650 SETPOINT FILE INFORMATION


VALUE
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]
0000 [0000 : FFFF]

EnerVista 650 Setup


UNIT

FAULT REPORT
NAME
Function
Pos Seq Module
Pos Seq Angle
Zero Seq Module
Zero Seq Angle
Line Length
Show Fault On HMI
Snapshot Events

VALUE
ENABLED
3.00 [0.01 : 250.00]
75. [25 : 90]
9.00 [0.01 : 750.00]
75. [25 : 90]
100.0 [0.0 : 2000.0]
ENABLED
ENABLED

UNIT
Ohm
Deg
Ohm
Deg

OSCILLOGRAPHY
NAME
Function
Trigger Position
Samples/Cycle
Max. Number Osc.
Automatic Overwrite
Snapshot Events

VALUE
ENABLED
30 [5 : 95]
64
4 [1 : 20]
DISABLED
ENABLED

UNIT
%

TIME SETTINGS
NAME
LOC. TIME OFFS. UTC
DAYLIG. SAVINGS TIME
DST START MONTH
DST START WEEKDAY
DST START DAY INST
DST START HOUR
DST STOP MONTH
DST STOP WEEKDAY
DST STOP DAY INST
DST STOP HOUR
IRIG-B LOCAL TIME

VALUE
0.0 [-24.0 : 24.0]
DISABLED
MAR
SUNDAY
LAST
2 [0 : 23]
OCT
SUNDAY
LAST
2 [0 : 23]
OFF

UNIT

GENERAL SETTINGS
NAME
Phase CT Ratio
Ground CT Ratio
Stv Ground CT Ratio
Phase VT Ratio
Phase VT Connection
Nominal Voltage
Nominal Frequency
Phase Rotation
Frequency Reference

VALUE
150.0 [1.0 : 6000.0]
150.0 [1.0 : 6000.0]
1.0 [1.0 : 6000.0]
54.5 [1.0 : 6000.0]
WYE
110.0 [1.0 : 250.0]
50 Hz
ABC
VI

UNIT

GE Power Management
NAME
Snapshot Events SWGR 15
Snapshot Events SWGR 16

650 SETPOINT FILE INFORMATION


VALUE
DISABLED
DISABLED

EnerVista 650 Setup


UNIT

PHASE TOC HIGH 1


NAME
Function
Input
Pickup Level
Curve
TD Multiplier
Reset
Voltage Restraint
Snapshot Events

VALUE
ENABLED
PHASOR(DFT)
3.22 [0.05 : 160.00]
IEEE Very Inv
4.00 [0.00 : 900.00]
INSTANTANEOUS
DISABLED
ENABLED

UNIT
A
s

PHASE IOC HIGH 1


NAME
Function
Input
Pickup Level
Trip Delay
Reset Delay
Snapshot Events

VALUE
ENABLED
PHASOR(DFT)
32.20 [0.05 : 160.00]
0.00 [0.00 : 900.00]
0.00 [0.00 : 900.00]
ENABLED

UNIT
A
s
s

NEUTRAL TOC 1
NAME
Function
Pickup Level
Curve
TD Multiplier
Reset
Snapshot Events

VALUE
ENABLED
1.00 [0.05 : 160.00]
IEEE Ext Inv
2.00 [0.00 : 900.00]
INSTANTANEOUS
ENABLED

UNIT
A
s

NEUTRAL IOC 1
NAME
Function
Pickup Level
Trip Delay
Reset Delay
Snapshot Events

VALUE
ENABLED
30.00 [0.05 : 160.00]
0.01 [0.00 : 900.00]
0.00 [0.00 : 900.00]
ENABLED

UNIT
A
s
s

PHASE UV 1
NAME
Function
Mode
Pickup Level
Curve
Delay
Minimum Voltage
Logic
Supervised by 52
Snapshot Events

VALUE
ENABLED
PHASE-PHASE
88. [3 : 300]
DEFINITE TIME
0.05 [0.00 : 900.00]
5. [0 : 300]
ANY PHASE
DISABLED
ENABLED

UNIT
V
s
V

PHASE OV 1
NAME
Function
Pickup Level
Trip Delay
Reset Delay

VALUE
ENABLED
121. [3 : 300]
0.05 [0.00 : 900.00]
0.00 [0.00 : 900.00]