Comparison of USA, Canadian, IEC and European markings

required for IEC-based Zone certifications


Markings Required for IEC-based Zone Certifications
USA

Canada

IEC

Europe

a)

Class I

-----

-----

-----

b)

Zone 0, 1 or 2

-----

-----

-----

c)

AEx symbol

Ex symbol

Ex symbol

EEx symbol

d)

Protection method
symbol(s)

Protection method
symbol(s)

Protection method
symbol(s)

Protection method
symbol(s)

e)

Group IIA - IIC

Group IIA - IIC

Group IIA - IIC

Group IIA - IIC

f)

Temperature Codes
T1 T6

Temperature Codes
T1 T6

Temperature Codes
T1 T6

Temperature Codes
T1 T6

Key
a) Indicates explosive gas atmospheres.
b) Indicates likelihood that explosive gas atmosphere is present when the equipment is operating.
c) Symbol for apparatus for use in explosive atmospheres. Internationally (including Canada), the symbol "Ex" is
used. In the U.S. only, the 2002 NEC requires the symbol "AEx" instead of "Ex". In Europe only, the symbol
"EEx" is used.
d) Indicates the method of protection(s) used to prevent ignition of the explosive gas atmospheres.
e) Indicates the ignition-related properties of the explosive gas atmospheres.
f)

Indicates the maximum surface temperature of the equipment under normal operating conditions.