Professional Documents
Culture Documents
Treatment
Design of Aerated lagoon
By
Mohd. Sayeed ul Hasan
Department of earth & environmental studies
Design a flow through type aerated lagoon without recycling the sludge for the 15 year
the following given and assumed data
SI.
No.
Given data
Value or
Conc.
Assumed
data
Value
Q=100000*75/10^3
7500m^3/d
population
100000
SSi
125mg/l
Sewage flow
75l/person-day
SSe
40mg/l
O2 conc.A.l
1.2mg/l
BOD5,S0
125mg/l
K base e
.5d^-1 @20*c
BOD5,S
40mg/l
MLVSS,X
.8*MLSS
40*C
Aeration const.
11*c
alpha
.85
MCRT
5day
beta
10
4m
Temp coeff
1.06
11
500m
Y=.6,
ks=90mg/l
12
27*c
Kd=.06d^-1
S=(Ks*(1+Kd*MCRT))/(MCRT*(YK-Kd)-1)
S=(90*(1+.06*5))/(5*(.6*6-.6)-1)
S=7mg/l < 15mg/l acceptable
6-
1. For summer
BOD5 @ constt. Rate K28.44=K20(1.06)^Tww-20
K28.44=1.2(1.06)^28.44-20
K28.44=1.96d^-1
2. Similarly in winter
K25.22=1.62d^-1
Compute BOD5 by the relation S/S0=1/(1+K*MCRT)
in summer S=125/(1+1.96*5)
S=11.57mg/l < 15mg/l acceptable
Similarly in winter S=13.73mg/l <15 mg/l
-7
O2 kg/d=Q(S0-S)/f- 1.42 Px
O2 kg/d=(37500(125-12.65)*1000*10^-6)/.68 -1.42*(52*(10^-6)*37500*
O2 kg/d=3426.77kg/d=142kg/hr
11- Calculate power required for supplying desired O2 each day
Nf=(N0(BCs(temp,alt)-Cl)*((1.02)^T-20)*A)/Cs
B=1
A=.85
T=28.44*C (summer)
Cl=1.2
N0=1.5 (assuming)
F=.92 for 500m
O2 saturation for tap water in field Csw=7.60
Cs=O2 saturation in tap water @20*C=9.08mg/l of water
Cs(temp,alt)=7.60*.92=6.992mg/l
Nf=(1.5(1*6.92-1.2)*((1.02)^28.44-20)*.85/9.08
Nf=.961kh/hp-h=23kg/hp-d
Power required to supply 3426kg of O2/d at field condition , P
P=3426/23=148.95=149 hp
ANY ?????
THANK YOU