HMI Turbine Screen Standards


(Version 1.0 Released August 12, 1998)

1999 General Electric Company, USA


All rights reserved
Printed in the United States of America

HMI Turbine Screen Standards

1.0 INTRODUCTION.......................................................................................................................................... 5
1.1 FILE NAMING CONVENTION ........................................................................................................................... 5
1.2 GENERAL DESIGN GUIDELINES ...................................................................................................................... 5
2.0 DESIGN PHILOSOPHY, FUNCTIONAL GROUPING AND OBJECT NAMING ................................... 7
2.1 INTERFACE FOUNDATION .............................................................................................................................. 7
3.0 7FA DESIGN STANDARDS........................................................................................................................ 21
3.1 OBJECT GROUPING AND NAMING ................................................................................................................. 22
Figure 3.1: Startup Screen Grouping........................................................................................................... 22
4.1 GENERAL FOUNDATION SCREEN .................................................................................................................. 24
4.2 NAVIGATIONAL BUTTONS............................................................................................................................ 25
4.3 ALARMS ..................................................................................................................................................... 26
4.4 TREND SCREENS ......................................................................................................................................... 26
5.0 DATA DELIVERY & ACTIVE CONTROL OBJECT TYPES................................................................. 29
6.0 BAR GRAPHS ............................................................................................................................................. 41
6.1 FSR BAR GRAPH ........................................................................................................................................ 42
Table 6.1: FSR ............................................................................................................................................ 42
6.2 BEARING TEMPERATURES ............................................................................................................................ 43
Table 6.2: Bearing Temperatures ................................................................................................................ 43
6.3 EXHAUST TEMPERATURES ........................................................................................................................... 44
Table 6.3: Exhaust Temperatures ................................................................................................................ 44
6.4 GENERATOR RTD TEMPERATURES .............................................................................................................. 46
Table 6.4 Generator RTD Temperatures...................................................................................................... 46
6.5 VIBRATION PROXIMETERS ........................................................................................................................... 48
Table 6.5: Vibration Proximeters................................................................................................................. 48
6.6 SEISMIC VIBRATION .................................................................................................................................... 49
Table 6.6 Seismic Vibration......................................................................................................................... 49
6.7 WHEELSPACE TEMPERATURES ..................................................................................................................... 51
Table 6.7 Wheelspace Temperatures............................................................................................................ 51
6.8 FLAME TEMPERATURES ............................................................................................................................... 54
Table 6.8 Flame Temperatures .................................................................................................................... 54
7.0 GRAPHIC SYMBOLS AND ANIMATION DYNAMICS ......................................................................... 55
7.1 FUEL LINES................................................................................................................................................. 55
7.2 GAS TURBINE ............................................................................................................................................. 56
7.3 DLN 2.6 PIPING & VALVING GRAPHIC ........................................................................................................ 57
7.4 DLN 2.6 NOZZLE GRAPHIC ......................................................................................................................... 59
7.5 EXHAUST THERMOCOUPLE GRAPHICS .......................................................................................................... 62
8.0 START CHECK SCREEN .......................................................................................................................... 64
9.0 TRIP SCREEN............................................................................................................................................. 66
10.0 LIQUID FUEL DELIVERY SYSTEM ..................................................................................................... 68
10.1 LIQUID FUEL DELIVERY............................................................................................................................. 68
11.0 WATER INJECTION SYSTEM ............................................................................................................... 71
12.0 STEAM POWER AUGMENTATION SYSTEM ..................................................................................... 73
13.0 FRAME ANIMATION .............................................................................................................................. 76

HMI Turbine Screen Standards

14.0 MULTI-UNIT CONFIGURATION........................................................................................................... 77


14.1 OVERVIEW ................................................................................................................................................ 77
14.2 NAMING CONVENTION .............................................................................................................................. 77
14.3 TOOLS BUTTON ........................................................................................................................................ 79
14.3 VIEWER LIMITATIONS ............................................................................................................................... 79

HMI Turbine Screen Standards

1.0 Introduction
CIMPLICITY HMI standards have been developed for GE Powerplant Turbines for both
Steam Turbines and Gas Turbines. The standards are applicable to all Frame sizes and are in
both English and Metric. The standards represent maximum case scenarios and thus
customization for a particular requisition does not require the requisition engineer to design
new screens, they simply need to delete screens that do not pertain to their requisition (dual
fuel, water injection, steam injection, etc). The design philosophy behind the standards, details
of screen components including geometry information and color animation is documented.
Adherence to the standards is strongly recommended since they will help to optimize operator
usability and assure graphical uniformity.
1.1 File Naming Convention
Individual standards are named so that requisition engineers can quickly identify the required
standard for their requisition. For example a frame 7001EA with English units will be named
7001EA_English.cim. Note: The standard must be renamed to Unit_Control.cimfor
navigation between the overview and synchronization screens to work properly.
All Trend screens will be named according to the trend data that is to be displayed. The word
Trendwill precede the description of the data contained within that file. Thus the following
are examples,
Trend_Bearing_Drain.cim
Trend_Bearing_Metal.cim
Trend_Exhaust_Temp.cim
Trend_Generator_RTD.cim
A separate synchronization file is required for each unit that is to be controlled. These files will
be named as follows.
Synchronization_Unit1.cim
Synchronization_Unit2.cim
Synchronization_Unit3.cim

1.2 General Design Guidelines


Some general design considerations have been adopted in the development of these design
standards. These include the display of critical turbine parameters, including IGV angle,
Compressor Delivery Pressure, Exhaust Temperature, Turbine Speed, on every screen. A
minimum height of 24 pts and width of 30 pts is used with buttons to facilitate usage in
touchscreen applications. In the selection of nomenclature acronyms have been avoided and
English wherever feasible.

HMI Turbine Screen Standards

HMI Turbine Screen Standards

2.0 Design Philosophy, Functional Grouping and Object Naming


2.1 Interface Foundation
Level 0:

Overview
Tools
Alarms

When procedures access files separate from the Unit_Control.cim file,


procedures are used.
L0
Sometimes buttons are stacked upon on another and the UNIT_NO
screen variable is used to set the buttons visibility. This feature allows
unit specific procedures to be linked to what appears to be a single
button.

synch

gt1 synch

gt2 synch

gt3 synch

gt4 synch

demand

gt1 demand

gt2 demand

gt3 demand

gt4 demand

Level 1:

Gas Turbine 1
Gas Turbine 2

Each turbine unit has a single pushbutton used to assign the UNIT,
UNIT_NAME and UNIT_NO screen variables. All points within the
Unit_Control.cim file (i.e., L1START, L4) are proceeded by the screen
variable UNIT(Unit_L1START, Unit_L4, Unit_L4T). Thus the L1 buttons
are used to navigate from Unit1 Control to Unit2 Control and the same
CIMPLICITY file may be used.

Gas Turbine 3
Gas Turbine 4

This functionality simplifies revision control on multi-unit interfaces. The


UNIT variable is assigned values such as T1_, T2_ for gas or S1_,
S2_ for steam, depending on the number of units. Thus, when Unit3
Control is selected, the variable Unitis assigned. The UNIT_NAME
variable is displayed in the upper right hand corner on the turbine
banner. The UNIT_NO variable is used to assign object visibilitys to
buttons like Toolsor GT# Synch.

HMI Turbine Screen Standards

Level 2:

Control

The second grouped of buttons on the right side of the Unit_Control


screen are used for function mode navigation. Functionally these
buttons break the DATA_CTRL frame containers navigation up into the
following four groups; Control, Monitoring, Auxiliary and Tests.

Monitor
Aux
Tests

When one of these buttons is depressed the last set of buttons actually
the NAV_CTRL frame container display will be affected. Mouse up sets
the NAV_CTRL screen variable and allows access to all Control options,
Monitoring Options, Auxiliary Options or Test Options.
The procedures for this level of navigation are preceded by L2, thus,
allowing functional grouping of all navigation procedures (i.e., L1, L2 and
L3).
Additionally, the last user selected control option, monitoring option,
auxiliary option or test option is maintained in memory. Thus allowing
the user the option of toggling between a certain control screen(ex. DLN
2.6) and a particular monitoring screen(ex. Exhaust Temps) by
depressing the level 2 navigation buttons (control/monitoring).

HMI Turbine Screen Standards

Level 3:

The final set of navigation buttons (colored 170, 170, 170) are used for
actual frame to frame navigation. The Level 3 options(button lists) are
displayed using a frame container called NAV_CTRL and are set to a
number between 1 and 4 corresponding with the value for Control,
Monitoring, Ax or Tests..
These buttons assign the variable DATA_CTRLand allow navigation to
all the control, monitoring, aux. and test frames(currently 26 possible
frames). The Data control frames are named according to the Level 3
buttons that are used to get to these frames. For example, the motors
button will take you to the motorsframe and the tripsbutton will take
you to the tripsframe.

Control

Monitor

Aux

Tests

start-up

bearing temps

demand

contacts

dln

exhaust

flame

overspeed test

FSR control

generator rtd

gen capability

shaft voltage

gen/exciter

hydrogen

start check

IGV Control

proximeter vibe

static start

liquid fuel

seismic vibration

timers

motors

wheelspace

trip diagram

steam power aug


water injection
gt1 synch
gt2
gt3
gt4

Screen File Names

All standards are max case scenarios. Standards are available for all
frame sizes in either English or metric. Thus customization for a
particular requisition does not require the requisition engineer to design
new screens, they simply need to delete screens or frames that do not
HMI Turbine
Screen Standards
9 etc).
pertain
to their requisition(dual
fuel, water injection, steam injection,
Standards are named so that requisition engineers can quickly identify

Procedures

Procedures have been named to foster functional grouping. All alarm


button actions are named using Alarm_. All navigation procedures
are named with a L0_, L1_, L2_ or L3_. All controller functions are
named using Ctrl_. All motor control functions are named Motor_.

HMI Turbine Screen Standards

10

HMI Turbine Screen Standards

11

Scripts

Scripts are used to accomplish tasks that cannot easily be


accomplished using available CIMPLICITY functionality. Scripts are
written using visual basic.
Scripts can attached to single objects, grouped objects or simply
adhered to the foundation screen. Most scripts are adhered to the
foundation screen. Consult the CIMPLICITY Base Manual for more
information on editing or creating your own scripts.

HMI Turbine Screen Standards

12

HMI Turbine Screen Standards

13

HMI Turbine Screen Standards

14

HMI Turbine Screen Standards

15

HMI Turbine Screen Standards

16

Variables

Variables are used to accomplish many different types of functions.


Variables can attached to single objects, grouped objects or simply
adhered to the foundation screen. Consult the CIMPLICITY Base
Manual for more information on editing or creating your own variables.

HMI Turbine Screen Standards

17

DATA_CTRL

This variable controls the frame position of the DATA_CTRL(data


control) frame container. The data control frame container has twentysix positions and contains all the control, monitoring, auxiliary and test
screens. The value data control variable is set by L3 procedural
functions.

LAST_AUX_FRAME
LAST_MON_FRAME
LAST_TEST_FRAME
LAST_CTRL_FRAME

These variables are used in conjunction with the SetLastFrame script


and function to set the appropriate last frame screen variable to the
value of the data control screen variable(DATA_CTRL). This allows the
L2 navigation buttons to remember which control, monitoring, auxiliary
or test frame was visited last. Enabling one button navigation from the
control, monitoring, auxiliary and test buttons.
The initial value of these variables can be set so that a favorite control,
HMI Turbine
Screen
18first
monitoring,
auxiliary
or Standards
test data control screen can be seen at the
depression of the navigation control buttons. However, last defaults to
the first screen control, monitoring, auxiliary or test screen set.

NAV_CTRL

This variable controls the frame position of the NAV_CTRL(navigation


control) frame container. The navigation control frame container has
four positions and contains all the buttons for accessing control,
monitoring, auxiliary and test screens. The value of the navigation
control variable is set by L2 procedural functions.

Control
Monitor
Aux
Tests

POPUP

The POPUP variable is used in conjunction with a screen hot spot to


access data about or control for certain motors, pumps and valves.
When a screen is opened POPUP is initialized at a value of zero.
Every popup is grouped and the groups visibility is set using the
control animation tab and the POPUP variables value. Thus only one
popup object can be displayed at any one time.
A X button in the upper right hand corner is used to set POPUP to
zero and close the currently viewed popup object.

Speed Ratio Valve X


Reference

###

Feedback

###

Data Popup Object Example

HMI Turbine Screen Standards

19

SHOW_POINT_ID

The SHOW_POINT_ID screen variable is used with a single button to


toggle from a datas text description to the GE Point ID. This
functionality is sited for the GEPPETTOs next revision.

Exhaust

### ##

Speed

#### ###

Max Vibe

#.## ##

CPD

### ###

IGV

## ###

Watts

##.# ##

Vars

##.# ##

TTXM

### ##

TNH_RPM

#### ###

BB_MAX

#.## ##

CPD

### ###

CSGV

## ###

DWATT

##.# ##

DVAR

##.# ##

HMI Turbine Screen Standards

20

3.0 7FA Design Standards


A listing of the frames for a maximum case 7F machine are shown in the attached table. The
Level 3 Procedure Names, associated Data_Ctrl Values which identify the order of the frames
in the frame container are specified. In addition whether the screen frame is a requirement or
optional depending on the requisition and the Navigation Control/ Classification for a maximum
case 7F machine are provided.
In a case where the optional frame is not required it will be necessary to perform the following
steps
1) Open the main frame container, go to the required frame and delete the required frame
using the delete button on the left-hand side of the screen.
2) Modify the LAST_CTRL_FRAME, LAST_MON_FRAME, LAST_AUX_FRAME or
LAST_TEST_FRAME variable to reflect the reduced number of frames. The variables
maybe located by closing the main frame container and under edit in the main toolbar
selecting properties and the variable tab.
3) Delete the button associated with the deleted frame (Note: the buttons are in their own
frame container.)
Procedure DATA_CTR
NAV_CTRL Classification
Frame Name
L
Name
Value
Required Control Monitoring Aux. Tests
L3_Startup
1
Yes
1
Frame_7F_Startup
L3_DLN26
2
Optional
1
Frame_DLN26
L3_FSR_Ctrl
3
Yes
1
Frame_FSRControl
L3_Gen_Exc
4
Yes
1
Frame_7F_GeneratorEX2
K
L3_IGV_Ctrl
5
Yes
1
Frame_IGVControl
L3_Liquid
6
Optional
1
Frame_7F_LiquidFuel
L3_Motors
7
Yes
1
Frame_7F_Motors
L3_SteamPA
8
Optional
1
Frame_7F_Steam
L3_Water_Inj
9
Optional
1
Frame_7F_WaterInjection
L3_Brg_Tmps
10
Yes
1
Bar_7F_BearingTemps.ci
m
L3_Exhaust
11
Yes
1
Bar_7F_ExhaustTemp
L3_Gen_RTD
12
Yes
1
Bar_7F_GeneratorRTD
L3_Hydrogen
13
Yes
1
Frame_Hydrogen Purity
L3_VibProx
14
Optional
1
Bar_7F_Proximeter.cim
L3_VibSeism
15
Yes
1
Bar_7F_Seismic.cim
L3_Wheelspc
16
Yes
1
Bar_7F_Wheelspace
L3_Flame
17
Yes
1
Bar_7F_Flame Temp
L3_Gen_Cap
18
Optional
1
Frame_7F_Gen_Cap
L3_StartCk
19
Yes
1
Frame_7F_StartChecks
L3_StaticStrt
20
Optional
1
Frame_StaticStart
L3_Timers
21
Yes
1
Frame_TimersCounters
L3_Trips
22
Yes
1
Frame_7F_Trips
L3_IO_Check
23
Yes
1 Frame_7F_IO_Check
L3_OS_Test
24
Yes
1 Frame_Overspeed3600
L3_ShaftMon
25
Optional
1 Frame_ShaftVoltMon
Totals
9
7
6
3
HMI Turbine Screen Standards

21

3.1 Object Grouping and Naming

The grouping of objects has been carried out at multiple levels. At the lowest level similar
objects were grouped and at the highest level all the objects in a single frame were grouped
(excluding the objects in the Frame Foundation). This method was found to be the optimum in
both the construction and modification of objects.
Note: If an object is ungrouped then the name of the object will be automatically deleted.
Example of Object Grouping and Naming
Figure 3.1: Startup Screen Grouping

The objects which form the Start up Screen are shown in Fig: 3.1. All the objects in the
screen are grouped at the highest level and are labeled Startup Display. The next level
of grouping is at the individual object level as shown in Fig: 3.2. The individual objects
are then sub-grouped into like objects. In the example the Status Data Group is made
up of the Status Data Boxes, Status Data, Status Banner/ Text and Status Shadow. The
naming of objects has been performed at all levels as an aid to understanding.

HMI Turbine Screen Standards

22

Fig 3.2 Individual Object Grouping

HMI Turbine Screen Standards

23

4.0 General Object Properties


General Screen
Characteristics

Background Colors Silver


Screen Size
800x600
Color Depth
At least 65,000 colors
Default Fonts
Text: 12 pt Arial
(Regular)
Data: 12 pt Lucida Sans
Unicode (Regular) LSU

4.1 General Foundation Screen


The general foundation screen comprises the Title Bar, RHS Navigation buttons and the Alarm
Window.
The title bar will contain:
GE Logo Font

Font

Color - White
GE Logo Font, Regular 22
Position 605.5, 5.85

Geometry

Width 800 pt
Height 25 pt
Gradient Shading
Shade Style Diagonal Up
Color 1 66, 65, 66
Color 2 - White

Background

Color

Customer Name

Font

Arial Bold, 20
Color White (Capital Case),
Position 604, 40

To obtain a 3D effect a carbon copy of name is


superimposed on the original with a slight offset.
Controller
Time & Date

Font

Black, Arial Bold, 12

Status Banner

Geometry

Width 150 pt
Height 25 pt
GT1 color 248,193,111
GT2 color 147,156,61
GT3 color 0,195,198
GT2 color 56,192,114
Position, 600, 650
Alignment, Top/Left

Color Animated
with Unit name

HMI Turbine Screen Standards

24

Unit Name

Font

White, Arial Bold Italic, 14 pt

Data_Ctrl Value Font

Font

Anchor Position, 599.9, 767.45


Arial Italic, 12 pt
Alignment, Top/Left
Anchor Position, 590.25, 652.55

4.2 Navigational Buttons


The functionality of the navigational buttons is described in detail in Section 2.0. The buttons
are physically located on the right hand side of each screen.

Overview
Tools
Alarms

Geometry
Text

Width 100 pt
Height 24 pt
Black, Arial Regular 12

(Exception Alarm
Button Text
Exclamation Mark

Height - 63.9 pt
White, Arial Bold 12
White, Arial Bold 48)

Colors

Gas Turbine 1
Gas Turbine 2
Gas Turbine 3
Gas Turbine 4

Overview
Gas Turbine 1
Gas Turbine 2
Gas Turbine 3
Gas Turbine 4
Tools
Alarms
Control, Monitor
Aux, Tests
Frame Navigation
Buttons

108,163,160
243,193,111
147,156,61
0,195,198
56,192,114
198,195,0
255,0,0 (Red)
0,128,128 (Teal)
170,170,170

Control

Monitor

Aux

Tests

start-up

bearing temps

demand

contacts

dln

exhaust

flame

overspeed test

FSR control

generator rtd

gen capability

shaft voltage

gen/exciter

hydrogen

start check

IGV Control

proximeter vibe

static start

liquid fuel

seismic vibration

timers

motors

wheelspace

trip diagram

steam power aug


water injection

HMI Turbine Screen Standards

25

4.3 Alarms
Alarms allow for 4 priority classifications distinguished by the implemented color scheme.
Ack/UnAck
Unacknowledged
Unacknowledged
Acknowledged
Acknowledged

Normal/Alarm
Alarm
Normal
Alarm
Normal

Text/Background
White/Red
Black/White
Red/White
Auto Reset

4.4 Trend Screens


Trend Screens are associated with Bar Graphs and are opened by button
actions located on individual Bar Graph screens. CIMPLICITY Trending can
only be accomplished in a real time mode. Thus, trend screens must be open
to continue trending.

General Screen
Characteristics

Background Colors

Screen Size
Color Depth

Buttons

Geometry,
Color
Font

Silver for Button Area,


Gray for Chart Area &
Time Interval Area
800x600
At least 65,000

Width 90 pts, Height 30 pts.


66, 65, 66
Black, Arial 10 pt

Trend screens, comprise of the title bar, trend options and time interval
selections for which trend is required. The title bar is similar to the main
screen title bar with the addition of the screen title.

HMI Turbine Screen Standards

26

Unit Name

Font

White, Arial Bold Italic, 14 pt

Data_Ctrl Value

Font

Anchor Position, 599.9, 767.45


Arial Italic, 12 pt
Alignment, Top/Left
Anchor Position, 590.25, 652.55

GE Logo Font

Font

Color - White
GE Logo Font, Regular 22
Position 605.5, 5.85

Geometry

Width 800 pt
Height 25 pt
Gradient Shading
Shade Style Diagonal Up
Color 1 66, 65, 66
Color 2 - White

Background

Color

Customer Name

Font

Arial Bold, 20

Color White (Capital


Case),
Position 604, 40
To obtain a 3D effect a carbon copy of name is
superimposed on the original with a slight offset.
Font

Status Banner

Black, Arial Bold, 12

Geometry

Width 150 pt
Height 25 pt
Color Animate GT1 color 248,193,111
with Unit
GT2 color 147,156,61
GT3 color 0,195,198

GT4 color 56,192,114


Position, 600, 650
Alignment, Top/Left

Trend Options

Trend Options are selectable by buttons, identified by point


description. Individual Buttons are available to select Var/
Watts/ Speed; all point descriptions, maximum point value,
clear display, show legend and hide legend.

HMI Turbine Screen Standards

27

y Var, Watts, Speed


Button

Point Description
Buttons

Point Description
Header

Time Interval

Time Interval
Buttons

Geometry Height 24 pts, Width 120 pts


Color - Silver

Geometry Height 24 pts, Width 90 pts


Color Silver
Text, Black, Arial Regular 11

Text, Black, Arial Regular 11


Alignment Left/Top

The time intervals currently available for Trend


Charts are 24hr, 5hr, 60min, 30min, 10min,
5min and 1min. These intervals maybe modified
by the requisition engineer as required.

Geometry Height 30 pts, Width 50 pts


Button Color, Silver
Text, Black, Arial Regular
12

Trend Chart Example

HMI Turbine Screen Standards

28

5.0 Data Delivery & Active Control Object Types


Data Delivery &
Active Control
Object Types

Data Groups, Enumerated Data Groups, Control Groups, Setpoint


Control Groups, Motor Control Groups and Bar Graph Groups
comprise the majority of data delivery and active control object
types.

Data Group Specifics

Data Groups are divided into five lesser groups.

Data_Boxes

Height - 16 pts in height


Widths divisible by 10 pts.
Fill Color Light Gray (231, 227, 231)
Two white lines placed on the bottom and on the right are used
to provide a shadowed look to this object. These boxes are
vertically aligned and spaced 3 pts apart. Text is bottom
aligned in the databox

Data

Data feedback using point ID.


Text Color - Black
Numeric Data using Lucida Sans Unicode 11pt, with a
right/center anchor
Text using Arial 11pt, with left center text anchor.

Accelerating
Starting
Enumerated State Text Data

Banner

789
3456
Numerical Data

TealTurbine
box. Text
descriptions
are grouped and centered on the29
HMI
Screen
Standards
banner.

Turbine Status

Exhaust

Turbine State

Speed

* Turbine Status is a Enumerated Description using the


Controllers enumerated state variable NORMAL.

HMI Turbine Screen Standards

30

EU_Label

Engineering units label,


Text Color - Black, Arial 11pt, left/center anchor.

deg F
rpm
Shadow

Two boxes encompassing all data being displayed. One black, one
white, slightly offset to provide a shadowed look appearance.

Data Group Example

Exhaust

### ##

Speed

#### ###

Max Vibe

#.## ##

CPD

### ###

IGV

## ###

Watts

##.# ##

Vars

##.# ##

HMI Turbine Screen Standards

31

.Control Group Specifics

Control groups objects are divided into three major groups; the
banner, the buttons and the shadow Data Groups are divided
into five lesser groups.

Banner

encompasses the control objects title


Text Color - White, Arial 12pt
Teal box background for text contrast

Load
Select
Buttons

Text Color - Black, Arial 12pt, text.


Geometry of 70 wide(or divisible by 10) and 24 high.
Title case is used for text. Buttons are aligned and vertically
spaced 0 pts apart.

Preselect Ld
Base Load
Peak Load
Shadow

Two boxes encompassing all data being displayed. One black, one
white, slightly offset to provide a shadowed look appearance.

HMI Turbine Screen Standards

32

Control Group Example

Load
Select
Preselect Ld
Base Load
Peak Load

Setpoint Group Specifics Setpoint group objects are divided into five major groups; Data
Boxes, Data Text and Banner, Data, Units and the Shadow

Data_Boxes

Height - 16 pts
Widths divisible by 10 pts.
Two white lines placed on the bottom and on the right are used
to provide a shadowed look to this object. These boxes are
vertically aligned and spaced 3 pts apart. Text is bottom aligned
in the box

HMI Turbine Screen Standards

33

Data Text & Banner

Text Color White, Arial 11pt, right/ center anchor.


The Banner is a Teal Box. The text descriptions are grouped
and centered on the banner.
Header Text - Black text, Arial 12 pt, left/ top anchor is placed
above Banner.

IGV Mode Control


Setpoint
Reference
IGV Angle
Data

Data feedback using point ID.


Text Color - Black, Numerical using Lucida Sans Unicode 11pt, with
a right/center anchor and Text using Arial 11pt, with left center text
anchor.

53.0
53.0
50.0

EU_Label

Engineering units label


Text Color - Black, Arial 11pt, left/center anchor.

DGA
DGA
DGA

Shadow

Two boxes encompassing all data being displayed. One


black, one white, slightly offset to provide a shadowed look
appearance.

HMI Turbine Screen Standards

34

Setpoint Group Example

IGV Mode Control


Setpoint

53.0 DGA

Reference

53.0 DGA

IGV Angle

50.0 DGA

Motor Control Group

Motor control group objects are divided into four major groups; the
banner, the buttons, status indicators and the shadow box.

Banner

Encompasses the control objects title (White, Arial 12pt) and the teal box
background for text contrast

Hydraulic Supply Pump

HMI Turbine Screen Standards

Auto
Rotate

35

Buttons

Text Color - Black, Arial 12pt, text.


Geometry of 70 pts wide and 24 pts high.
Title case is used for text.
Buttons are aligned and vertically spaced 0 pts apart.
The text on the buttons is color animated and turns yellow when the button
is in the active state.

#1 Lead

#2 Lead

#1 Lead

On

#2 Lead

Off

Off
Active

Status Boxes

On

Inactive

Text Color Black, Arial Bold 12 pt centered on the object.


Geometry - Height 22 pts, Width - 68 pts wide.
Two white lines placed on the top and on the left hand side are used to
provide a raised look to this object. These boxes are vertically left aligned with
the buttons directly above and have their middles aligned with the button to
the right.

Running

Running
Shading

The boxes and text are color animated


Boxes: Running State, Color Red with center gradient
shading of 255, 195, 198
Stopped State, Color 0,195,0 with center gradient
shading of198, 255, 198
Text: Running State, Text Runningwith color Lime
Stopped State, Text Stoppedwith color Red

Stopped

Running

Color Animation

HMI Turbine Screen Standards

36

Shadow

Two boxes encompassing all data being displayed. One black, one
white, slightly offset to provide a shadowed look appearance.

Motor Control Group Example

Hydraulic Supply Pump

Auto
Rotate

#1 Lead

#2 Lead

On

Running

Running

Off

Enumerated Data Group


Specifics

Enumerated Data Group objects consist of four objects,


Enumerated Data Descriptions, Data Boxes, Data and Data
Shadow.

HMI Turbine Screen Standards

37

Data Descriptions

Text Color - White, Arial 11pt, right/center anchor.


The text descriptions are grouped and centered on the
Teal Box banner.

Turbine Status
Turbine State
Control Mode
Fuel Control
Tie Line Status
IGV Control
The Turbine Status is an Enumerated Description using the
Controllers enumerated state variable NORMAL.

HMI Turbine Screen Standards

38

Enumerated Data Boxes

Geometry Height - 16 pts


Width of 130 pts divisible by 10 pts.
Two white lines placed on the bottom and on the right are used
to provide a shadowed look to this object. These boxes are
vertically aligned and spaced 3 pts apart.

Enumerated Data

Text Color Black, Arial 11pt, with left center text


anchor

Accelerating
Starting
Manual
Acceleration LP
Sequence In Progress
IGV Full Open

Shadow

Two boxes encompassing all data being displayed. One black, one
white, slightly offset to provide a shadowed look appearance.

HMI Turbine Screen Standards

39

Enumerated Group Example

Turbine Status Accelerating


Turbine State Starting
Control Mode Manual
Fuel Control Acceleration LP
Tie Line Status

Sequence In Progress

IGV Control IGV Full Open

HMI Turbine Screen Standards

40

6.0 Bar Graphs

Gas Control Valves

###

###
###

##
200

##
100

###
###

###
###

###
###

###

##
100

160

80

80

120

60

60

80

40

40

40

20

20

Ref Fbk

SRV

Ref Fbk

PM1

Ref Fbk

PM2

Ref Fbk

PM3

Ref Fbk

QUAT

Axis Unit Font


X-Axis Label
Y-Axis Minor Label
Y-Axis Major Label
Label Alignment

Arial Reg. 10 pt, Color - Black 0,0,198


Arial Reg. 12 pt, Color - Blue
Arial Reg. 10 pt, Color - Black
Arial Reg. 12 pt, Color - Blue
Parallel to Axis

Chart Lines

Black 0,0,198
Width: 0 pt
Number of horizontal lines on graph should be minimized and
placed behind bar graphs.
Width: 20 pt
Ht: 120 pt (Increment or decrement 10 pts)
Color: Black
Color: Light Gray
Right hand side and bottom side shaded white to give a 3-D
container effect. Grouping the RHS side and bottom side into a
single object facilitates alignment. RHS should be 1 pt less than
height of bar and anchored to the top of the bar. (If bar is 120 x
20 then shading should be 119 x 20).

Bar Geometry
Bar Border
Bar Fill
Bar Shading

Bar Data Buttons

See Data Buttons above


Width: 30 pts
Height: 16 pts

Dynamic Pointers have been added to bar graphs to identify Alarm (Yellow) and Trip (Red)
limits. The pointer levels are obtained using the actual constants in the controller.

HMI Turbine Screen Standards

41

6.1 FSR Bar Graph

The color animation for the FSR bar graph is shown in Table 6.1. The range is 0 100%
Table 6.1: FSR
Parameter

Point Name

FSR
SU
ACC

T1_FSR
T1_FSRSU
T1_FSRCC

Normal Fill
Color
0,195,198
0,195,198
0,195,198

SPD

T1_FSRN

0,195,198

TEMP

T1_FSRT

0,195,198

SD

T1_FSRSD

0,195,198

MAN

T1_FSRMAN

0,195,198

Color Animation
Switch
Non
Non
T1_L30F_ACN Eq 1
0
T1_L30F_ND Eq 1
0
T1_L30F_TMP Eq 1
0
T1_L30F_SD Eq 1
0
T1_L30F_MAN Eq 1
0

HMI Turbine Screen Standards

Color

Lime
Blue
Lime
Blue
Lime
Blue
Lime
Blue
Lime
Blue

42

6.2 Bearing Temperatures

The color animation for the Bearing Temperatures is shown in Table 6.2. The temperature
range is 0-300 deg F.
The Dynamic Alarm Limit Pointer (Yellow), and its value is used in the color animation switch.
e.g. for T1_LTTH1 the pointer value is given by the controller constant T1_LOKALM1
Table 6.2: Bearing Temperatures
Parameter

Point Name

Lube Oil Header

T1_LTTH1

Normal Fill
Color
0,195,198

Inactive Thrust
Bearing #1
Inactive Thrust
Bearing #2
Active Thrust
Bearing #1
Active Thrust
Bearing #2
Turbine Bearing 1
#1
Turbine Bearing 1
#2
Turbine Bearing
#1 Drain
Turbine Bearing 2
#1
Turbine Bearing 2
#2
Turbine Bearing
#2 Drain
Generator
Bearing 1 #1
Generator
Bearing 1 #2
Generator
Bearing #1 Drain

T1_BTTI1_4

0,195,198

T1_BTTI1_8

0,195,198

T1_BTTA1_
7
T1_BTTA1_
14
T1_BTJ1_1

0,195,198

T1_BTJ1_2

0,195,198

T1_LTB1D

0,195,198

T1_BTJ2_1

0,195,198

T1_BTJ2_2

0,195,198

T1_LTB2D

0,195,198

T1_BTGJ1_
1
T1_BTGJ1_
2
T1_LTB1D

0,195,198

0,195,198
0,195,198

0,195,198
0,195,198

Color Animation
Switch
(T1_LTTH1 GE
T1_LOKALM1)
(T1_BTTI1_4 GE
T1_BTKALM1)
(T1_BTTI1_8 GE
T1_BTKALM2)
(T1_BTTA1_7 GE
T1_BTKALM3)
(T1_BTTA1_14 GE
T1_BTKALM4)
(T1_BTJ1_1 GE
T1_BTKALM5)
(T1_BTJ1_2 GE
T1_BTKALM6)
(T1_LTB1D GE
T1_LOKALM2)
(T1_BTJ2_1 GE
T1_BTKALM7)
(T1_BTJ2_2 GE
T1_BTKALM8)
(T1_LTB2D GE
T1_LOKALM3)
(T1_BTGJ1_1 GE
T1_BTKALM9)
(T1_BTGJ1_2 GE
T1_BTKALM10)
(T1_LTG1D GE
T1_LOKALM4)

HMI Turbine Screen Standards

Animated
Color
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow

43

Generator
Bearing 2 #1
Generator
Bearing 2 #2
Generator
Bearing #1 Drain

T1_BTGJ2_
1
T1_BTGJ2_
2
T1_LTG2D

0,195,198
0,195,198
0,195,198

(T1_BTGJ2_1 GE
T1_BTKALM11)
(T1_BTGJ2_2 GE
T1_BTKALM12)
(T1_LTG2D GE
T1_LOKALM5)

Yellow
Yellow
Yellow

6.3 Exhaust Temperatures

The color animation for an Exhaust Temperature is shown in Table 6.3. The temperature range
is 0-1400 deg F. The parameter designation X varies from 1 to 27 depending upon the
thermocouple position; the color animation switches and colors are however are the same for
all thermocouples.
The red (trip) and yellow (alarm) dynamic pointers in the case of the exhaust tempertures are
an indication of approximate alarm and trip limits, actual alarms and trips are generated using
the mean exhaust temperature. The pointers are set as follows:
Dynamic Alarm Limit Color Yellow, (T1_TTKOT3 + T1_TTRXB)
Dynamic Trip Limit Color Red, (T1_TTKOT1 MIN (T1_TTRXB+T1_TTKOT2))
Table 6.3: Exhaust Temperatures
Parameter

Point Name

Exhaust Temp # X

T1_TTXD_X

Normal Fill
Color
0,195,198

Color Animation
Switch
T1_TTXD1_X GE
(T1_TTKOTX +
T1_TTRXB)

Animated
Color
Yellow

(T1_TTXD1_X GE
(T1_TTRXB +
T1_TTKOT2)) OR
(T1_TTXD1_X GE
T1_TTKOT1)

Red

HMI Turbine Screen Standards

44

Example:
Exhaust Temp # 3

T1_TTXD1_3 GE
(T1_TTKOT3 +
T1_TTRXB)

Yellow

(T1_TTXD1_3 GE
(T1_TTRXB +
T1_TTKOT2)) OR
(T1_TTXD1_3 GE
T1_TTKOT1)

Red

HMI Turbine Screen Standards

45

6.4 Generator RTD Temperatures

The color animation for the Generator RTD Temperatures is shown in Table 6.4. The
temperature range is 0-300 deg F.
The Dynamic Alarm Limit Pointer (Yellow) is provided by the controller e.g. for T1_DTGSF1 the
pointer value is given by the controller constant DTKGSF.
Table 6.4 Generator RTD Temperatures
Parameter

Point Name

Stator Coupling
End #1
Stator Coupling
End #2
Stator Coupling
End #3
Stator Collector
End #1
Stator Collector
End #2
Stator Collector
End #3
Stator Coupling
End #1
Stator Coupling
End #2

T1_DTGSF1

Normal Fill
Color
0,195,198

T1_DTGSF2

0,195,198

T1_DTGSF3

0,195,198

T1_DTGSA4

0,195,198

T1_DTGSA5

0,195,198

T1_DTGSA6

0,195,198

T1_DTGSC7

0,195,198

T1_DTGSC8

0,195,198

Color Animation
Switch
(T1_DTGSF1 GE
T1_DTKGSF)
(T1_DTGSF2 GE
T1_DTKGSF)
(T1_DTGSF3 GE
T1_DTKGSF)
(T1_DTGSA4 GE
T1_DTKGSA)
(T1_DTGSA5 GE
T1_DTKGSA)
(T1_DTGSA6 GE
T1_DTKGSA)
(T1_DTGSC7 GE
T1_TGKSFA)
(T1_DTGSC8 GE
T1_TGKSFA)

HMI Turbine Screen Standards

Animated
Color
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow

46

Cold Gas
Coupling End #1
Cold Gas
Collector End #1
Cold Gas
Collector End #1
Cold Gas
Collector End #2
Cold Gas
Collector End #3
Hot Air Coupling
End #1
Hot Air Coupling
End #2
Hot Air Collector
End #1
Hot Air Collector
End #2
Frame Cold Gas

T1_DTGSC9

0,195,198

T1_DTGGC1
0
T1_DTGGC1
3
T1_DTGGC1
1
T1_DTGGC1
2
T1_DTGGH2
8
T1_DTGGH2
9
T1_DTGGAC
23
T1_DTGGAH
17
T1_DTGGK2
4

0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198

(T1_DTGSC9 GE
T1_TGKSFA)
(T1_DTGGC10 GT
T1_TGKGCA)
(T1_DTGGC13 GT
T1_TGKGCA)
(T1_DTGGC11 GT
T1_TGKGCA)
(T1_DTGGC12 GT
T1_TGKGCA)
(T1_DTGGH28 GT
T1_TGKGHA)
(T1_DTGGH29 GT
T1_TGKGHA)
(T1_DTGAC23 GE
T1_TGKGCA)
(T1_DTGAH17 GE
T1_TGKGHA)
(T1_DTGGK24 GT
T1_DTKGGK)

HMI Turbine Screen Standards

Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow

47

6.5 Vibration Proximeters

The color animation for the Vibration Proximeters is shown in Table 6.5. The vibration range is
0-10 ins/sec.
Table 6.5: Vibration Proximeters
Parameter
Axial Position Z1
Axial Position Z2
Turbine Bearings 1X
Turbine Bearings 1Y
Turbine Bearings 2X
Turbine Bearings 2Y
Generator Bearings 3X
Generator Bearings 3Y
Generator Bearings 4X
Generator Bearings 4Y

Point Name
T1_TVT96VS1Z1
T1_TVT96VS1Z2
T1_TVT39VS1X
T1_TVT39VS1Y
T1_TVT39VS2X
T1_TVT39VS2Y
T1_TVT39VS9X
T1_TVT39VS9Y
T1_TVT39VS10X
T1_TVT39VS10Y

Normal Fill Color


0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198
0,195,198

HMI Turbine Screen Standards

48

6.6 Seismic Vibration

The color animation for Seismic Vibration is shown in Table 6.6. The range is 0-1.2 ins/sec.
The dynamic alarm pointer (Yellow) and the dynamic trip pointer is (Red) are provided by the
controller e.g. for T1_BB1 the alarm pointer value is given by the controller constant
T1_LK39VA1 and the trip pointer by T1_LK39VT1.

Table 6.6 Seismic Vibration


Parameter
Turbine Forward
#1

Turbine Forward
#2

Turbine Aft #1

Point
Name
T1_BB1

T1_BB2

T1_BB4

Normal
Fill Color
0,195,198

0,195,198

0,195,198

Color Animation Switch


(T1_BB1 GE
T1_LK39VA1) AND
(T1_BB1 LT
T1_LK39VT1)

Animated
Color
Yellow

(T1_BB1 GT
T1_LK39VT1)
(T1_BB2 GE
T1_LK39VA2) AND
(T1_BB2 LT
T1_LK39VT2)

Red

T1_BB2 GE
T1_LK39VT2
(T1_BB4 GE
T1_LK39VA4) AND
(T1_BB4 LT
T1_LK39VT4)

Red

(T1_BB4 GE
T1_LK39VT4)

Red

HMI Turbine Screen Standards

Yellow

Yellow

49

Turbine Aft #2

Generator Aft #1

Generator Aft #2

Generator
Forward #1

Generator
Forward #2

T1_BB5

T1_BB7

T1_BB8

T1_BB9

T1_BB10

0,195,198

0,195,198

0,195,198

0,195,198

0,195,198

(T1_BB5 GE
T1_LK39VA5) AND
(T1_BB5 LT
T1_LK39VT5)

Yellow

(T1_BB5 GE
T1_LK39VT5)
(T1_BB7 GE
T1_LK39VA7) AND
(T1_BB7 LT
T1_LK39VT7)

Red

(T1_BB7 GE
T1_LK39VT7)
(T1_BB8 GE
T1_LK39VA8) AND
(T1_BB8 LT
T1_LK39VT8)

Red

(T1_BB8 GE
T1_LK39VT8)
(T1_BB9 GE
T1_LK39VA9) AND
(T1_BB9 LT
T1_LK39VT9)

Red

(T1_BB9 GE
T1_LK39VT9)
(T1_BB10 GE
T1_LK39VA10) AND
(T1_BB10 LT
T1_LK39VT10)

Red

(T1_BB10 GE
T1_LK39VT10)

Red

HMI Turbine Screen Standards

Yellow

Yellow

Yellow

Yellow

50

6.7 Wheelspace Temperatures

The color animation for the Wheelspace Temperatures is shown in Table 6.7. The range is 0900 deg F.
Table 6.7 Wheelspace Temperatures
Parameter

Point Name

First Stage
Forward Inner #1

T1_TTWS1FI
1

First Stage
Forward Inner #2

First Stage Aft


Outer #1

First Stage Aft


Outer #2

T1_TTWS1FI
2

T1_TTWS1A
O1

T1_TTWS1A
O2

Normal Fill
Color
0,195,198

0,195,198

0,195,198

0,195,198

Color Animation
Switch
(T1_L3 EQ 1) AND
(T1_TTWS1FI1 GE
T1_WSKALM1)

Animated
Color
Yellow

(T1_L3 EQ 0) AND
(T1_TTWS1FI1 GE
(T1_WSKALM1+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS1FI2 GE
T1_WSKALM1))

Yellow

(T1_L3 EQ 0) AND
(T1_ TTWS1FI2 GE
(T1_WSKALM3+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS1AO1 GE
T1_WSKALM3)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS1AO1 GE
(T1_WSKALM3+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS2FO1 GE
T1_WSKALM4)

Yellow

(T1_L3 EQ 0) AND

Yellow

HMI Turbine Screen Standards

Yellow

Yellow

Yellow

51

Second Stage
Forward Inner #1

Second Stage
Forward Inner #2

Second Stage Aft


Outer #1

Second Stage Aft


Outer #2

Third Stage
Forward Inner #1

Third Stage
Forward Inner #2

T1_TTWS2F
O1

T1_TTWS2F
O2

T1_TTWS2A
O1

T1_TTWS2A
O2

T1_TTWS3F
O1

T1_TTWS3F
O2

0,195,198

0,195,198

0,195,198

0,195,198

0,195,198

0,195,198

(T1_TTWS2FO1 GE
(T1_WSKALM4+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS2FO1 GE
T1_WSKALM4)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS2FO1 GE
(T1_WSKALM4+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS2FO2 GE
T1_WSKALM4)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS2FO2 GE
(T1_WSKALM4+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS2AO1 GE
T1_WSKALM5)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS2AO1 GE
(T1_WSKALM5+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS2AO2 GE
T1_WSKALM5)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS2AO2 GE
(T1_WSKALM5+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS3FO1 GE
T1_WSKALM6)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS3FO1 GE
(T1_WSKALM6+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS3FO2 GE
T1_WSKALM6)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS3FO2 GE
(T1_WSKALM6+T1_
WSKALM9))

Yellow

HMI Turbine Screen Standards

Yellow

Yellow

Yellow

Yellow

Yellow

52

Third Stage Aft


Outer #1

Third Stage Aft


Outer #2

T1_TTWS3A
O1

T1_TTWS3A
O2

0,195,198

0,195,198

(T1_L3 EQ 1) AND
(T1_TTWS3AO1 GE
T1_WSKALM7)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS3AO1 GE
(T1_WSKALM7+T1_
WSKALM9))
(T1_L3 EQ 1) AND
(T1_TTWS3AO2 GE
T1_WSKALM7)

Yellow

(T1_L3 EQ 0) AND
(T1_TTWS3AO2 GE
(T1_WSKALM7+T1_
WSKALM9))

Yellow

HMI Turbine Screen Standards

Yellow

53

6.8 Flame Temperatures

The color animation for the Flame Temperatures is shown in Table 6.8. The range is 1200
counts.
Table 6.8 Flame Temperatures
Parameter

Point Name

Flame
Detector #1
Flame
Detector #2
Flame
Detector #3
Flame
Detector #4

T1_FD_INTEN
S1
T1_FD_INTEN
S2
T1_FD_INTEN
S3
T1_FD_INTEN
S4

Normal Fill
Color
0,195,198

Color Animation
Switch
Non

0,195,198

Non

0,195,198

Non

0,195,198

Non

HMI Turbine Screen Standards

Color

54

7.0 Graphic Symbols and Animation Dynamics


All Symbols will change color according to the following. When the color changes the entire
symbol 'fill color' will change unless otherwise specified. Graphic Symbols will be placed in a
Cimview screen to form a Symbol Library.

7.1 Fuel Lines

Gas Line

Color, Olive (128, 128, 0)


Width, 2pts
Visibility IF L83FGI eq 1 or L83FM eq 1

Liquid Line

Color, Olive (128, 128, 0)


Width, 2pts
Visibility IF L84TL eq 1 or L84MXT eq 1

Steam Line

Color, Maroon
Width, 2pts

Control Valves
Gas Line

SRV Valve
Color Animation:Inactive Color Green
Active - Red
SRV Line
Color Animation:Inactive - Gradient Color1 Green
Color2 - Lime
Active - Gradient Red
(IF FSGR gt 1)
Control Valve
Color Animation:Inactive Color Green
Active - Red
Control Line
Color Animation:Inactive - Gradient Color1 Green
Color2 - Lime
Active - Gradient Red
(IF FSGR gt 1)

HMI Turbine Screen Standards

55

Control Valves
Liquid Line

LCV Valve
Color Animation:Inactive Color Green
Active - Red
LCV Line
Color Animation:Inactive - Gradient Color1 Green
Color2 - Lime
Active - Gradient Red
(IF FQROUT gt 1)

Control Valves
Steam Line

LCV Valve
Color Animation:Inactive Color Green
Active - Red
LCV Line
Color Animation:Inactive - Gradient Color1 Green
Color2 - Lime
Active - Gradient Red
(IF L33CJ1C eq 0)

7.2 Gas Turbine

The gas turbine graphics have been developed using the BOLT
standard as a template. To the template, Modulating IGVs, Generator
Breaker and Bleed Heat have been added.
Gas Turbine
Graphics

Modulating IGVs

Color Animation
Inactive, Gray (Gradient Shading), VALID LT 1
Active, Compressor,
Green (Gradient Shading)
Combustor,
Red (Gradient Shading)
Hot Section,
Yellow (Gradient shading)
Flame Color Gradient Color1 222,130,0
Color2 Yellow
External Edge, Black, Width 2 pt
Fill Color, Gradient Shading Vertical
Color 1, Silver
Color 2, White
Internal Border Color, 132, 255, 255
HMI Turbine Screen Standards
56

Bleed Heat

Generator Breaker

Color Animation Active, Line Color 0, 195, 198,


Rectangle Color Red
Inactive, Line Color Black,
Rectangle Color Green
Geometry
Line, Width 2pt
Internal Rectangle, Width 12.5 pt, Height 2.8 pt
External Rectangle, Width 27.2 pt, Height 6.6 pt

.Color Animation, Breaker Open Green


Breaker Closed Red
Geometry,

Lines, Width 20 pt, Height 0 pt


Circles, Diameter 9pt
Black Circle, Width 1pt

Buttons,

Color, Silver
Text Color, Black
Font, Arial 11
Geometry, Width, 30 pts, Height 20 pts

7.3 DLN 2.6 Piping & Valving Graphic


The properties for the DLN 2.6 piping and valving graphic are shown below

HMI Turbine Screen Standards

57

Piping

PM1 Valve

Color, Gradient Shading


Color 1, Olive
Color 2, 255, 255, 198
External Border, Black, Width 0 pt

Control Valve
The control valve consists of series of objects with the following
colors and geometry.
1. Color, Black (Fill)
;Geometry Width 32.3 pts, Height 11.45 pts
2. Color, Black (Rectangle); Geometry Width 32.3 pts, Height 11.45
pts, Width 0 pts.
3. Color, Gradient Shading from Center
Color 1, 234, 190, 15
Color 2, 255, 255, 198
External Border, Black, Width 0 pt
Geometry, Width, 32.25 pt, Height, 11.45
4. Color, Black (Rectangle); Geometry Width 32.3 pts, Height 11.45
pts, Width 0 pts
Valve Orifice
The valve orifice consists of a series of objects with the following
colors and geometry.
1. Color, 127,127,127 ; Geometry Width 39 pts, Height 17.95 pts
2. Color, 153,153,153 ; Geometry Width 39 pts, Height 16 pts
3. Color, 178,178,178 ; Geometry Width 39 pts, Height 12.4 pts
4. Color, 204,204,204 ; Geometry Width 39 pts, Height 8.6 pts
5. Color, 299,299,299 ; Geometry Width 39 pts, Height 5.95 pts
6. Color, White
; Geometry Width 39 pts, Height 2.3 pts
7. Gradient Shading ; Geometry Width 39 pts, Height 17.95 pts
Color 1, 66, 65, 66
Color 2, White
Valve Stem
The valve orifice consists of a series of objects with the following
colors and geometry.
1. Color, 127,127,127 ; Geometry Width 2.85 pts, Height 11.6 pts
2. Color, 178,178,178 ; Geometry Width 2.15 pts, Height 11.6 pts
3. Color, 299,299,299 ; Geometry Width 1.5 pts, Height 11.6 pts
4. Color, White
; Geometry Width 0.45pts, Height 11.6 pts
5. Color, Black
; Geometry Width 0 pts, Height 11.6 pts
6. Color, Black
; Geometry Width 0 pts, Height 11.6 pts
Font
Arial, Bold, 12 pt

The remaining control valves PM2, PM3, the Quaternary Valve, Vent Valve and the SRV
valve are identical in design to the PM1 with the control valve shaded as follows:

HMI Turbine Screen Standards

58

7.4 DLN 2.6 Nozzle Graphic


PM2 Valve

Control Valve
Color, Gradient Shading from Center
Color 1, 247,27,2
Color 2, White

PM3 Valve

Control Valve
Color, Gradient Shading from Center
Color 1, 56, 192,114
Color 2, White

Quaternary Valve

Control Valve
Color, Gradient Shading from Center
Color 1, Color 1, 77, 124, 172
Color 2, Color 2, White

Vent & SRV Valves

Control Valve
Color, Gradient Shading from Center
Color 1, 127, 127, 127
Color 2, White

Outer Circle

Geometry, Width 240 pts, Height 240pts.


Color, External border, White, Width 0 pts
Fill Color, Gradient Shading from Center
Color 1, 66,65,66
Color 2, White
HMI Turbine Screen Standards

59

Quaternary Circle

Geometry, Width 220 pts, Height 220pts.


Color, External border, White, Width 0 pts
Fill Color, Gradient Shading from Center
Color 1, 77, 124, 172
Color 2, 231, 227, 231

Quaternary Animation

Geometry, Width 185 pts, Height 185 pts.


Color, External border, Black, Width 0.5 pts
Fill Color, Black
Color Animation
Fill Color, Red (L30QGCV & L28FDX eq 1)

Inner Circle

Geometry, Width 165 pts, Height 165 pts.


Color, External border, White, Width 1 pts
Fill Color, Gradient from Center
Color Animation
Fill Color, Red (L30QGCV & L28FDX eq 1)

Quaternary Text

White, Arial, Regular 12

PM3 On

Geometry, Width 50 pts, Height 50 pts


Color, External border, Black, Width 0.5 pts
Fill Color, Black
Color Animation
Fill Color, Red (L30PM3_C & L28FDX eq 1)

PM3 Off

Geometry, Width 34 pts, Height 34 pts


Color, External border, Black, Width 0.5 pts
Fill Color, Gradient Shading from Center
Color 1, 56,192,114
Color 2, 198,255,255
Text, Arial 11, Bold, Alignment Center\Center

PM2 On

Geometry, Width 50 pts, Height 50 pts


Color, External border, Black, Width 0.5 pts
Fill Color, Black
Color Animation
Fill Color, Red (L30PM2_C & L28FDX eq 1)

PM2 Off

Geometry, Width 34 pts, Height 34 pts


Color, External border, Black, Width 0.5 pts
Fill Color, Gradient Shading from Center
Color 1, 56,192,114
Color 2, 198,255,255
Text, Arial 11, Bold, Alignment Center\Center

HMI Turbine Screen Standards

60

PM1 On

Geometry, Width 50 pts, Height 50 pts


Color, External border, Black, Width 0.5 pts
Fill Color, Black
Color Animation
Fill Color, Red (L30PM1_C & L28FDX eq 1)

PM1 Off

Geometry, Width 34 pts, Height 34 pts


Color, External border, Black, Width 0.5 pts
Fill Color, Gradient Shading from Center
Color 1, 234, 190, 15
Color 2, 255, 227,198
Text, Arial 11, Bold, Alignment Center\Center

HMI Turbine Screen Standards

61

7.5 Exhaust Thermocouple Graphics


An Upstream schematic of the Exhaust thermocouples for a 7FA machine is shown below.

Heading

Black, Arial, Regular 10, Alignment Left\Top

Point Description

Black, Arial, Bold 8, Alignment Center\Top


Color Animation
Color 1, Navy, L30TXA eq 0 & L86TXT eq 0
Color 2, Yellow, L30TXA eq 1 & L86TXT eq 0
Color 3, Red, L86TXT eq 1

Lines

Black, Width 2 pts

Outer Circle

Geometry, Width 148 pt, Height 148 pt


Black, Width 2 pts
Fill Color, Gradient from Center
Single Color, Olive

Burners

Geometry, Width 17.8 pt, Height 17.8 pt


Color 66,65, 66, Width 0.5 pt
Text, Black, Arial, Bold 14 pt
Fill Color, Gradient from Center
Single Color, 66,65,0
Color Animation
Gradient, L28FDX eq 1
Color 1, 255, 255, 132
Color 2, 255, 130, 0

Inner Circle 1

Geometry, Width 72 pt, Height 72 pt


Color Black, Width 2 pt
Fill Color, Pattern
Color, Teal
Pattern Color, White
HMI Turbine Screen Standards

62

Inner Circle 2

Geometry, Width 58 pt, Height 58 pt


Color Black, Width 2 pt
Fill Color, Gradient from center
Color 1, Gray
Color 2, 231, 227, 231

Inner Circle 3

Geometry, Width 25 pt, Height 25 pt


Color Black, Width 2 pt
Fill Color, Gradient Horizontal
Color 1, Silver
Color 2, White

Center

Geometry, Width 14 pt, Height 14 pt


Color Black, Width 2 pt
Fill Color, Pattern
Color 1, Maroon
Color 2, White

HMI Turbine Screen Standards

63

8.0 Start Check Screen


Start Check 0

Bus Undervoltage
L27BN or L27BN
Comp Inlet Thermocouples Disagree
L86TCI
Gas Fuel or IGV Control Valve Fault
L3VLVFLT
Customer Permissive to Start
L3CP
Spare
SPARE
Spare
SPARE
Spare
SPARE

NOT
READY T O START

The Start Check Screen provides a list of


signals which all must be in the proper
state GREEN to permit a start. Therefore,
a green signal is required to start the unit.
If signals are RED then a start request is
inhibited.

When a RED signal is present then


the text in the Data Box turns red and
the NOT READY TO STARTsignal
is displayed. When all signals are
green then the Data Box displays the
READY TO STARTsignal in green.

READY TO START

Start Check Buttons

Geometry, Width 220 pts, Height 27 pts


Color Animation
Fill Color, Lime L3TCK0 eq 1
Fill Color, Red L3TCK0 eq 0
Text, Black, Arial, Bold 11

Data Boxes

Geometry, Width 220 pts, Height 27 pts


Color Animation
Normal Fill Color, Red
Fill Color, Lime
Text, Black, Arial Regular 12, Alignment Center\ Bottom
Shading, two white lines placed on the bottom and on
the right are used to provide a shadowed look to this
object. These boxes are vertically aligned and spaced
2 pts apart.

HMI Turbine Screen Standards

64

The start permissives for a maximum case 7FA machine are listed in the table below.
Point Description

Point Name

Normal
Color

Color Animation
Switch

Animated
Color

Start Check 0
Bus UnderVoltage

T1_L27BN

Red

Lime

T1_L86TCI

Red

T1_L27BN Eq 1 or
T1_L27BZ eq 1
T1_L86TCI eq 0

T1_L3VLVFLT

Red

T1_L3VLVFLT eq 0

Lime

T1_L3CP

Red

T1_L3CP eq 1

Lime

T1_L26QN

Red

T1_L26QN eq 1

Lime

T1_L28FDSCK
T1_L430
T1_L86HD

Red
Red
Red

T1_L28FDSCK eq 1
T1_L430 eq 0
T1_L86HD eq 0

Lime
Lime
Lime

T1_L52GX

Red

T1_L52GX eq 0

Lime

T1_L3SS_RS

Red

T1_L3SS_RS eq 1

Lime

T1_L30EX_SS

Red

T1_L30EX_SS eq 0

Lime

T1_L86CBA

Red
Red

T1_L86CBA eq 0

Lime
Lime

T1_L4Y

Red

T1_L4Y eq 1

Lime

T1_L38BHSTCK

Red

Lime

T1_L3STCK_HGE
N
T1_L94SSX
T1_L4INHIBIT_ST

Red

T1_L86MP

Red

T1_L38BHSTCK
eq 1
T1_L3STCK_HGEN eq
1
T1_L94SSX eq 0
T1_L4INHIBIT_ST
eq 0
T1_L86MP eq 0

T1_L4T

Red

T1_L4T eq 0

Lime

T1_L43DIAG
T1_L39VD3
T1_L3TFLT
T1_L14HM

Red
Red
Red
Red

T1_L43DIAG eq 0
T1_L39VD3 eq 0
T1_L3TFLT eq 0
T1_L14HM eq 0

Lime
Lime
Lime
Lime

Compressor Inlet
Thermocouples
Disagree
Gas Fuel or IGV Control
Valve Fault
Start Check 1
Customer Permissive to
Start
Lube Oil Tank Temp Normal
Flame Detector Trouble
Control Mode = OFF
Hydraulic Protective
Trouble
Generator Breaker
Closed
LCI(Static Start)
Ready to Start
EX2000 Status S
Exciter Alarm
Start Check 2
Compressor Bleed
Valve or IGV Pos.
Lockout
Loss of Master
Protective
Compressor Operating
Limit BH Start Check
Hydrogen Start Check
Static Starter Shutdown
Static Start Inhibited
from other unit
Master Protective
Startup Trip
Start Check 3
Loss of Master
Protective
Off-Line Diagnostics
Vibration Start Inhibit
Loss of CDP Bias
HP Speed Minimum
Firing Speed

Red
Red

HMI Turbine Screen Standards

Lime

Lime
Lime
Lime
Lime

65

Start Check AA
20AA System Start
Check enable
Upstream AA Hi/Lo
Position Fault
20AA Position
Feedback Fault
Downstream AA Hi/Lo
Position Fault

T1_L3STAA_ENB

Red

T1_L3STAA_ENB eq 0

Lime

T1_L30AA1PO_A
LM
T1_L30AAFB_AL
M
T1_L30AA2PO_A
LM

Red

T1_L30AA1PO_ALM
eq 0
T1_L30AAFB_ALM eq
0
T1_L30AA2PO_ALM
eq 0

Lime

Red
Red

Lime
Lime

9.0 Trip Screen


The Trip screen provides a list of Protective
trips for the 7FA. The trips are normally
GREEN and turn RED when activated.
Some signals are not latched, so the data
logger must be checked for an accurate
chain of events, leading to any highlighted
trips that may appear on the display.

M aster Protective Trip

Protective Status Trip


L4PST
Pre-Ignition Trip
L4PRET
Post-Ignition Trip
L4POST
Starting Device Trip
L3SMT
Inlet Guide Vane Control Trouble Trip
L4IGVT
TCEA 5E/PB Circuit Status
L5E_TCEA

A list of the protective trips for a maximum case 7FA is shown in the table below.
Point Description
Master Protective Trip
Protective Status Trip
Pre-Ignition Trip
Post-Ignition Trip
Starting Device Trip
Inlet Guide Vane
Control Trouble Trip
TCEA 5E/PB Circuit
Status
Protective Check 1
Low Lube Oil Pressure
Trip
Fire Indication Trip
Generator Differential
Trip Lockout

Point Name

Normal
Color

Color Animation
Switch

Animated
Color

T1_L4PST
T1_L4PRET
T1_L4POST
T1_L3SMT
T1_ L4IGVT

Lime
Lime
Lime
Lime
Lime

T1_L4PST eq 1
T1_L4PRET eq 0
T1_L4POST eq 0
T1_L3SMT eq 0
T1_ L4IGVT eq 0

Red
Red
Red
Red
Red

T1_L5E_TCEA

Lime

T1_L5E_TCEA eq 0

Red

T1_L63QTX

Lime

T1_L63QTX eq 0

Red

T1_L45FTX
T1_L86TGT

Lime
Lime

T1_L45FTX eq 0
T1_L86TGT eq 0

Red
Red

HMI Turbine Screen Standards

66

TCEA External Trip


Transfer Differential Trip
Lockout
Exhaust Pressure High
Trip
Protective Check 2
Vibration Trip
Startup Fuel Flow
Excessive Trip
Loss of Protective HP
Speed Inputs
Customer Trip Input
Protective Check 3
Control Speed Signal
Lost - HP
Protective Speed Signal
Trouble
Control Speed Signal
Trouble
GCV Not Following
Reference Trip
Secondary GCV Not
Following Ref Trip
Quaternary GCV Not
Following Ref Trip
PM3 GCV Not Following
Reference Trip
Protective Check 4
Control System Fault
Trip
Pre-Ignition Trip
Auxiliary Check
(Servos)
Pre-Ignition Trip
Auxiliary Logic
Post-Ignition Trip
Post Ignition Trip
Auxiliary
Loss of Flame trip
High Exhaust
Temperature trip
Exhaust
Overtemperature trip
Compressor Bleed
Valve Pos. Trouble Trip
Load Tunnel
Temperature High - Trip

T1_L4_RLYT
T1_L86TT

Lime
Lime

T1_L4_RLYT eq 0
T1_L86TT eq 0

Red
Red

T1_ L63ETH

Lime

T1_ L63ETH eq 0

Red

T1_L39VTRIP
T1_L2SFT

Lime
Lime

T1_L39VTRIP EQ 0
T1_L2SFT EQ 0

Red
Red

T1_L12H_FLT

Lime

T1_L12H_FLT EQ 0

Red

T1_L4CT

Lime

T1_L4CT EQ 0

Red

T1_L12HF

Lime

T1_L12HF EQ 0

Red

T1_L12HFD

Lime

T1_L12HFD_P EQ 0

Red

T1_L12HFD_C

Lime

T1_L12HFD_C EQ 0

Red

T1_L86GCVT

Lime

T1_L86GCVT EQ 0

Red

T1_L86GCVST

Lime

T1_L86GCVST EQ 0

Red

T1_L86GCVQT

Lime

T1_L86GCVQT EQ 0

Red

T1_L86GCV3T

Lime

T1_L86GCV3T EQ 0

Red

T1_L3SFLT

Lime

T1_L3SFLT EQ 0

Red

T1_L3ACS

Lime

T1_L3ACS EQ 1

Red

T1_L4PRETX

Lime

T1_L4PRETX EQ 0

Red

T1_L4POSTX

Lime

T1_L4POSTX EQ 0

Red

T1_L28FDT
T1_L30SPT

Lime
Lime

T1_L28FDT EQ 0
T1_L30SPT EQ 0

Red
Red

T1_L86TXT

Lime

T1_L86TXT EQ 0

Red

T1_L86CBT

Lime

T1_L86CBT EQ 0

Red

T1_L30LTT

Lime

T1_L30LTT EQ 0

Red

HMI Turbine Screen Standards

67

10.0 Liquid Fuel Delivery System


The liquid fuel screen comprises of the liquid fuel delivery system, the purge air system and
piping for water injection. The components, pumps, valves are obtained from the Bolt
Standards and are constructed from a large number of individual objects, as a result detailed
descriptions of component geometrys are not provided.

10.1 Liquid Fuel Delivery

Piping

Geometry, Pipe Width 7pts


Border Color, Black 0 pt
Color, Gradient shading
Color 1, Olive
Color 2, 198, 195, 0
Note: direction of shading is consistent with
direction of pipe.

Pumps

Pump body
Fill Color, Gradient Shading from Center
Color 1, Gray
Color 2, 231, 227, 231
Text, Black, Arial Bold 12

Liquid Control Valve

The liquid control valve is color animated to show the


state of the reference and feedback signals.
Fill Color, Red, from Left
Range: 0, 100 Units: Percent
Text, Black, Arial Bold 12
HMI Turbine Screen Standards

68

Stop Valve Solenoid

The text in the Stop Valve Solenoid is color animated


Text: Valve Open, Text Openwith color Red
Valve Closed,Text Closedwith color Lime

Check Valve

Object Color, Gradient Shading Diagonal Up


Color 1, Yellow
Color 2, 255, 255, 210

Round Light
Border Color, Black 2 pts,
Geometry, Width 19.6 pts, Height 20 pts
Line Color, White
Geometry, Width 8.15 pts, Height 6.25 pt
The object is color animated
Object Color, Olive.
Animated Color, Yellow
based on {Point_to_Change_Color} variable
Flame

External Border, Black 1 Pt


Fill Color, Gradient Horizontal
Color 1, Olive
Color 2, 255, 255, 198
Internal Border, Aqua 1 Pt
Fill Color, Black
Flame, color animated
Normal Color, Black, T1_L28FDX eq 0
Animated Color, Gradient, Vertical, T1_L28FDX eq 1
Color 1, 198, 65, 0
Color 2, Yellow
Water Injection, Visibility is set by T1_L30WATERON eq 1.0
Fill Color, Aqua, gradient from center

HMI Turbine Screen Standards

69

10.2 Purge Air System

Piping

Geometry, Pipe Width 7pts


Border Color, Black 0 pt
Color, Gradient shading
Color 1, Green
Color 2, 198, 225, 198
Note: direction of shading is consistent with direction of
pipe.

Purge\ Isolation Valve

The text in the Stop Valve Solenoid is color animated


Text: Valve Open, Text Openwith color Red
Valve Closed,Text Closedwith color Lime

HMI Turbine Screen Standards

70

11.0 Water Injection System


The water injection screen comprises of the water injection delivery system and the
purge air system. The components, pumps, valves are obtained from the Bolt
Standards and are constructed from a large number of individual objects, as a result
detailed descriptions of component geometrys are not provided.

Pumps

Pump body
Fill Color, Gradient Shading from Center
Color 1, Gray
Color 2, 231, 227, 231
Text, Black, Arial Bold 12

Piping
(Water Injection)

Geometry, Pipe Width 7pts


Border Color, Black 0 pt
Color, Gradient shading
Color 1, Olive
Color 2, 198, 195, 0
Note: direction of shading is consistent with
direction of pipe.

Piping
(Purge Air System)

Geometry, Pipe Width 7pts


Border Color, Black 0 pt
Color, Gradient shading
Color 1, Green
Color 2, 198, 255, 198
Note: direction of shading is consistent with
direction of pipe.

Check Valve

Object Color, Gradient Shading Diagonal Up


Color 1, Yellow
Color 2, 255, 255, 210
HMI Turbine Screen Standards

71

Stop Valve\ Isolation Valve

The stop valve is color animated for open and closed


states
Open, Color Red,
T1_L33WP1O eq 1
Closed, Color 0,195,0 T1_L20WP1C eq 1
Text, Black Arial bold 11

Text

Text, Black Arial bold 11

Data_Boxes

Height - 16 pts
Widths divisible by 10 pts.
Two white lines placed on the bottom and on the right
are used to provide a shadowed look to this object.
These boxes are vertically aligned and spaced 3 pts
apart. Text is bottom aligned in the box

Data

Data feedback using point ID.


Text Color - Black, Numerical using Lucida Sans Unicode
11pt, with a right/center anchor and Text using Arial 11pt,
with left center text anchor.

Water Injection

External Border, Black 1 Pt


Fill Color, Gradient Horizontal
Color 1, Olive
Color 2, 255, 255, 198
Internal Border, Aqua 1 Pt
Fill Color, Black
Flames, have four modes of color animation
Mode 1, T1_L28FDX eq 1 NOT T1_L84TG eq 1
Line, Gray 0.5 pt
Fill, Gradient
Color 1, Yellow
Color 2, 198, 65, 0
Mode 2, T1_L28FDX eq 0 or
Mode 3, T1_L28FDX eq 1 T1_L84TG eq 1
Line, None
Fill, None
Mode 4, 1
Color 2, Yellow
Line, None
Fill Color, Yellow

HMI Turbine Screen Standards

72

The components, pumps, valves are obtained from the Bolt Standards and are constructed
from a large number of individual objects, as a result detailed descriptions of component
geometrys are not provided.

Water Injector

The water injector is constructed from 4 individual objects


Object 1, Geometry Width 7.75 pt, Height 6.4 pt
Fill Color Black, Gradient to Corner
Object 2, Geometry Width 3.9 pt, Height 9.7 pt
Fill Color 215, 215, 215 Gradient Vertical
Object 3, Geometry Width 7.75 pt, Height 9.7 pt
Fill Color 114, 114, 114 Gradient Vertical
Object 4, Geometry Width 7.75 pt, Height 6.4 pt
Fill Color 97,97,97, Gradient to Corner

Water Spray

The water spray consists of two sets of identical objects.


Each object consisting of 4 lines Color Aqua, Width 0.5 pts
Geometry
Line 1, Width 18.65 pts, Height 8.7 pts
Line 2, Width 17 pts,
Height 12.3 pts
Line 3, Width 14.75 pts, Height 14.7 pts
Line 4, Width 11.15 pts, Height 15.75 pts

12.0 Steam Power Augmentation System

HMI Turbine Screen Standards

73

The steam injection schematic shows the steam system, fuel delivery system and
purge air system (in green, not fully shown). The valves are obtained from the Bolt
Standards and are constructed from a large number of individual objects, as a
result detailed descriptions of component geometries are not provided.

Piping

Geometry, Pipe Width 7pts


Border Color, Black 0 pt
Color, Gradient shading
Color 1, Red
Color 2, 255, 130, 132
Note: direction of shading is consistent with direction
of pipe.

Stop Valve
Header Text, Black Arial bold 12
The text in the Control Valve is color animated
Text: Valve Open, Text Openwith color Red
Valve Closed,Text Closedwith color Lime
Valve is color animated for open and closed states
Open, Gradient Shading,
T1_L33PL2O eq 1
Color 1, Red
Color 2, 255, 227, 198
Closed, Gradient Shading, T1_L33PL2O eq 0
Color 1, 0, 195, 0
Color 2, 198, 255, 198

Status Indicator

Steam Valves

The text in the Status Indicator is color animated


Text: Valve Open, Text Openwith color Red
Valve Closed,Text Closedwith color Lime

Header Text, Black Arial bold 12


Control Valve uses Gradient Shading
Color 1, 56, 192, 114
Color 2, White
Valve Orifice is color animated for open and closed states
Open, Gradient Shading,
T1_L30PM3_C eq 0
Color 1, Red
Color 2, 255, 195, 198
Closed, Gradient Shading,
T1_L30PM3_C eq 1
Color 1, Green
Color 2, 198, 255, 198

HMI Turbine Screen Standards

74

Steam Injector

Steam

The Steam injector is identical to the water injector and


constructed from 4 individual objects.
Object 1, Geometry Width 7.75 pt, Height 6.4 pt
Fill Color Black, Gradient to Corner
Object 2, Geometry Width 3.9 pt, Height 9.7 pt
Fill Color 215, 215, 215 Gradient Vertical
Object 3, Geometry Width 7.75 pt, Height 9.7 pt
Fill Color 114, 114, 114 Gradient Vertical
Object 4, Geometry Width 7.75 pt, Height 6.4 pt
Fill Color 97,97,97, Gradient to Corner

The steam object consist of 8 lines Color Aqua, Width 0 pts


Geometry
Line 1, Width 12.8 pts, Height 13.75 pts
Line 2, Width 12.8 pts, Height 11 pts
Line 3, Width 12.8 pts, Height 8.25 pts
Line 4, Width 12.8 pts, Height 5.5 pts
Line 5, Width 12.85 pts, Height 5.5 pts
Line 6, Width 12.85 pts, Height 8.25 pts
Line 7, Width 12.85 pts, Height 11 pts
Line 8, Width 12.85 pts, Height 13.75 pts

HMI Turbine Screen Standards

75

13.0 Frame Animation

HMI Turbine Screen Standards

76

14.0 Multi-Unit Configuration


14.1 Overview
CIMPLICITY design standards are directly applicable to multi-unit applications. A single set of
screens is used for a multi-unit system using pushbuttons on the Foundation screen for
navigation between units. Data for individual units is obtained is by setting the screen
variables UNIT, UNIT_NAME and UNIT_NO.
In a multi-unit system a CIMPLICITY server can access its own data and can act as a viewer
for a maximum of two other computers. The screen variable LOCAL_PROJECT is used to
determine if the HMI is operating as a server or as a viewer (LOCAL_PROJECT =0 for
Viewer,
LOCAL_PROJECT =1 for Server)
A Remote system can operate as a server or a viewer
Each turbine unit has a single pushbutton used to assign the UNIT,
UNIT_NAME and UNIT_NO screen variables. All points within the
Gas Turbine 1
Unit_Control.cim file (i.e., L1START, L4) are proceeded by the screen
variable UNIT(Unit_L1START, Unit_L4, Unit_L4T). Thus the L1 buttons
Gas Turbine 2
are used to navigate from Unit1 Control to Unit2 Control and the same
Gas Turbine 3
CIMPLICITY file may be used.

Gas Turbine 4

This functionality simplifies revision control on multi-unit interfaces. The


UNIT variable is assigned values such as T1_, T2_ for gas or S1_,
S2_ for steam, depending on the number of units. Thus, when Unit3
Control is selected, the variable Unitis assigned. The UNIT_NAME
variable is displayed in the upper right hand corner on the turbine
banner. The UNIT_NO variable is used to assign object visibilitys to
buttons like Toolsor GT# Synch.

14.2 Naming Convention


Consider a Multi-Unit system with three servers (SVR1, SVR2, SVR3, a viewer VWR1 ,
and a remote viewer. The naming convention is shown in the Table. The Unit Variables
are initialized at start up
Computer Name
SVR1
SVR2
SVR3
REM1
Project Name
SVR1
SVR2
SVR3
REM1
Unit Variable
\\SVR1\Tn_ \\SVR2\T2_ \\SVR3\T3_ \\REM1\Tn_
.
For server SVR1 the navigation button Gas Turbine 1 initiates a procedure
L1_Gas_Turbine_1 with the associated actions. The variable LOCAL_VARIABLE is set
to 1 on SRV1. For the remaining procedures, L1_Gas_Turbine_2 and
L1_Gas_Turbine_3 the variable is set to 0 as shown in the example below where n is the
unit number.

HMI Turbine Screen Standards

77

For Server SVR1


L1_Gas_Turbine_1 UNIT, \\SVR1\Tn_
UNIT_NAME, GTn
UNIT_NO,1
LOCAL_PROJECT,1
L1_Gas_Turbine_2 UNIT, \\SVR2\T2_
UNIT_NAME, GT2
UNIT_NO,2
LOCAL_PROJECT,0
L1_Gas_Turbine_3 UNIT, \\SVR3\T3_
UNIT_NAME, GT3
UNIT_NO,3
LOCAL_PROJECT,0
For Server SVR2
L1_Gas_Turbine_1 UNIT, \\SVR1\Tn_
UNIT_NAME, GTn
UNIT_NO,1
LOCAL_PROJECT,0
L1_Gas_Turbine_2 UNIT, \\SVR2\T2_
UNIT_NAME, GT2
UNIT_NO,2
LOCAL_PROJECT,1
L1_Gas_Turbine_3 UNIT, \\SVR3\T3_
UNIT_NAME, GT3
UNIT_NO,3
LOCAL_PROJECT,0
For Viewer VWR1, VWR2 .
L1_Gas_Turbine_1 UNIT, \\VWR1\Tn_
UNIT_NAME, GTn
UNIT_NO,1
LOCAL_PROJECT,0
L1_Gas_Turbine_2 UNIT, \\VWR1\T2_
UNIT_NAME, GT2
UNIT_NO,2
LOCAL_PROJECT,0
L1_Gas_Turbine_3 UNIT, \\VWR1\T3_
UNIT_NAME,
UNIT_NO,3
LOCAL_PROJECT,0

HMI Turbine Screen Standards

78

For Remote REM1


L1_Gas_Turbine_1 UNIT, \\REM1\Tn_
UNIT_NAME, GTn
UNIT_NO,1
LOCAL_PROJECT,1
L1_Gas_Turbine_2 UNIT, \\REM1\T2_
UNIT_NAME, GT2
UNIT_NO,2
LOCAL_PROJECT,1
L1_Gas_Turbine_3 UNIT, \\REM1\T3_
UNIT_NAME, GT3
UNIT_NO,3
LOCAL_PROJECT,1
Note: If REM1 is acting as a Server then Local_Project is a 1 and when it is acting as a
Viewer it is 0

14.3 Tools Button


The tools button in a multi-unit system consist of a number
of buttons equivalent to the number of units grouped
together as a single object in CIMPLICITY. The visibility of
each individual button is controlled by the screen variable
UNIT_NO. This button color is OLIVE. This object (group of
buttons) overlays a second button color GRAY which has
visibility controlled by the screen variable
LOCAL_PROJECT.

14.3 Viewer Limitations


When CIMPLCITY HMI is acting as a Viewercertain
functions are not available. These include

Valve Calibration
Setting Hardware Jumpers
Demand
IO_Check
Viewer Synchronization

These functions are activated by buttons which execute


procedures on the CIMPLICITY HMI screens. These buttons
overlay duplicate buttons whose visibility is controlled by the
variable LOCAL_PROJECT. When the system is a viewer
the LOCAL_PROJECT variable is set to zero and the Viewer
buttons become. These buttons have a dark gray faceplate.
A screen text is also activated which alerts the operator to
the viewer limitation.

HMI Turbine Screen Standards

79

This page intentionally left blank.