Professional Documents
Culture Documents
New Tds 1c Alum Xlpe Awa PVC 0.6 1kv 90d Iec Resist React
New Tds 1c Alum Xlpe Awa PVC 0.6 1kv 90d Iec Resist React
Bedding
Mylar
tape
XLPE
insulation
Specifications
Color-coding
Customer Specification
IEC 60228
IEC 60502 - 1
Marking
MFD BY PHEPS DODGE
PHILS. 1C _mm AL XLPE
AWA PVC 0.6/1kV 90D
2015
Voltage Rating
0.6/1 (1.2)kV
Aluminum wire
armour
Size
No. of
singles
(nom.)
mm
Conductor
diameter
(approx.)
Insulation
thickness
Insulation
diameter
(approx.)
mm
mm
mm
Compressed
Aluminum
conductor
(AA-1350)
Temperature Rating
90C Normal condition
130C Emergency condition
250C Short-circuit condition
Armour
No. of
singles
Jacket
thickness
Cable
diameter
(approx.)
Cable
weight
(approx.)
DC
resistance
@ 20C
Cond.
reactance
Cable
ampacity
mm
mm
mm
kg / km
/ km
/ km*
A**
Singles
diameter
95
19
12.3
1.1
14.5
35
1.6
1.7
23.6
795
0.320
0.1223
217
120
37
13.9
1.2
16.3
38
1.6
1.8
25.6
927
0.253
0.1183
276
150
37
15.7
1.4
18.5
42
1.6
1.8
27.8
1,096
0.206
0.1152
276
185
37
17.2
1.6
20.4
46
1.6
1.9
30.0
1,266
0.164
0.1138
312
240
37
19.6
1.7
23.0
51
1.6
2.0
32.7
1,522
0.125
0.1107
362
300
61
22.0
1.8
25.6
46
2.0
2.1
36.7
1,941
0.100
0.1102
407
400
61
25.5
2.0
29.5
52
2.0
2.3
41.0
2,430
0.078
0.1074
466
500
61
28.2
2.2
32.6
57
2.0
2.4
44.3
2,835
0.061
0.1058
528
Executive office:
2297 2/F BCS Prime Bldg. Pasong
Tamo Ext. Makati City, Philippines
T. (632) 813-2529
F. (632) 893-4990
Manufacturing Plant:
Luisita Industrial Park
San Miguel, Tarlac City Philippines
T. (6345) 985-1088 to 91
Customer Approval
Name
Signature
Date
PDP
Prep GGM
Approval CCG
Date 11/04/15