Bare Copper Conductor, Soft Drawn

Specifications : - PNS 1207

Application :

Aerial power transmission,


distribution lines, and ground wires.

Stranded Copper Conductor

Size
1.6 mm Solid

CONSTRUCTION
Cross-sectional Overall
# of wires diameter
Area
Diameter
mm
mm
mm
1
1.6
2.01
1.60

Approx.
Weight
Kg. / Km.
17.87

Resistance
Cable
@ 20C (nom.) Ampacity*
ohm / Km
(A)
8.57
-

2.0 mm Solid

2.0

3.14

2.00

27.93

5.49

2.6 mm Solid

2.6

5.31

2.60

47.20

3.25

3.2 mm Solid

3.2

8.04

3.20

71.50

2.14

2.0 mm Stranded

0.6

1.98

1.76

17.95

9.00

3.5 mm Stranded

0.8

3.52

2.35

31.91

5.06

5.5 mm Stranded

1.0

5.50

2.93

49.85

3.24

8.0 mm Stranded

1.2

7.92

3.52

71.79

2.25

92

14 mm Stranded

1.6

14.07

4.69

127.62

1.26

131

22 mm Stranded

2.0

21.99

5.87

199.41

0.80

161

30 mm Stranded

2.3

29.08

6.74

263.72

0.61

180

38 mm Stranded

19

1.6

38.20

7.82

346.41

0.46

210

50 mm Stranded

19

1.8

48.35

8.80

438.42

0.37

254

60 mm Stranded

19

2.0

59.69

9.78

541.26

0.30

291

80 mm Stranded

19

2.3

78.94

11.24

715.82

0.22

354

100 mm Stranded

19

2.6

100.88

12.71

914.73

0.18

417

125 mm Stranded

37

2.1

128.15

14.37

1,162.07

0.14

488

150 mm Stranded

37

2.3

153.73

15.74

1,393.96

0.12

562

200 mm Stranded

37

2.6

196.44

17.79

1,781.31

0.09

668

250 mm Stranded

37

3.0

252.89

20.19

2,293.18

0.09

774

250 mm Stranded

61

2.3

253.44

20.23

2,298.14

0.07

774

325 mm Stranded

61

2.6

323.87

22.87

2,936.76

0.05

904

400 mm Stranded

61

2.9

402.92

25.51

3,653.57

0.04

1033

500 mm Stranded

61

3.2

490.59

28.15

4,448.58

0.04

1181

Note : Above figures are nominal and subject to standard manufacturing tolerances
*Ampacity is based from PEC Table 3.10.1.21 Ampacities of Bare Covered Condcutors, Based on 40C Ambient,
80C Total Conductor Temperature, 610mm/sec Wind Velocity