ElectricPowerSubstationsEngineeringJ.D.McDonald