FAULT REPORT
NAME
Function
Pos Seq Module
Pos Seq Angle
Zero Seq Module
Zero Seq Angle
Line Length
Show Fault On HMI
Snapshot Events
VALUE
ENABLED
3.00 [0.01 : 250.00]
75. [25 : 90]
9.00 [0.01 : 750.00]
75. [25 : 90]
100.0 [0.0 : 2000.0]
ENABLED
ENABLED
UNIT
Ohm
Deg
Ohm
Deg
OSCILLOGRAPHY
NAME
Function
Trigger Position
Samples/Cycle
Max. Number Osc.
Automatic Overwrite
Snapshot Events
VALUE
ENABLED
30 [5 : 95]
64
4 [1 : 20]
DISABLED
ENABLED
UNIT
%
TIME SETTINGS
NAME
LOC. TIME OFFS. UTC
DAYLIG. SAVINGS TIME
DST START MONTH
DST START WEEKDAY
DST START DAY INST
DST START HOUR
DST STOP MONTH
DST STOP WEEKDAY
DST STOP DAY INST
DST STOP HOUR
IRIG-B LOCAL TIME
VALUE
0.0 [-24.0 : 24.0]
DISABLED
MAR
SUNDAY
LAST
2 [0 : 23]
OCT
SUNDAY
LAST
2 [0 : 23]
OFF
UNIT
GENERAL SETTINGS
NAME
Phase CT Ratio
Ground CT Ratio
Stv Ground CT Ratio
Phase VT Ratio
Phase VT Connection
Nominal Voltage
Nominal Frequency
Phase Rotation
Frequency Reference
VALUE
40.0 [1.0 : 6000.0]
40.0 [1.0 : 6000.0]
50.0 [1.0 : 6000.0]
54.5 [1.0 : 6000.0]
WYE
110.0 [1.0 : 250.0]
50 Hz
ABC
VI
UNIT
GE Power Management
NAME
Snapshot Events SWGR 15
Snapshot Events SWGR 16
VALUE
ENABLED
PHASOR(DFT)
3.02 [0.05 : 160.00]
IEEE Very Inv
4.00 [0.00 : 900.00]
INSTANTANEOUS
DISABLED
ENABLED
UNIT
A
s
VALUE
ENABLED
PHASOR(DFT)
30.23 [0.05 : 160.00]
0.00 [0.00 : 900.00]
0.00 [0.00 : 900.00]
ENABLED
UNIT
A
s
s
NEUTRAL TOC 1
NAME
Function
Pickup Level
Curve
TD Multiplier
Reset
Snapshot Events
VALUE
ENABLED
1.00 [0.05 : 160.00]
IEEE Ext Inv
1.00 [0.00 : 900.00]
INSTANTANEOUS
ENABLED
UNIT
A
s
NEUTRAL IOC 1
NAME
Function
Pickup Level
Trip Delay
Reset Delay
Snapshot Events
VALUE
ENABLED
30.00 [0.05 : 160.00]
0.00 [0.00 : 900.00]
0.00 [0.00 : 900.00]
ENABLED
UNIT
A
s
s
VALUE
ENABLED
PHASOR(DFT)
0.050 [0.005 : 16.000]
IEEE Ext Inv
1.00 [0.00 : 900.00]
INSTANTANEOUS
ENABLED
UNIT
A
s
PHASE OV 1
NAME
Function
Pickup Level
Trip Delay
Reset Delay
Logic
Snapshot Events
VALUE
ENABLED
121. [3 : 300]
0.05 [0.00 : 900.00]
0.00 [0.00 : 900.00]
ANY PHASE
ENABLED
15
UNIT
V
s
s