You are on page 1of 6

Service Report

Order Nr

Key Word

PLTMG TELUK LEMBU II

Subject

COMMISSIONING

Module Type

JMS 620 GS NL 6 UNITS

Module Nr

M03

Engine Nr

1073463

Design Nr

J P 265

Year of Delivery

2013

Operating hours
Start Nr
Software version

RPS
3.30 1a
OPC
CUST
VIS
3.30 1a

KLS
MMU
1.0
MONIC

IGN 7.64
SPS
TEC.J 2.06

Service Technician

Rendra
Nayim

Date of work
From
To

08 Nov 13

1.
2.
3.
4.
5.
6.
7.
8.

18 Nov 13

Purpose of business trip, assignment


Ascertained fault, troubleshooting and result
Open tasks
Missing parts ( Nr of pieces, description and P/N)
Demounted parts ( info from their whereabouts)
Conclusion
Recommendation
Remark

Purpose of business trip, assignment


PT. NAVIGAT Energy, SERVICE CENTER. Jl. Raya Kebayoran Lama No. 42C Jakarta
12220
Telp: +62 21 72789388, Fax +62 21 72789427
Page 1

Commissioning new engine installation


Ascertained fault, troubleshooting and result
Commissioning new engine after installation completed, the plant stand of 6 units of
JMS 620 GS NL, with various Design no.
M01 J P225 Serial No 1073373
M02 J P269 Serial No 1073478
M03 J P265 Serial No 1073463
M04 J P267 Serial No 1073468
M05 J P263 Serial No 1073456
M06 J P245 Serial No 1073419
Open tasks
Engine installation with enclosure

6 units enclosure installation

PT. NAVIGAT Energy, SERVICE CENTER. Jl. Raya Kebayoran Lama No. 42C Jakarta
12220
Telp: +62 21 72789388, Fax +62 21 72789427
Page 2

Engine installation in the enclosure

HT and LT Cooling pipe installation

PT. NAVIGAT Energy, SERVICE CENTER. Jl. Raya Kebayoran Lama No. 42C Jakarta
12220
Telp: +62 21 72789388, Fax +62 21 72789427
Page 3

Gas Train installation

Module Installation
All units operate in mains parallel operation, the unit synchronize with grid at 20kV
system, the generator output 11kV are step up to 20kV through Step up transformer.
PT. NAVIGAT Energy, SERVICE CENTER. Jl. Raya Kebayoran Lama No. 42C Jakarta
12220
Telp: +62 21 72789388, Fax +62 21 72789427
Page 4

The generator output through junction box for metering on Diane XT 3

Step up transformer from 11kV to 20kV


Missing /damage parts (Nr of pieces, description and P/N)
Pressure transducer
SAFI2
Charger
PT. NAVIGAT Energy, SERVICE CENTER. Jl. Raya Kebayoran Lama No. 42C Jakarta
12220
Telp: +62 21 72789388, Fax +62 21 72789427
Page 5

Demounted parts (info from their whereabouts)


No demounted parts
Conclusion
All units have test parallel with grid, and no islan opeartion. The units successfully
loaded untill 100 persent of the nominal output 3345kW, and supply to grid system.
Recommendation
Remarks

PT. NAVIGAT Energy, SERVICE CENTER. Jl. Raya Kebayoran Lama No. 42C Jakarta
12220
Telp: +62 21 72789388, Fax +62 21 72789427
Page 6