LV power air circuit breakers

and switch-disconnectors
Catalogue

Masterpact NT and NW
Merlin Gerin

We do more with electricity

000000000 yyyy Schneider Electric - All right reserved

Schneider Electric Industries SA


5, rue Nadar
92506 Rueil-Malmaison Cedex France
Tel : +33 (0)1 41 29 82 00
Fax : +33 (0)1 47 51 80 20

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given iin this publication

ce
document
a thas
imprim
This
document
been printed on ecological paper
sur du papier cologique.

http://www.schneiderelectric.com
Design: Schneider Electric - AMEG
Photos: Schneider Electric
Printed:

BTP207E

mm-yy

E58856

Things

never be
same

E58880

will
the

The original Masterpact has set a new standard for power circuit breakers
around the world. Over the years, other major manufacturers have tried to
keep up by developing products incorporating Masterpacts most
innovative features, including the breaking principle, modular design and
the use of composite materials.
Today, Schneider Electric continues to innovate with the new Merlin Gerin
Masterpact NT and NW ranges.
In addition to the traditional features of power circuit breakers
(withdrawability, discrimination and low maintenance), Masterpact now
offers built-in communications and metering functions, all in optimised
frame sizes.
Masterpact NT and NW incorporate the latest technology to enhance both
performance and safety. Easy to install, with user-friendly, intuitive
operation and environment-friendly design, they are, quite simply, circuit
breakers of their time.

Masterpact

Schneider Electric

E58873

The ultimate power


in power distribution

New Masterpact,
new levels of performance
Five performance levels

025855

029693

N1 - for standard applications with low short-circuit levels.


H1 - for industrial sites with high short-circuit levels or installations with
two parallel-connected transformers.
H2 - high-performance for heavy industry where very high short-circuits
can occur.
H3 - for incoming devices supplying critical applications requiring both
high performance and a high level of
discrimination.
L1 - for high current-limiting capability and a
discrimination level (37 kA) as yet unequalled by
any other circuit breaker of its type; intended for
the protection of cable-type feeders or to raise the
performance level of a switchboard when the
transformer power rating is increased.

E58868

Integration in a communications network


Masterpact can be integrated in a general supervision system to optimise
installation operation and maintenance. The communication architecture
is open, and may be upgraded for interfacing with any protocol.

Switch-disconnector versions

E58865

The switch-disconnectors are derived directly from the circuit breakers


and offer the same features and performance levels. They are available in
HA, NA and HF versions, depending on the models. The HF version
includes instantaneous protection to prevent closing on a short-circuit.
Once closed, the switch-disconnectors are unprotected and behave like
ordinary switches. They are often used for busbar coupling.

1000 V and 400 Hz distribution systems


The Masterpact range can be used on 1000 V
installations (mining industry) and 400 Hz systems
(aeronautics, computer centres).

Masterpact

Schneider Electric

E58882

Thing will be never


the same

3 frame sizes, 2 families


The new range of power circuit breakers
includes two families:
c Masterpact NT, the worlds smallest true
power circuit breaker, with ratings from 800 to
1600 A;
c Masterpact NW, in two frame sizes, one from
800 to 4000 A and the other from 4000 A to
6300 A.

Masterpact NT
056477

E58891

800 to 1600 A

Masterpact NW

056473

De 4000 6300 A

E58893

056472

E58892

800 to 4000 A

Masterpact

Schneider Electric

E58869

No other offer can


put us in the shade

Optimised
volumes
E58879

The smallest circuit breaker


in the world
Masterpact NT innovates by offering all the
performance of a power circuit breaker in an
extremely small volume. The 70 mm pole pitch
means a three-pole drawout circuit breaker can
be installed in a switchboard section 400 mm
wide and 400 mm deep.

E58880

Practical installation solutions

E58881

The new range improves upon all the


installation solutions which have already made
Masterpact a success. It has been designed to
standardise switchboards, optimise volumes
and simplify installation:
c incoming connection to top or bottom
terminals;
c no safety clearance required;
c connection:
v horizontal or vertical rear connection;
v front connection with minimum extra space;
v mixed front and rear connections;
c 115 mm pole pitch on all versions;
c no derating up to 55 C and 4000A.

Optimised volumes
Up to 4000 A, Masterpact NW circuit breakers
are all the same size, the same as the old M08
to 32 range.
From 4000 A to 6300 A, there is just one size,
much smaller than before.

Retrofit solutions
Special connections are available to replace a
fixed or drawout Masterpact M08 to 32 with a
Masterpact NW, without modifying the busbars
or the door cut-out.

Masterpact

Schneider Electric

E58867

A perfect fit

E58871

Ease of
installation

E58879

With optimised sizes, the Masterpact NT and


NW ranges simplify the design of switchboards
and standardise the installation of devices:
c a single connection layout for Masterpact NT;
c three connection layouts for Masterpact NW:
v one from 800 to 3200 A;
v one for 4000 A;
v one up to 6300 A;
c identical connection terminals from 800 to
6300 A (Masterpact NW);
c front connection requires little space because
the connectors to not increase the depth of the
device;
c rear connection to vertical or horizontal
busbars simply by turning the connectors 90.

E58870

E58872

Vertical front connection of a fixed


Masterpact NW.

Vertical and horizontal rear connection


of a fixed Masterpact NW.

Connection to busbars.

Masterpact

Schneider Electric

E58878

The shortest distance


between two points

Innovation
E58875

Greater dependability
Filtered breaking
The patented new design of the arc chutes includes stainless-steel filters.
The chutes absorb the energy released during breaking, thus limiting the
stresses exerted on the installation. They filter and cool the gases
produced, reducing effects perceptible from the outside.

Automatic unlatching
The automatic unlatching of the circuit breaker operating mechanism for
high short-circuits extends performance up to 150kA. It produces ultrafast tripping for all short-circuits higher than 37 kA (L1) and 65 kA (H3).
For lower short-circuits, the system does not react so that the control unit
can provide total discrimination with downstream devices.

Filtered breaking

More intelligent trip units


Today, with the high speed of calculation, the small size of memories and
advances in miniaturisation, trip units have become circuit breaker control
units offering increasingly powerful functions. They accurately measure
system parameters, instantly calculate values, store data, log events,
signal alarms, communicate, take action, etc. The new Masterpact
ranges, equipped with Micrologic control units, constitute both an
extremely reliable protective device and an accurate measurement
instrument.
E58874

User friendly
Intuitive use
Micrologic control units are equipped with a digital LCD display used in
conjunction with simple navigation buttons. Users can directly access
parameters and settings. Navigation between screens is intuitive and the
immediate display of values greatly simplifies settings. Text is displayed in
the desired language.

backed by incomparable security


Protection functions are separate from the measurement functions and
are managed by an ASIC electronic component. This independence
guarantees immunity from conducted or radiated disturbances and
ensures a high degree of reliability.
A patented double setting system for protection functions establishes:
* a maximum threshold set using the control-unit dials;
* fine adjustments via the keypad or remotely. The fine adjustments for
thresholds (to within one ampere) and tripping delays (to within a fraction
of a second) are displayed directly on the screen.
The control unit cover can be lead-sealed to prevent uncontrolled access
to the dials and protect the settings.

Navigation buttons on a Micrologic P


control unit.

Masterpact

Schneider Electric

E58876

How many green circuit


breakers do you know?

Ready for
the future
Compliance with
environmental requirements
Schneider Electric fully takes into account
environmental requirements, starting right from the
design phase of every product through to the end of
its service life:
c the materials used for Masterpact are not
potentially dangerous to the environment;
c the production facilities are non-polluting in
compliance with the ISO 14001 standard;
c filtered breaking eliminates pollution in the
switchboard;
c the energy dissipated per pole is low, making
energy losses insignificant;
c the materials are marked to facilitate sorting for
recycling at the end of product service life.

Simple upgrading of
installations
Installations change, power levels increase, new
equipment is required and switchboards must be
extended. Masterpact is designed to adapt to these
changes:
c all control units are interchangeable;
c communication with a supervision system is an
option that may be added at any time;
c a reserve chassis can be pre-addressed so that
system parameters do not have to be modified when
a drawout device is installed at a later date;
c any future changes to the products will be
designed to ensure continuity with the current
ranges, thus simplifying installation upgrades.

Masterpact

Schneider Electric

Masterpact NT and NW
10 years already

056409

The original Masterpact has set a new standard for power circuit breakers
around the world. Over the years, other major manufacturers have tried to
keep up by developing products incorporating Masterpacts most
innovative features, including the breaking principle, modular design and
the use of composite materials.
Today, Schneider Electric continues to innovate with the new Merlin Gerin
Masterpact NT and NW ranges.
In addition to the traditional features of power circuit breakers
(withdrawability, discrimination and low maintenance), Masterpact now
offers built-in communications and metering functions, all in optimised
frame sizes.
Masterpact NT and NW incorporate the latest technology to enhance both
performance and safety. Easy to install, with user-friendly, intuitive
operation and environment-friendly design, they are, quite simply, circuit
breakers of their time.

Setting the standard, once again

Masterpact

Schneider Electric

Loup

ultimate
in

The
power

power distribution

Masterpact

Schneider Electric

5 levels of
performance

044587

026160

Masterpact NT and NW offer 5 levels of performance to cover a wide


range of applications.

Special applications

E58868

053598

N1 - for standard applications with low short-circuit levels.


H1 - for industrial sites with high short-circuit levels or installations with
two parallel-connected transformers.
H2 - high-performance for heavy industry where very high short-circuits
can occur.
H3 - for incoming devices supplying critical applications requiring both
high performance and a high level of discrimination.
L1 - for high current-limiting capability and a discrimination level (37 kA)
as yet unequalled by any other circuit breaker of its type; intended for the
protection of cable-type feeders or to raise the performance level of a
switchboard when the transformer power rating is increased.

Switch-disconnectors
The switch-disconnectors are derived directly from the
circuit breakers.
They are available in a number of versions:
c for Masterpact NT: HA (equivalent to H1).
c for Masterpact NW:
v NA and HA (equivalent to N1 and H1)
v HF, a high-performance switch-disconnector including
instantaneous protection to prevent closing on a shortcircuit. Once closed, the switch-disconnector is
unprotected and behaves like an ordinary switch. It is
often used for busbar coupling.

029693

1000 V and 400 Hz distribution systems


The Masterpact range can be used on 1000 V
installations (mining industry) and 400 Hz systems
(aeronautics, computer centres).

Masterpact

Schneider Electric

Tournesol

Things
will
the

never be
same

Masterpact

Schneider Electric

3 frame sizes,
2 families
The new range of power circuit breakers
includes two families:
c Masterpact NT, the worlds smallest true power
circuit breaker, with ratings from 800 to 1600 A;
c Masterpact NW, in two frame sizes, one from
800 to 4000 A and the other from 4000 A to
6300 A.

056477

800 to 1600 A

E58891

Masterpact NT

056473

4000 to 6300 A

E58893

056472

800 to 4000 A

E58892

Masterpact NW

Masterpact

Schneider Electric

Cypres

No other

offer can put us


in the shade

Masterpact

Schneider Electric

E58879

Optimised
volumes
The smallest circuit
breaker in the world
Masterpact NT innovates by offering all the
performance of a power circuit breaker in an
extremely small volume. The 70 mm pole pitch
means a three-pole drawout circuit breaker can
be installed in a switchboard section 400 mm
wide and 400 mm deep.

E58881

E58880

Practical installation solutions:


The new range improves upon all the installation
solutions which have already made Masterpact a
success. It has been designed to standardise
switchboards, optimise volumes and simplify
installation:
c incoming connection to top or bottom terminals
c no safety clearance required
c connection:
v horizontal or vertical rear connection
v front connection with minimum extra space
v mixed front and rear connections
c 115 mm pole pitch on all versions
c no derating up to 55 C and 4000A.

Optimised volumes
Up to 4000 A, Masterpact NW circuit breakers are
all the same size, the same as the old M08 to 32
range.
The dimensions of a 3-pole Masterpact NW40
drawout circuit breaker are therefore
440 mm x 440 mm x 400 mm (H x W x D).
From 4000 A to 6300 A, there is just one size,
much smaller than before.
The dimensions of a 3-pole Masterpact NW63
drawout circuit breaker are therefore
480 mm x 730 mm x 440 mm (H x W x D).

Retrofit solutions
Special connections are available to replace a
fixed or drawout Masterpact M08 to 32 with a
Masterpact NW, without modifying the busbars or
the door cut-out.

Masterpact

Schneider Electric

Abeilles

fit

perfect

Masterpact

Schneider Electric

E58871

Ease of
installation
With optimised sizes, the Masterpact NT and
NW ranges simplify the design of switchboards
and standardise the installation of devices:
c a single connection layout for Masterpact NT
c three connection layouts for Masterpact NW:
v one from 800 to 3200 A
v one for 4000 A
v one up to 6300 A
c identical connection terminals from 800 to
6300 A (Masterpact NW)
c front connection requires little space because
the connectors to not increase the depth of the
device
c rear connection to vertical or horizontal
busbars simply by turning the connectors 90.

E58870

E58872

Vertical front connection of a fixed Masterpact NW

Connection to busbars.

Vertical and horizontal rear connection of a fixed


Masterpact NW.

Masterpact

Schneider Electric

Girafe

The
shortest distance
between

two points
Giraffe

hoto

iraffe p

e the G
n replac

gic

Microlo

You ca
by
hoto.
logic p
o
r
ic
M

the

10

Masterpact

Schneider Electric

Innovation

E58875

Greater dependability
Filtered breaking
The patented new design of the arc chutes includes stainless-steel filters.
The chutes absorb the energy released during breaking, thus limiting the
stresses exerted on the installation. They filter and cool the gases
produced, reducing effects perceptible from the outside.

Automatic unlatching

Filtered breaking.

The automatic unlatching of the circuit breaker operating mechanism for


high short-circuits extends performance up to 150kA. It produces ultrafast tripping for all short-circuits higher than 37 kA (L1) and 65 kA (H3).
For lower short-circuits, the system does not react so that the control unit
can provide total discrimination with downstream devices.

E58874

Greater intelligence
Today, with the high speed of calculation, the small size of memories and
advances in miniaturisation, trip units have become circuit breaker control
units offering increasingly powerful functions. They accurately measure
system parameters, instantly calculate values, store data, log events,
signal alarms, communicate, take action, etc. The new Masterpact
ranges, equipped with Micrologic control units, constitute both an
extremely reliable protective device and an accurate measurement
instrument.

User friendly
Intuitive use
Navigation buttons on a Micrologic P
control unit.

Micrologic control units are equipped with a digital LCD display used in
conjunction with simple navigation buttons. Users can directly access
parameters and settings. Navigation between screens is intuitive and the
immediate display of values greatly simplifies settings. Text is displayed in
the desired language.

backed by incomparable security


Protection functions are separate from the measurement functions. They
are managed by an ASIC electronic component common to all the control
units to guarantee immunity from conducted or radiated disturbances and
ensure a high degree of reliability.
A patented double setting system for protection functions establishes a
maximum threshold set using the control-unit dials and fine adjustments
via the keypad or remotely. The fine adjustments for thresholds (to within
one ampere) and tripping delays (to within a fraction of a second) are
displayed directly on the screen.
The control unit cover can be lead-sealed to prevent uncontrolled access
to the dials and protect the settings.

11

Masterpact

Schneider Electric

Oiseaux

How many green

circuit breakers
do you

know?

12

Masterpact

Schneider Electric

Ready
for the future
Compliance with
environmental
requirements
Schneider Electric fully takes into account
environmental requirements, starting right from the
design phase of every product through to the end of
its service life:
c the materials used for Masterpact are not
potentially dangerous to the environment
c the production facilities are non-polluting in
compliance with the ISO 14001 standard
c filtered breaking eliminates pollution in the
switchboard and the energy dissipated per pole is
low, making energy losses insignificant
c the materials are marked to facilitate sorting for
recycling at the end of product service life.

Integration
in a communications
network
Masterpact can be integrated in a general
supervision system to optimise installation operation
and maintenance. The communication architecture is
open, and may be upgraded for interfacing with any
protocol.

Simple upgrading of
installations
Installations change, power levels increase, new
equipment is required and switchboards must be
extended. Masterpact is designed to adapt to these
changes:
c all control units are interchangeable
c communication with a supervision system is an
option that may be added at any time
c a reserve chassis can be pre-addressed so that
system parameters do not have to be modified when
a drawout device is installed at a later date
c any future changes to the products will be
designed to ensure continuity with the current
ranges, thus simplifying installation upgrades.

13

Masterpact

Schneider Electric

Masterpact

Schneider Electric

Masterpact

Functions
and characteristics

Presentation

General overview
Detailed contents

10

Circuit breakers and switch-disconnectors


NT06 to NT16
NW08 to NW63

12
14

Micrologic control units


Overview of functions
Micrologic A ammeter
Micrologic P power meter
Micrologic H harmonic meter
Accessories and test equipment

16
18
20
24
26

Communication
COM option in Masterpact
Overview of functions
Masterpact in a communication network

28
29
30

Connections
Overview of solutions
Optional accessories

32
33

Locking
On the device
On the chassis

36
37

Indication contacts
Remote operation

38

Remote ON/OFF
Remote tripping

40
43

Accessories
Source-changeover systems

44

Presentation
Mechanical interlocking
Electrical interlocking
Associated automatic controllers

46
47
48
49

Display modules

50

Dimensions and connection


Electrical diagrams
Installation recommendations
Additional characteristics
References

Masterpact

53
81
91
115
121

Schneider Electric

Functions
and characteristics

General overview
Detailed contents

This chapter describes all the functions


offered by Masterpact NT and NW devices.
The two product families have identical
functions implemented using the same or
different components depending on the
case.

Circuit breakers and switch-disconnectors

page 12

056402

c ratings:
v Masterpact NT 630 to 1600 A
v Masterpact NW 800 to 6300 A
c circuit breakers type N1, H1, H2, H3, L1
c switch-disconnectors type NA, HA, HF
c 3 or 4 poles
c fixed or drawout versions
c option with neutral on the right
c protection derating

page 16
E46256

E46253

Micrologic control units


Ammeter A
2.0 basic protection
5.0 selective protection
6.0 selective + earth-fault protection
7.0 selective + earth-leakage protection
Power meter P
5.0 selective protection
6.0 selective + earth-fault protection
7.0 selective + earth-leakage protection
Harmonic meter H
5.0 selective protection
6.0 selective + earth-fault protection
7.0 selective + earth-leakage protection
c external sensor for earth-fault protection
c rectangular sensor for earth-leakage protection
c setting options (long-time rating plug):
v low setting 0.4 to 0.8 x Ir
v high setting 0.8 to 1 x Ir
v without long-time protection
c external power-supply module
c battery module

100 %

40 %

menu

Communication

page 28

c COM option in Masterpact


c Masterpact in a communication network

E46427
E46428
E46431

056403

page 32
E46426

Connections
c rear connection (horizontal or vertical)
c front connection
c mixed connections
c optional accessories
v bare-cable connectors and connector shields
v terminal shields
v vertical-connection adapters
v cable-lug adapters
v interphase barriers
v spreaders
v disconnectable front-connection adapter
v safety shutters, shutter locking blocks, shutter
position indication and locking

10

Masterpact

Schneider Electric

056405

page 36

E47481

E47482

Locking
c pushbutton locking by padlockable transparent cover
c OFF-position locking by padlock or keylock
c chassis locking in disconnected position by keylock
c chassis locking in connected, disconnected
and test positions
c door interlock (inhibits door opening with breaker
in connected position)
c racking interlock (inhibits racking with door open)
c racking interlock between crank and OFF pushbutton
c automatic spring discharge before breaker removal
c mismatch protection

page 38

E47301

E47302

056428

Indication contacts
c standard or low-level contacts:
v ON/OFF indication (OF)
v fault trip indication (SDE)
v carriage switches for connected (CE),
disconnected (CD) and test (CT) positions
c programmable contacts:
v 2 contacts (M2C)
v 6 contacts (M6C).

OF contact

M2C contact

E47303

page 40

E47304

Gear motor

MX, XF and MN voltage


releases

Accessories
c auxiliary terminal shield
c operation counter
c escutcheon
c transparent cover for escutcheon
c escutcheon blanking plate

11

Masterpact

page 44
E47483

056407

Remote operation
c remote ON/OFF:
v gear motor
v XF closing or MX opening voltage releases
v PF ready-to-close contact
v options: RAR automatic or Res electrical
remote reset
- BPFE electrical closing pushbutton
c remote tripping function:
v MN voltage release
- standard
- adjustable or non-adjustable delay
v or second MX voltage release

0039

Schneider Electric

056408

Functions
and characteristics

Circuit breakers
and switch-disconnectors
NT06 to NT16
common characteristics
number of poles
rated insulation voltage (V)
impulse withstand voltage (kV)
rated operational voltage (V AC 50/60 Hz)
suitability for isolation
degree of pollution

Ui
Uimp
Ue
IEC 60947-2
IEC 60664-1

3/4
1000/1250
12
690 / 1000V
3

circuit-breaker characteristics as per IEC 60947-2


rated current (A)
rating of 4th pole (A)
sensor ratings (A)
type of circuit breaker
ultimate breaking capacity (kA rms)
V AC 50/60 Hz

rated service breaking capacity (kA rms)


rated short-time withstand current (kA rms)
V AC 50/60 Hz
integrated instantaneous protection (kA peak 10%)
rated making capacity (kA peak)
V AC 50/60 H

In

at 40C / 50C**

Icu

220/415 V
440 V
525 V
690 V
1000 V
% Icu
0.5 s
3s

Ics
Icw

Icm

220/415 V
440 V
525 V
690 V
1000 V

break time (ms)


closing time (ms)

circuit-breaker characteristics as per NEMA AB1


breaking capacity (kA)
V AC 50/60 Hz

240 V
480 V
600 V

switch-disconnector characteristics as per IEC 60947-3


type of switch-disconnector
rated making capacity (kA peak)
V AC 50/60 Hz

Icm

rated short-time withstand current (kA rms)


V AC 50/60 Hz
ultimate breaking capacity (Icu) with external protection relay,
maximum delay 350 ms

220/415 V
440 V
500/690 V
1000 V
0.5 s
3s

Icw

installation, connection and maintenance


service life
C/O cycles x 1000

mechanical
electrical

with maintenance
without maintenance
without maintenance

440 V
690 V
1000 V
690 V
FC
RC
FC
RC
3P
4P
3P
4P
3P/4P
3P/4P

motor control (AC3-947-4)


connection

drawout
fixed

dimensions (mm)
HxWxD

drawout
fixed

weight (kg)
(approximate)

drawout
fixed

* see the current-limiting curve in the additional characteristics section


** 50C: rear vertical connected. Refer to temperature derating tables
for other connection types.
(1) SELLIM system

12

Masterpact

Schneider Electric

NT06

NT08

NT10

NT12

NT16

630
630
400
to 630

800
800
400
to 800

1000
1000
400
to 1000

1250
1250
630
to 1250

1600
1600
800
to 1600

H1
42
42
42
42
100 %
42
20
88
88
88
88
25
< 50

L1*
150
130
100
25
-

H10
20

10
1(1)
330
286
220
52
9

20
42
25

42
42
42

150
100
25

HA
75
75
75
42
20
42

H1
42
42
42
42
100 %
42
20
88
88
88
88
25
< 50

H10
20

42
42
42

HA10
42
20
20

HA
75
75
75
42
20
42

HA10
42
20
20

25
12.5
6 (NT16: 3)
2 (NT16: 1)
2 (NT16: 1)
c
c
c
c

25
12.5
0.5
c
c
-

25
25
25
12.5
12.5
12.5
6
3
3
2
0.5
3
2
c
c
c
c
c
c
c
c
c
c
322 x 288 x 280
322 x 358 x 280
301 x 274 x 211
301 x 344 x 211
30/39
14/18

20
42
25

sensor selection
sensor rating (A)
Ir threshold setting (A)

400
160 to 400

630
250 to 630

13

800
320 to 800

Masterpact

1000
400 to 1000

1250
500 to 1250

1600
640 to 1600

Schneider Electric

056409

Functions
and characteristics

Circuit breakers
and switch-disconnectors
NW08 to NW63
common characteristics
number of poles
rated insulation voltage (V)
impulse withstand voltage (kV)
rated operational voltage (V AC 50/60 Hz)
suitability for isolation
degree of pollution

Ui
Uimp
Ue
IEC 60947-2
IEC 60664-1

3/4
1000/1250
12
690/1150
4

circuit-breaker characteristics as per IEC 60947-2

056410

rated current (A)


rating of 4th pole (A)
sensor ratings (A)
type of circuit breaker
ultimate breaking capacity (kA rms)
V AC 50/60 Hz

rated service breaking capacity (kA rms)


rated short-time withstand current (kA rms)
V AC 50/60 Hz
integrated instantaneous protection (kA peak 10%)
rated making capacity (kA peak)
V AC 50/60 Hz

In

at 40C / 50C**

Icu

220/415 V
440 V
525 V
690 V
1150 V
% Icu
1s
3s

Ics
Icw

Icm

220/415 V
440 V
525 V
690 V
1150 V

break time (ms)


closing time (ms)

circuit-breaker characteristics as per NEMA AB1


breaking capacity (kA)
V AC 50/60 Hz

240 V
480 V
600 V

switch-disconnector characteristics as per IEC 60947-3


type of switch-disconnector
rated making capacity (kA peak)
V AC 50/60 Hz

Icm

rated short-time withstand current (kA rms)


V AC 50/60 Hz
ultimate breaking capacity (Icu) with external protection relay,
maximum delay 350 ms

220/415 V
440 V
500/690 V
1150 V
1s
3s

Icw

installation, connection and maintenance


service life
C/O cycles x 1000

mechanical
electrical

with maintenance
without maintenance
without maintenance

440 V
690 V
1150 V
690 V
FC
RC
FC
RC
3P
4P
3P
4P
3P/4P
3P/4P

motor control (AC3-947-4)


connection

drawout
fixed

dimensions (mm)
HxWxD

drawout
fixed

weight (kg)
(approximate)

drawout
fixed

* see the current-limiting curve in the additional characteristics section


** 50C: rear vertical connected. Refer to temperature derating tables
for other connection types.
(1) except 4000 A

14

Masterpact

Schneider Electric

NW08 NW10 NW12 NW16 NW20

NW25 NW32 NW40

NW40b NW50 NW63

800
800
400
to 800

2500
2500
1250
to 2500

4000
4000
2000
to 4000

4000
4000
2000
to 4000

H3
150
150
130
100
-

H10
50

65
65
150
330
330
286
220
25

50
50
without
105
25

H1
H2
100
150
100
150
100
130
100
100
100 %
100
100
100
100
without270
220
330
220
330
220
286
220
220
25
25
< 80

150
150
100

100
100
100

HA10
105
50
50
50

HA
187
187
187
85
85
85

1000
1000
400
to 1000

N1
H1
H2
42
65
100
42
65
100
42
65
85
42
65
85
100 %
42
65
85
22
36
50
without without 190
88
143
220
88
143
220
88
143
187
88
143
187
25
25
25
< 70
42
42
42

65
65
65

100
100
85

NA
88
88
88
42
42

HA
105
105
105
50
36
50

HF
187
187
187
85
75
85

25
12.5
10
10
10
10
10
10
10
10
10
c
c
c
c
c
c
c
c
c
c
c
c
439 x 441 x 395
439 x 556 x 395
352 x 422x 297
352 x 537x 297
90/120
60/80

1250
1250
630
to 1250

1600
1600
800
to 1600

2000
2000
1000
to 2000

L1*
150
150
130
100
-

H10
50

30
30
80
330
330
286
220
10

50
50
without
105
25

150
150
100

65
65
65

100
100
85

HA10
105
50
50
50

HA
105
105
105
50
36
50

HF
187
187
187
85
75
85

0.5
c
c
-

20
10
8
6
6
c
c
c
c

3
3
c
c
-

H1
H2
65
100
65
100
65
85
65
85
100 %
65
85
36
75
without 190
143
220
143
220
143
187
143
187
25
25
< 70

8
6
6
c
c
c
c

3200
3200
1600
to 3200

H3
150
150
130
100
-

L1*
150
150
130
100
-

H10
50

65
65
150
330
330
286
220
25

30
30
80
330
330
286
220
10

50
50
without
105
25

150
150
100

150
150
100

65
65
65

100
100
85

HA10
105
50
50
50

HA
121
121
121
55
55
55

HF
187
187
187
85
75
85

0.5
c
c
-

20
10
5
2.5
2.5
c
c
c (1)
c

2
2
6
c
c
-

3
3
c
c
-

H1
H2
65
100
65
100
65
85
65
85
100 %
65
85
65
75
without 190
143
220
143
220
143
187
143
187
25
25
< 70

5
2.5
2.5
c
c
c (1)
c

1.25
1.25
2.5
c
c
-

5000
5000
2500
to 5000

6300
6300
3200
to 6300

150
150
100

10
5
1.5
1.5
1.5
1.5
c
c
c
c
479 x 786 x 395
479 x 1016 x 395
352 x 767x 297
352 x 997x 297
225/300
120/160

0.5
c
c
-

sensor selection
sensor rating (A)
Ir threshold
setting (A)

400
160
to 400

630
250
to 630

800
320
to 800

1000
400
to 1000

15

1250
500
to 1250

1600
630
to 1600

Masterpact

2000
800
to 2000

2500
1000
to 2500

3200
1250
to 3200

4000
1600
to 4000

5000
2000
to 5000

6300
2500
to 6300

Schneider Electric

Functions
and characteristics

Micrologic control units


Overview of functions

All Masterpact circuit breakers are


equipped with a Micrologic control unit that
can be changed on site.
Control units are designed to protect Power
circuits and loads. Alarms may be
programmed for remote indications.
Measurements of current, voltage,
frequency, power and power quality
optimise continuity of service and energy
management.

Dependability
Integration of protection functions in an ASIC electronic component used in all
Micrologic control units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances.
On Micrologic A, P and H control units, advanced functions are managed by an
independent microprocessor.

Micrologic name codes

Current protection
Micrologic 2: basic protection

X: type of protection
c 2 for basic protection
c 5 for selective protection
c 6 for selective + earth-fault protection
c 7 for selective + earth-leakage protection
Y: control-unit generation
Identification of the control-unit generation.
0 signifies the first generation.
Z: type of measurement
c A for ammeter
c P for power meter
c H for harmonic meter.

E46019

X Y

Protection:
0

Ir

Isd

long time + instantaneous

Micrologic 5: selective protection


E46020

2.0 A

Protection:
056411

Ir

Isd

Ii

long time + short time + instantaneous

t
E46033

E46020

Micrologic 6: selective + earth-fault protection

Protection:

Ir

Isd

Ii

Ig

long time
+ short time
+ instantaneous
+ earth fault

t
E46034

E46020

Micrologic 7: selective + earth-leakage protection

Protection:

16

Ir

Isd

Ii

Masterpact

In

long time
+ short time
+ instantaneous
+ earth leakage

Schneider Electric

Measurements and programmable protection


A: ammeter
c I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these
measurements
c fault indications
c settings in amperes and in seconds

P: A + power meter + programmable protection


c measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and
maximeters and minimeters
c IDMTL long-time protection, minimum and maximum voltage and frequency, voltage and
current imbalance, phase sequence, reverse power
c load shedding and reconnection depending on power or current
c measurements of interrupted currents, differentiated fault indications, maintenance
indications, event histories and time-stamping, etc.

H: P + harmonics

2.0 A

E46251

c power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 51st
order
c waveform capture after fault, alarm or on request
c enhanced alarm programming: thresholds and actions

100 %

40 %

E46256

E46255

6.0 H

7.0 H

E46256

7.0 P

E46255

6.0 P

5.0 H

E46256

5.0 P

E46256

5.0 A

E46252

menu

100 %

40 %

6.0 A

E46253

menu

100 %

40 %

7.0 A

E46253

menu

100 %

40 %

menu

17

Masterpact

Schneider Electric

Control units
Micrologic A ammeter

Micrologic A control units protect power


circuits.
They also offer measurements, display,
communication and current maximeters.
Version 6 provides earth-fault protection,
version 7 provides earth-leakage
protection.

Protection settings ........................................................

E46028

Functions
and characteristics

Micrologic 6.0 A

9
10
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=

MAX
s
kA

11

100 %
12
40 %

Protection thresholds and delays are set using the adjustment dials.
The selected values are momentarily displayed in amperes and in seconds.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth fault protection
Residual or source ground return.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
d Protected against nuisance tripping.
k DC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2),
neutral protection at In (4P 4t).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.

Ammeter measurements ...........................................


13

menu

long time

Ir

.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

tsd
(s)

D
C
B
A

.3
.2
.1
on

.2
.1
0
I t off
2

delay

tg
F
G
H
J

Ii

.4 .4 .3

setting

Ig

Communication option

In conjunction with the COM communication option, the control unit transmits the
following:
c setting values
c all ammeter measurements
c tripping causes
c maximeter reset.

instantaneous

short time

(s)

on

.2
.1
2

I t

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1

4
3

Micrologic A control units measure the true rms value of currents.


A digital LCD screen continuously displays the most heavily loaded phase (Imax)
or displays the I1, I2, I3, IN, Ig, In, stored-current (maximeter) and setting values by
successively pressing the navigation button.
The optional external power supply makes it possible to display currents < 20% In.

@ 6 Ir

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

menu

6
8

0
off

ground fault

1
2
3
4
5
6
7
8
9
10
11
12
13

long-time current setting and tripping delay


overload signal (LED)
short-time pick-up and tripping delay
instantaneous pick-up
earth-leakage or earth-fault pick-up and tripping delay
earth-leakage or earth-fault test button
long-time rating plug screw
test connector
lamp test, reset and battery test
indication of tripping cause
digital display
three-phase bargraph and ammeter
navigation buttons

Note.
Micrologic A control units come with a transparent leadseal cover as standard.

18

Masterpact

Schneider Electric

Micrologic 2.0 A

long time
current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %)
thermal memory
Isd = Ir x

1.5

10

2.5

Ir

tr

Isd
I

menu

I2
I3 IN
I1
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

Micrologic 5.0 / 6.0 / 7.0 A


0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
12.5 25
50
100
200
300
400
0.5
1
2
4
8
12
16
0.34 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping

0.98

500
20
13.8

600
24
16.6

10

E46023

Micrologic 5.0 / 6.0 / 7.0 A

long time
current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
thermal memory

time delay (ms)


at In or 1200 A

600
24
16.6

Micrologic 2.0 A

Protection

Ir
tr
Isd
tsd

Isd = Ir x

1.5

2.5

Off
I2t On
tsd (max resettable time)
tsd (max break time)

0
20
80

0.1
0.1
80
140

0.2
0.2
140
200

0.3
0.3
230
320

0.4
0.4
350
500

Ii = In x

10

12

15

off

Ig = In x
In i 400 A
400 A < In i 1200 A
In > 1200 A
settings
I2t Off
I2t On
tg (max resettable time)
tg (max break time)

Micrologic 6.0 A
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500
640
720
0
0.1
0.2
0.1
0.2
20
80
140
80
140
200

D
0.5
0.5
800
0.3
0.3
230
320

E
0.6
0.6
880
0.4
0.4
350
500

F
0.7
0.7
960

G
0.8
0.8
1040

H
0.9
0.9
1120

J
1
1
1200

Micrologic 7.0 A
0.5
1
2

60
80
140

350
350
500

800
800
1000

settings

I2t

residual earth leakage (Vigi)


sensitivity (A)
In
accuracy: 0 to -20 %
time delay (ms.)
settings
tn (max resettable time)
tn (max break time)

Ammeter
continuous current measurements
measurements from 20 to 200 % of In
accuract: 1.5 % (including sensors)
maximeters

140
140
200

230
230
320

Ii
0

E46024

earth fault
pick up (A)
accuracy: 10 %

500
20
13.8

continuous current measurements


measurements from 20 to 200 % de In
accuracy: 1.5% (including sensors)
maximeters

instantaneous
pick-up (A)
accuracy: 10 %

fixed: 20 ms

Ammeter

short time
pick-up (A)
accuracy: 10 %
time delay (ms) at 10 Ir

0.98

I t on

Ig
2

tg

I t off

Micrologic 5.0 / 6.0 / 7.0 A

10

20

30

E46243A

instantaneous
pick-up (A)
accuracy: 10 %
time delay

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
12.5 25
50
100
200
300
400
0.5
1
2
4
8
12
16
0.34 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping

E46022

Protection

In
tn

I
menu

I2
I3
IN
Ig
In
I1
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max Ig max In max

Note.
All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the
battery.

19

Masterpact

Schneider Electric

Control units
Micrologic P power

Micrologic P control units include all the


functions offered by Micrologic A.
In addition, they measure voltages and
calculate power and energy values.
They also offer new protection functions
based on currents, voltages, frequency and
power reinforce load protection.

Protection settings ........................................................

E46017

Functions
and characteristics

Micrologic 6.0 P

9
10

I (A)
Trip

2000A
11

24s
20 kA
0.4s

Programmable alarms and other protection ......................

Off

13
14

12
15

long time

.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

16

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

D
C
B
A

on

I t

off

delay

tg
F
G
H
J

Ii

(s)

setting

Ig

Depending on the thresholds and time delays set using the keypad or remotely
using the COM option, the Micrologic P control unit monitors currents and voltage,
power, frequency and the phase sequence. Each threshold overrun is signalled
remotely via the COM option. Each threshold overrun may be combined with
tripping (protection) or an indication carried out by an optional M2C or M6C
programmable contact (alarm), or both (protection and alarm).

Load shedding and reconnection ........................................

Ir

The adjustable protection functions are identical to those of Micrologic A


(overloads, short-circuits, earth-fault and earth-leakage protection).
Double setting
Within the range determined by the adjustment dial, fine adjustment of thresholds
(to within one ampere) and time delays (to within one second) is possible on the
keypad or remotely using the COM option.
IDMTL setting
Coordination with fuse-type or medium-voltage protection systems is optimised by
adjusting the slope of the overload-protection curve. This setting also ensures
better operation of this protection function with certain loads.
Neutral protection
On three-pole circuit breakers, neutral protection may be set using the keypad or
remotely using the COM option, to one of four positions: neutral unprotected (4P
3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t) and
neutral protection at 2 In (4P 3t + 2N). Neutral protection at 2 In is used when the
neutral conductor is twice the size of the phase conductors (major load imbalance,
high level of third order harmonics).
On four-pole circuit breakers, neutral protection may be set using a three-position
switch or the keypad: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t
+ N/2), neutral protection at In (4P 4t). Neutral protection produces no effect if the
long-time curve is set to one of the IDMTL protection settings.

(s)

on

.2
.1
2

I t

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1

4
3

6
8

0
off

ground fault

Load shedding and reconnection parameters may be set according to the power or
the current flowing through the circuit breaker. Load shedding is carried out by a
supervisor via the COM option or by an M2C or M6C programmable contact.

Measurements .......................................................................
The Micrologic P control unit calculates in real time all the electrical values (V, A,
W, VAR, VA, Wh, VARh, VAh, Hz), power factors and crest factors.
The Micrologic P control unit also calculates demand current and demand power
over an adjustable time period. Each measurement is associated with a minimeter
and a maximeter.
In the event of tripping on a fault, the interrupted current is stored. The optional
external power supply makes it possible to display the value with the circuit breaker
open or not supplied.

Histories and maintenance indicators ................................


The last ten trips and alarms are recorded in two separate history files.
Maintenance indications (contact wear, operation cycles, etc.) are recorded for
local access.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

long-time current setting and tripping delay


overload signal (LED)
short-time pick-up and tripping delay
instantaneous pick-up
earth-leakage or earth-fault pick-up and tripping delay
earth-leakage or earth-fault test button
long-time rating plug screw
test connector
lamp + battery test and indications reset
indication of tripping cause
high-resolution screen
measurement display
maintenance indicators
protection settings
navigation buttons
hole for settings lockout pin on transparent cover

Indication option via programmable contacts


The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used to
signal threshold overruns or status changes. They can be programmed using the
keypad on the Micrologic P control unit or remotely using the COM option.

Communication option (COM)


The communication option may be used to:
c remotely read and set parameters for the protection functions
c transmit all the calculated indicators and measurements
c signal the causes of tripping and alarms
c consult the history files and the maintenance-indicator register.
An event log and a maintenance register, stored in control-unit memory but not
available locally, may be accessed in addition via the COM option.

Note.
Micrologic P control units come with a non-transparent
lead-seal cover as standard.

20

Masterpact

Schneider Electric

Micrologic 5.0 / 6.0 / 7.0 P

long time (rms)


current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
IDMTL setting
curve slope
thermal memory

time delay (ms.) at 10 x Ir

Ir

tr
Isd

IDMTL

2.5

Off
I2t On
tsd (max resettable time)
tsd (max break time)

0
20
80

0.1
0.1
80
140

0.2
0.2
140
200

0.3
0.3
230
320

0.4
0.4
350
500

Ii = In x

Ig = In x
In i 400 A
400 A < In i 1200 A
In > 1200 A
settings
I2t Off
I2t On
tg (max resettable time)
tg (max break time)

Micrologic 6.0 P
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500
640
720
0
0.1
0.2
0.1
0.2
20
80
140
80
140
200

settings

I2t

10

tsd

10

12

15

OFF

D
0.5
0.5
800
0.3
0.3
230
320

E
0.6
0.6
880
0.4
0.4
350
500

F
0.7
0.7
960

G
0.8
0.8
1040

H
0.9
0.9
1120

J
1
1
1200

Micrologic 7.0 P
0.5
1
2

10

60
60
140

350
350
500

800
800
1000

140
140
200

230
230
320

E46024

1.5

Alarms and other protection

I t on

Ig
2

I t off

tg

20

30

In
tn

Micrologic 5.0 / 6.0 / 7.0 P

current
current imbalance
maximum demand current

Iimbalance
Imax demand: I1, I2, I3, IN, Ig

threshold
0.05 to 0.6 Imax
0.4 In at short-time pick-up

time delay
1 to 40 s.
0 to 1500 s.

voltage
voltage imbalance
minimum voltage
maximum voltage

Uimbalance
Umin
Umax

0.02 to 0.3 Uaverage


60 to 690 V between phases
100 to 930 V between phases

1 to 40 s.
0.2 to 5 s.
0.2 to 5 s.

power
reserve power

rP

5 to 500 kW

0.2 to 20 s.

frequency
minimum frequency
maximum frequency

Fmin
Fmax

45 to 400 Hz
45 to 540 Hz

0.2 to 5 s.
0.2 to 5 s.

t
threshold
threshold

delay

1/2/3 or 1/3/2

Load shedding and reconnection


measured value
current
power

600
24
16.6

Ii

Isd = Ir x

residual earth leakage (Vigi)


sensitivity (A)
In
accuracy: 0 to -20 %
time delay (ms.)
settings
tn (max resettable time)
tn (max break time)

phase sequence
sequence

500
20
13.8

E46243

earth fault
pick-up (A)
accuracy: 10 %

E46015

instantaneous
pick-up (A)
accuracy: 10 %

0.98

I
P

delay
0

I/U/P/F

instantaneous

Micrologic 5.0 / 6.0 / 7.0 P


threshold
0.5 to 1 Ir per phases
200 kW to 10 MW

time delay
20% tr to 80% tr.
10 to 3600 s.

E46016

short time (rms)


pick-up (A)
accuracy: 10 %
time delay (ms.) at 10 x Ir

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

Micrologic 5.0 / 6.0 / 7.0 P


0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
12.5 25
50
100
200
300
400
0.5
1
2
4
8
12
16
0.34 0.69 1.38 2.7
5.5
8.3
11
SIT
VIT
EIT
HVFuse DT
20 minutes before and after tripping

E46021

Protection

t
threshold
threshold

delay

delay

I/P

Note.
All current-based protection functions require no auxiliary source.
Voltage-based protection functions are connected to AC power via a voltage
measurement input built into the circuit breaker.

21

Masterpact

Schneider Electric

Control units
Micrologic P power

3850A

E46261

E46258

Functions
and characteristics

Imax

instant.

N 1 2 3
100

I1
I2

=
=

4800A
4600A

I3

4000A

IN

=
=

200A
13A

50

Reset ( + / - )

Navigation from one display to another is intuitive. The six buttons on the keypad
provide access to the menus and easy selection of values. When the setting cover
is closed, the keypad may no longer be used to access the protection settings, but
still provides access to the displays for measurements, histories, indicators, etc.

Measurements .......................................................................
Instantaneous values
The value displayed on the screen is refreshed every second.
Minimum and maximum values of measurements are stored in memory
(minimeters and maximeters).

currents
Default display

Display of a maximum
current

I rms

U inst.
U12 =
U23 =
U31 =
U1N =
U2N =
U3N =

E46263

E46262

I max rms

400V
404V
401V
230V
229V
233V

Pinst.
P

(kW)
+2180

(kVAR)
-650

(kVA)
+2280

A
A
A
A

1
2
e-fault
1
2
e-fault

3
N
e-leakage
3
N
diffrentiel

V
V
V
%

12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3

voltages
U rms
V rms
U average rms
U imbalance

power, energy
P active, Q reactive, S apparent
E active, E reactive, E apparent

W, Var, VA
Wh, VARh, VAh

power factory

PF

totals
totals consumed - supplied
totals consumed
totals supplied
total

frequencies

F (Hz)

Display of a power

E46265

E47305

Display of a voltage

P
Pdemand
demande
PActive P (kW)
2180 kW +2180
QRactive (kVAR)
Q
- 650 kVAR -650

60.0

S
(kVA)
Apparente+2280
S
2280 kVA

Display of a frequency

Display of a demand power

Hz

Demand metering
The demand is calculated over a fixed or sliding time window that may be
programmed from 5 to 60 minutes. According to the contract signed with the power
supplier, an indicator associated with a load shedding function makes it possible to
avoid or minimise the costs of overrunning the subscribed power. Maximum
demand values are systematically stored and time stamped (maximeter).
currents
I demand
I max demand

A
A
A
A

1
2
e-fault
1
2
e-fault

3
N
e-leakage
3
N
e-leakage

power
P, Q, S demand
P, Q, S max demand

W, Var, VA
W, Var, VA

totals
totals

Minimeters and maximeters


Only the current and power maximeters may be displayed on the screen.

Trip
history
Ir
03/08/1999

Isd
27/07/1999

Umax
30/06/1999

Display of a tripping history

E46260

E46259

Histories .................................................................................

Trip
03/08/1999
12:02:36
Ir =

1000A

I1 =

1200A

I2 =
I3 =

1430A
1060A

IN =

53A

Display after tripping

The last ten trips and alarms are recorded in two separate history files that may be
displayed on the screen.
c tripping history:
v type of fault
v date and time
v values measured at the time of tripping (interrupted current, etc.).
c alarm history:
v type of fault
v date and time
v values measured at the time of the alarm..

Maintenance indicators ........................................................


A number of maintenance indicators may be called up on the screen:
c contact wear
c operation counter:
v cumulative total
v total since last reset

22

Masterpact

Schneider Electric

E47070

POWERLOGIC System Manager Demo


Edit View Setup Control Display Reports

File

Time
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98

Ready

5 seconds

Event
08:49:06
08:49:01
08:48:38
08:48:30
08:46:16
08:39:19
08:39:06
08:39:06
08:38:57
08:30:44
08:24:31
08:24:30
08:24:15
08:18:07
07:54:05
07:53:55
07:53:54
07:51:46
07:51:33
07:51:29
07:50:17
07:50:17
07:49:13
07:48:57
07:48:38
07:48:22
07:46:54
07:44:59
07:44:59

With the communication option

Tools Window Help

Sampling Mode : MANUAL

Module

Net Server Shutdown


User Log Out
DB Table Change
DB Table Change
DB Table Change
User Log In
Security Check
Net Server Started
User Log In
Net Server Shutdown
Security Check
Net server Started
User Log IN
IPC Error
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
Setup: Device Name Change
Setup: Device Added
Setup: Device Name Change
Setup: Device Added
User Log In
Security Check
Net Server Started

User : master
User : master
User : master
User : master
User : master
User : master
Key Status : Key Found
User : master

PowerLogic Network
SMS-3000 Client
Alarm Setup
Alarm Setup
Alarm Setup
SMS-3000 Client
PowerLogic Network
Level : 1
PowerLogic Network
Event/Alarm/Network
User : master
Level : 1
PowerLogic Network
Key Status : Key Found
PowerLogic Network
User : master
Level : 1
PowerLogic Network
Event/Alarm/Network
User : NA
Err : 109
SMS-3000 Client
User : -1
Logger Template Devices Logger Setup
User : -1
Logger Template Topics Logger Setup
User : -1
Logger Templates
Logger Setup
User : master
Analog Levels Assigned Alarm Setup
User : master
Analog Levels Template Alarm Setup
User : master
Functions
Alarm Setup
User : master
Digital Levels Assigned
Alarm Setup
User : master
Analog Levels Assigned Alarm Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : Transformer Temp User : master
Device Setup
Device : Transformer Temp User :master
Device Setup
User : master
User Level : 1
SMS-3000 Client
Key Status : Key Found
PowerLogic Network
User :master
Level : 1
PowerLogic Network

ONLINE: DEMO

Level : 1
User level : 1
TOD Event Tasks
Tasks
TOD Events
User level : 1

No working system

Display of an event log on a supervisor

9:30

Additional measurements, maximeters and minimeters


Certain measured or calculated values are only accessible with the COM
communication option:
c I peak / r, (I1 + I2 + I3)/3, I imbalance
c load level in % Ir
c total power factor
The maximeters and minimeters are available only via the COM option for use with
a supervisor.
Event log
All events are time stamped.
c trips
c beginning and end of alarms
c modifications to settings and parameters
c counter resets
c system faults:
v fallback position
v thermal self-protection
c loss of time
c overrun of wear indicators
c test-kit connections
c etc.
Maintenance register
Used as an aid in troubleshooting and to better plan for device maintenance
operations.
c highest current measured
c operation counter
c number of test-kit connections
c number of trips in operating mode and in test mode
c contact-wear indicator.

Additional technical characteristics


Setting the display language
System messages may be displayed in six different languages. The desired language is
selected via the keypad.
Protection functions
All current-based protection functions require no auxiliary source. Voltage-based
protection functions are connected to AC power via a voltage measurement input built
into the circuit breaker.
Measurement functions
Measurement functions are independent of the protection functions.
The high-accuracy measurement module operates independently of the protection
module, while remaining synchronised with protection events.
Measurement-calculation mode
c measurement functions implement the new zero blind time concept which consists in
continuously measuring signals at a high sampling rate. The traditional blind window
used to process samples no longer exists. This method ensures accurate energy
calculations even for highly variable loads (welding machines, robots, etc.).
c energies are calculated on the basis of the instantaneous power values, in two
manners:
v the traditional mode where only positive (consumed) energies are considered
v the signed mode where the positive (consumed) and negative (supplied) energies are
considered separately.
Accuracy of measurements (including sensors)
cvoltage (V) 1%
c current (A) 1.5%
c frequency (Hz) 0.1 Hz
c power (W) and energy (Wh) 2.5%
Stored information
The fine setting adjustments, the last 100 events and the maintenance register remain in
the control-unit memory even when power is lost.
Time-stamping
Time-stamping is activated only if an external power supply module is present (max. drift
of 1 hour per year).
Reset
An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum
data, peak values, the counters and the indicators.

23

Masterpact

Schneider Electric

Control units
Micrologic H harmonics

Micrologic H control units include all the


functions offered by Micrologic P.
Integrating significantly enhanced
calculation and memory functions, the
Micrologic H control unit offers in-depth
analysis of power quality and detailed
event diagnostics. It is intended for
operation with a supervisor.

In addition to the Micrologic P functions, the Micrologic H control unit offers:


c in-depth analysis of power quality including calculation of harmonics and the
fundamentals
c diagnostics aid and event analysis through waveform capture
c enhanced alarm programming to analyse and track down a disturbance on the
AC power system

E46257

Functions
and characteristics

Measurements .......................................................................

(A)

The Micrologic H control unit offers all the measurements carried out by Micrologic
P, with in addition:
c phase by phase measurements of:
v power, energy
v power factors
c calculation of:
v current and voltage total harmonic distortion (THD)
v current, voltage and power fundamentals (50 Hz)
v current and voltage harmonics up to the 51st order.
Instantaneous values displayed on the screen

(V)

I rms

Micrologic 7.0 H

I
U
P
E

currents

(kW)

I max rms

(kWh)

A
A
A
A

1
2
e-fault
1
2
e-fault

3
N
e-leakage
3
N
e-leakage

V
V
V
%

12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3

voltages
U rms
V rms
U average rms
U imbalance

Harmonics

power, energy
P active, Q reactive, S apparent
E active, E reactive, E apparent

W, Var, VA
Wh, VARh, VAh

power factor

PF

totals 1
2
3
totals consumed - supplied
totals consumed
totals supplied
total 1
2
3

frequencies
F

long time

Ir
.7
.6
.5
.4

x In

power-quality indicators

instantaneous

short time

setting

In
(A)

3
2
1
.5

total fundamentals
THD
U and I harmonics

@ 6 Ir

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd
(s)

.4 .4 .3
.2
.1
0
I t off

.3
.2
.1

on

delay

t
(ms)
230
10
140
20
30
60
7

Hz

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

Ii

6 8 10
4
12
3
15
off
2
x In

U I
U I
3 5

%
amplitude

P Q S
7

11 13

Harmonics 3, 5, 7, 9, 11 and 13, monitored by electrical utilities, are displayed on the


screen.

Demand measurements
Similar to the Micrologic P control unit, the demand values are calculated over a
fixed or sliding time window that may be set from 5 to 60 minutes.

test

350

currents
800

I demand

earth leakage

I max demand

A
A
A
A

1
2
e-fault
1
2
e-fault

3
N
e-leakage
3
N
e-leakage

puissances
P, Q, S demand
P, Q, S max demand

W, Var, VA
W, Var, VA

totals
totals

Maximeters
Only the current maximeters may be displayed on the screen.

Histories and maintenance indicators


These functions are identical to those of the Micrologic P.

Note.
Micrologic H control units come with a non-transparent
lead-seal cover as standard.

24

Masterpact

Schneider Electric

E47071

POWERLOGIC System Manager Demo


File Edit View Setup Control Display

Reports

Time

With the communication option

Tools Window Help

Sampling Mode : MANUAL

5 seconds

Event

Module

Phase A-N Voltage - Harmonics Analysis


Phase 1-N

1,20

Harmonics(RMS)

Fundamental:

1,00

RMS:
RMS-H:

% Fundamental

0,80

Peak:
CF:
THD:

H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07

0,60
OK

0,40

0,20
0,00
H2

H3

H4

H5

H6

H7

H8

H9

H10

H11

H12

Harmonics

ONLINE: DEMO

Ready

No working system

9:30

E47072

Display of harmonics up to 12th order.


POWERLOGIC System Manager Demo
Edit View Setup Control Display Reports

File

Tools Window Help


5 seconds

Sampling Mode : MANUAL

Phase A-N Voltage

Phase A Current

167

642

83

321

0
17

-83

33

50

66

17

-321

33

50

66

Your Specific Device - Phase A-N Voltage

-167

-642

Harmonics(RMS)

Fundamental:

Phase B-N Voltage

118.08

RMS:

118.11

RMS-H:

167

2.38

Peak:

83

166.86

CF:

1.41

0
17

-83

33

50

THD:

2.02

-167

H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07

Additional measurements, maximeters and minimeters


Certain measured or calculated values are only accessible with the COM
communication option:
c I peak / r, (I1 + I2 + I3)/3, I imbalance
c load level in % Ir
c power factor (total and per phase)
c voltage and current THD
c K factors of currents and average K factor
c crest factors of currents and voltages
c all the fundamentals per phase
c fundamental current and voltage phase displacement
c distortion power and distortion factor phase by phase
c amplitude and displacement of current and voltage harmonics 3 to 51.
The maximeters and minimeters are available only via the COM option for use with
a supervisor.
Waveform capture
The Micrologic H control unit stores the last 12 cycles of each instantaneous
current or voltage measurement. On request or automatically on programmed
events, the control unit stores the waveforms. The waveforms may be displayed in
the form of oscillograms by a supervisor via the COM option.
Enhanced alarm programming
Each instantaneous value can be compared to user-set high and low thresholds.
Overrun of a threshold generates an alarm. An alarm or combinations of alarms
can be linked to programmable actions, including circuit-breaker opening,
activation of a M2C or M6C contact, selective recording of measurements in a log,
waveform capture, etc.
Event log and maintenance registers
The Micrologic H offers the same event log and maintenance register functions as
the Micrologic P.

OK

ONLINE: DEMO

Ready

No working system

9:30

E47070

Waveform capture
POWERLOGIC System Manager Demo
Edit View Setup Control Display Reports

File

Additional technical characteristics


Tools Window Help

Sampling Mode : MANUAL

Time
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98
04/21/98

Ready

Log

5 seconds

Event
08:49:06
08:49:01
08:48:38
08:48:30
08:46:16
08:39:19
08:39:06
08:39:06
08:38:57
08:30:44
08:24:31
08:24:30
08:24:15
08:18:07
07:54:05
07:53:55
07:53:54
07:51:46
07:51:33
07:51:29
07:50:17
07:50:17
07:49:13
07:48:57
07:48:38
07:48:22
07:46:54
07:44:59
07:44:59

Module

Net Server Shutdown


User Log Out
DB Table Change
DB Table Change
DB Table Change
User Log In
Security Check
Net Server Started
User Log In
Net Server Shutdown
Security Check
Net server Started
User Log IN
IPC Error
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
DB Table Change
Setup: Device Name Change
Setup: Device Added
Setup: Device Name Change
Setup: Device Added
User Log In
Security Check
Net Server Started

User : master
User : master
User : master
User : master
User : master
User : master
Key Status : Key Found
User : master

PowerLogic Network
SMS-3000 Client
Alarm Setup
Alarm Setup
Alarm Setup
SMS-3000 Client
PowerLogic Network
Level : 1
PowerLogic Network
Event/Alarm/Network
User : master
Level : 1
PowerLogic Network
Key Status : Key Found
PowerLogic Network
User : master
Level : 1
PowerLogic Network
Event/Alarm/Network
User : NA
Err : 109
SMS-3000 Client
User : -1
Logger Template Devices Logger Setup
User : -1
Logger Template Topics Logger Setup
User : -1
Logger Templates
Logger Setup
User : master
Analog Levels Assigned Alarm Setup
User : master
Analog Levels Template Alarm Setup
User : master
Functions
Alarm Setup
User : master
Digital Levels Assigned
Alarm Setup
User : master
Analog Levels Assigned Alarm Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : MicroLogic Breaker User :master
Device Setup
Device : Transformer Temp User : master
Device Setup
Device : Transformer Temp User :master
Device Setup
User : master
User Level : 1
SMS-3000 Client
Key Status : Key Found
PowerLogic Network
User :master
Level : 1
PowerLogic Network

ONLINE: DEMO

Level : 1
User level : 1
TOD Event Tasks
Tasks
TOD Events
User level : 1

No working system

9:30

Setting the display language


System messages may be displayed in six different languages. The desired language is
selected via the keypad.
Protection functions
All current-based protection functions require no auxiliary source. Voltage-based
protection functions are connected to AC power via a voltage measurement input built
into the circuit breaker.
Measurement functions
Measurement functions are independent of the protection functions.
The high-accuracy measurement module operates independently of the protection
module, while remaining synchronised with protection events.
Measurement-calculation mode
An analogue calculation function dedicated to measurements enhances the accuracy of
harmonic calculations and the power-quality indicators. The Micrologic H control unit
calculates electrical magnitudes using 1.5 x In dynamics (20 x In for Micrologic P).
Measurement functions implement the new zero blind time concept
Energies are calculated on the basis of the instantaneous power values, in the traditional
and signed modes.
Harmonic components are calculated using the discrete Fourier transform (DFT).
Accuracy of measurements (including sensors)
cvoltage (V) 1%
c current (A) 1.5%
c frequency (Hz) 0.1 Hz
c power (W) and energy (Wh) 2.5%
c total harmonic distortion 1%
Stored information
The fine-setting adjustments, the last 100 events and the maintenance register remain in
the control-unit memory even when power is lost.
Time-stamping
Time-stamping is activated only if an external power supply module is present (max. drift
of 1 hour per year).
Reset
An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum
data, peak values, the counters and the indicators.

25

Masterpact

Schneider Electric

E47477

External sensor (CT)

056467

Functions
and characteristics

Rectangular sensor for


source return protection

Micrologic control units


Accessories and test equipment

External sensors
External sensor for earth-fault and neutral protection
The sensors, used with the 3P circuit breakers, are installed on the neutral
conductor for:
c neutral protection (with Micrologic P and H)
c residual type earth-fault protection (with Micrologic A, P and H)..
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
c NT06 NT16: TC 400/1600
c NW08 NW20: TC 400/2000
c NW25 NW40: TC 1000/4000
c NW40b NW63: TC 2000/6300.
For double neutral protection (2 IN,) the sensor rating must be compatible with the
measurement range: 2 x IN.
Rectangular sensor for earth-leakage protection
The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection. Rectangular
sensors are available in two sizes.
Inside dimensions (mm)
c 280 x 115 up to 1600 A for Masterpact NT
c 470 x 160 up to 4000 A for Masterpact NW.
External sensor for source ground return protection
The sensor is installed around the connection of the transformer neutral point to
earth and connects to the Micrologic 6.0 control unit via an MDGF module to
provide the source ground return (SGR) protection.
Voltage measurement inputs
Voltage measurement inputs are required for power measurements and for earthleakage protection.
As standard, the control unit is supplied by internal voltage measurement inputs
placed downstream of the pole for voltages between 100 and 690 V AC. On
request, it is possible to replace the internal voltage measurement inputs by an
external connector which enables the control unit to draw power directly from the
distribution system upstream of the circuit breaker.

056412

Long-time rating plug


Four interchangeable plugs may be used to limit the long-time threshold setting
range for higher accuracy.
As standard, control units are equipped with the 0.4 to 1 plug.
Setting ranges

025171

025173

standard
Ir = In x
Low-setting option Ir = In x
high-setting option Ir = In x
off plug

0,4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1


0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8
0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1
no long-time protection

External power-supply module


The external power-supply module makes it possible to use the display even if the
circuit breaker is open or not supplied (for the exact conditions of use, see the
electrical diagrams part of this catalogue).
This module powers both the control unit and the M2C and M6C programmable
contacts.
With the Micrologic A control unit, this module makes it possible to display currents
of less than 20% of In.
With the Micrologic P and H, it can be used to display fault currents after tripping
and to time-stamp events (alarms and trips).
Characteristics
c power supply:
v 110/130, 200/240, 380/415 V AC (+ 10% - 15%), consumption 10 VA
v 24/30, 48/60, 100/125 V DC (+20% -20%), consumption 10 W
c output voltage: 24 V DC; power delivered: 5 W / 5 VA
c ripple < 5%
c class 2 isolation.

Battery module
The battery module makes it possible to use the display even if the power supply to
the Micrologic control unit is interrupted.
Characteristics:
c battery run-time: 12 hours (approximately)
c mounted on vertical backplate or symmetrical rail

26

Masterpact

Schneider Electric

056429

Spare parts
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
When the cover is closed:
c it is impossible to modify settings using the keypad unless the settings lockout
pin on the cover is removed.
c the test connector remains accessible.
c the test button for the earth-fault and earth-leakage protection function remains
accessible.
Characteristics
c transparent cover for basic Micrologic and Micrologic A control units
c non-transparent cover for Micrologic P and H control units.
Spare battery
A battery supplies power to the LEDs identifying the tripping causes. Battery
service life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.

Lead-seal cover

056413

M2C, M6C programmable contacts


056430

These contacts are optional equipment for the Micrologic P and H control units.
They are described with the indication contacts for the circuit breakers.
characteristics
minimum load
breaking
capacity (A)
p.f.: 0.7

M2C

M2C/M6C
V AC
V DC

M6C

240
380
24
48
125
250

10mA/24V
5
3
1.8
1.5
0.4
0.15

M2C: 24 V DC power supplied by control unit (consumption 100 mA).


M6C: external 24 V DC power supply required (consumption 100 mA).

056466

Test equipment

Portable test kit

Mini test kit


The autonomous hand-held mini test kit may be used to:
c check operation of the control unit and the tripping and pole-opening system by
sending a signal simulating a short-circuit
c supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units).
Power source: standard LR6-AA battery.
Portable test kit
The portable test kit is available in two versions:
c the autonomous version with built-in keypad and display
c the complete version controlled by a PC.
The autonomous version may be used to check:
c the mechanical operation of the circuit breaker
c the electrical continuity of the connection between the circuit breaker and the
control unit
c operation of the control unit:
v display of settings
v operating tests on the ASIC electronic component
v automatic and manual tests on protection functions
v test on the zone-selective interlocking (ZSI) function
v inhibition of the earth-fault protection
v inhibition of the thermal memory.
The complete version controlled by a PC offers in addition:
c comparison of the real tripping curve with the catalogue curves available on the
PC
c reset of the M2C / M6C contacts and indications
c reading and modification of settings and counters
c reading of histories and logs
c waveform capture
c analysis of harmonics.

27

Masterpact

Schneider Electric

Communication
COM option in Masterpact

The COM option is required for integration


of the circuit breaker or switch-disconnector
in a supervision system.
Masterpact uses the Digipact or Modbus
communications protocol for full
compatibility with the SMS PowerLogic
electrical-installation management systems.
An external gateway is available for
communication on other networks:
c Profibus
c Ethernet

For fixed devices, the COM option is made up of:


c a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and its
kit for connection to XF and MX communicating voltage releases.
For drawout devices, the COM option is made up of:
c a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and its
kit for connection to XF and MX communicating voltage releases
c a "craddle" communication module supplied separately with its set of sensors
(CE, CD and CT contacts).
Status indication by the COM option is independent of the device indication
contacts. These contacts remain available for conventional uses.
Digipact or Modbus Device communication module
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
Digipact or Modbus craddle communication module
This module is independent of the control unit. With Modbus "craddle"
communication module, this module makes it possible to address the craddle and
to maintain the address when the circuit breaker is in the disconnected position.
Consumption: 30 mA, 24 V.
XF and MX communicating voltage releases
The XF and MX communicating voltage releases are equipped for connection to
the "device" communication module.
The remote-tripping function (second MX or MN) are independent of the
communication option. They are not equipped for connection to the "device"
communication module.

Digipact device
communication module.

communication
Bus

++
CCM

CT

modb

us

CE

E47073

Digipact craddle
communication module

CD

056431
056401

Functions
and characteristics

CE
C

056431

CT
C
OF
SDE
PF
CH

Modbus device
communication module

CD
C
MX
XF

4
5

E45183

3
Modbus craddle
communication module

1
2
3
4
5

Device communication module


Craddle communication module
OF, SDE, PF and CH device sensors
CE, CD and CT craddle sensors
MX and XF release

: hard wire
: communication bus

Note: eco COM


The eco COM Modbus is intended to fit the circuit breaker with module display
(DMB300, DMC300).

28

Masterpact

Schneider Electric

POWERLOGIC System Manager Demo


Edit View Setup Control Display Reports

File

Time

The Masterpact switch-disconnectors are compatible only with the Digipact COM
option.

Tools Window Help


5 seconds

Sampling Mode : MANUAL

Event

Module

Phase A-N Voltage - Harmonics Analysis


Phase 1-N

1,20

Harmonics(RMS)

Fundamental:

1,00

RMS:
RMS-H:

0,80
% Fundamental

E47071

Overview of functions

Peak:
CF:
THD:

H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07

0,60
OK

0,40

0,20
0,00
H2

H3

H4

H5

H6

H7

H8

H9

H10

H11

The Masterpact circuit breakers are compatible with the Digipact or Modbus COM
option.
The COM option may be used with all types of control units to:
c identify the device
c indicate status conditions
c control the device.
Depending on the different types of Micrologic (A, P, H) control units, the COM
option also offers:
c setting of the protection and alarms functions
c analysis of the AC-power parameters for operating-assistance and maintenance
purposes

H12

Harmonics

Ready

ONLINE: DEMO

No working system

9:30

switch-disconnector with circuit breaker with


communication bus
communication bus
Digipact

Modbus

Digipact

Modbus

c
-

A
A

P
P

H
H

A
A

A
A

P
P

H
H

c
c
c
c

A
A
A
A
A

P
P
P
P
P

c
-

device identification
address
calibre
type of device
type of control unit
type of long-time rating plug

A
A

P
P
P
P
P

H
H
H
H
H

H
H
H
H
H

A
A
A
A
A

P
P
P
P
P

H
H
H
H
H

P
P

H
H

H
H

P
P
P

H
H
H
H

P
P

H
H

status indications
ON/OFF OF
spring charged CH
ready to close PF
fault-trip SDE
connected/disconnected/test
position CE/CD/CT

commandes
opening / closing MX/XF
spring charging
reset of the mechanical
indicator

protections and alarms settings


reading of protections settings
writing of fine settings in the range
imposed by the adjustment dials
reading/writing of alarms (dlestage, relestage, M2C)
reading/writing of alarms personnalisables

operating and maintenance aids


measurement
current
voltages, frequency, power, etc.
power quality: fundamental, harmonics
programming of demand metering
fault readings
type of fault
interrupted current
waveform capture
on faults
on demand or programmed
histories and logs
trip history
alarm history
event logs
indicators
counter operation
contact wear
maintenance register

P
P

H
H

H
H

P
P
P

H
H
H

P
P
P

H
H
H

Note.
See the description of the Micrologic control units for further details on protection and
alarms, measurements, waveform capture, histories, logs and maintenance indicators.

29

Masterpact

Schneider Electric

Communication
Masterpact in a communication
network

E67968

Functions
and characteristics

Software

Communication
interface

RS 232C,Ethernet
RS 485

Communication
Bus
IN
LIN GER
MERSV

JBus

pulsar

BBus

com
error

com
24V

Data concentrator
DC150

OK
error

3
N1

N1

Device

OF24

MN

Com
CD3
CE6

CD2
CE5

UC1

UC2

UC3

UC4

M2C

UC2

SDE2

CE3

CE2

MX1

XF

PF

CD3

CD1
CD2
814
824
812
834
822
811
832
821
831

MCH

OC24

OF23
OC23

OF22
OC22

OF21
OC21

CE1

CD1
CE4

CE1
CE2
314
CE3
324
312
SDE1
334
322
311
332
K2 84
321
82
UC4 M2C/M6C
Q3 184/
331
UC3
V3 484/ 474/ Q2 182
K1 81
UC2
2+
V2
Q1 181/
M3 F
UC1
Com 6 Z5 M1 M2 3 T4 VN - V1 471/
E5 E 4 Z3 Z4 T T1 T2 F1
E3 E E2 Z1 Z2
E1

MCHB
PF
2
XF
254
B3
MX1
A2
252
MN/MX2 12 C2
B1
A3
251
D2/ C 13 C3
A1
/C
C1
D1/ C11

OF14
OC14

OF13
OC13

OF12

OF11

OC12
OF24

CT1
CT2
914
CT3
924
912
OF1
934
922
OF2
911
14
932
OF3
921
24
12
OF4
931
OF11114 44 34 32 22
11
OF12124
21
42
OF13134
31
112
OF14144
41
122
OF21214
111
132
OF22224
121
142
OF23234
131
212
OF24244
141
222
211
232
221
242
231
241

Reset

push
push

70

Ig
Isd I n
Ii

Ap

CD2
CE5

NX 32

ON

Ics =

UC3

UC4

M2C

UC2

SDE2

CE3

CE2

MX1

XF

PF

CD1
CD2
814
824
812
834
822
811
832
821
831

MCH

OC24

OF23
OC23

OF22
OC22

OF21
OC21

CE1

CE1
CE2
314
CE3
324
312
SDE1
334
322
311
332
K2 84
321
82
UC4 M2C/M6C
Q3 184/
331
UC3
V3 484/ 474/ Q2 182
K1 81
UC2
2+
V2
Q1 181/
M3 F
UC1
Com 6 Z5 M1 M2 3 T4 VN - V1 471/
E5 E 4 Z3 Z4 T T1 T2 F1
E3 E E2 Z1 Z2
E1

MCHB
PF
2
XF
254
B3
MX1
A2
252
MN/MX2 12 C2
B1
A3
251
D2/ C 13 C3
A1
/C
C1
D1/ C11

Reset

Icu (kA)
100
100
85

OF14
OC14

OF13
OC13

OF12

OF11

OC12

CT1
CT2
914
CT3
924
912
OF1
934
922
OF2
911
14
932
OF3
921
24
12
OF4
931
OF11114 44 34 32 22
11
OF12124
21
42
OF13134
31
112
OF14144
41
122
OF21214
111
132
OF22224
121
142
OF23234
131
212
OF24244
141
222
211
232
221
242
231
241

100%

push
push

70

NX 32

ON

Icu

Ir

Ig
Isd I n
Ii

Ap

reset

Ics =

Icu (kA)
100
100
85

100%

Icu
50/60Hz

O OFF

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

Icw 85kA/1s

cat.B

ed
discharg

50/60Hz

O OFF

H2

Ue (V)
220/440
525
690

OFF

Micrologic

Icw 85kA/1s

cat.B

ed
discharg

UC2

H2

Ue (V)
220/440
525
690

OFF

reset

UC1

CD1
CE4

CD3

Micrologic

Ir

MN

Com
CD3
CE6

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI

VDE

UTE

3
125

VDE

3
125

Digipact Bus

ModBUS Bus
volets
shutters

volets
shutters

Test

Test

Masterpact

Masterpact

Devices
Circuit breakers equipped with Micrologic control units may be connected to either
a Digipact or Modbus communication bus. The information made available
depends on the type of Micrologic control unit (A, P or H) and on the type of
communication bus (Digipact or Modbus).
Switch-disconnectors may be connected exclusively to the Digipact communication
bus.

Communication bus
Digipact
The Digipact bus is the internal bus of the low-voltage switchboard in which the
Digipact communicating devices are installed (Masterpact with Digipact COM,
PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data
concentrator (see the Powerlogic System catalogue).
Addresses
Addressing is carried out by the DC150 data concentrator.
Number of devices
The maximum number of devices that may be connected to the Digipact bus is
calculated in terms of communication points. These points correspond to the
amount of traffic the bus can handle. The total number of points for the various
devices connected to a single bus must not exceed 100.
If the required devices represent more than 100 points, add a second Digipact
internal bus.
Communicating device
DC150 data concentrator
Micrologic + Digipact COM
PM150
SC150
UA150

Number of points
4
4
4
4
4

Length of bus
The maximum recommended length for the Digipact internal bus is 200 meters.
Bus power source
Power is supplied by the DC150 data concentrator (24 V)..

30

Masterpact

Schneider Electric

Modbus
The Modbus RS485 (JBus) system is an open bus on which communicating
Modbus devices (Masterpact with Modbus COM, PM300, Sepam, Vigilohm, etc.)
are installed. All types of PLCs and microcomputers may be connected to the bus.
Addresses
The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255).
The device communication module comprises three addresses linked to:
b circuit-breaker manager;
b measurement manager;
b protection manager.
The craddle communication module comprises one address linked to:
b the craddle manager.
The division of the system into four managers secures data exchange with the
supervision system and the circuit-breaker actuators.
The manager addresses are automatically derived from the circuit-breaker address
@xx entered via the Micrologic control unit (the default address is 47).
logic addresses
@xx
@xx + 50
@xx + 200
@xx + 100

Circuit-breaker manager
Craddle manager
Measurement managers
Protection manager

(1 to 47)
(51 to 97)
(201 to 247)
(101 to 147)

Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Masterpact with Modbus COM, PM300, Sepam,
Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data
exchanged and the desired response time. The RS485 physical layer offers up to
32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device).
A drawout device uses two connection points (communication modules on the
device and on the craddle).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20% ripple, insulation class II).

Communication interface
The Modbus bus may be connected to the central processing device in any of
three manners:
b direct link to a PLC. The communication interface is not required if the PLC is
equipped with a Modbus port;
b direct link to a computer. The Modbus (RS485) / Serial port (RS232)
communication interface is required;
b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP
(Ethernet) communication interface is required.

Software
To make use of the information provided by the communicating devices, software
with a Modbus driver must be used.

Micrologic utilities
This is a set of Modbus drivers that may be used with a PC to:
b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software)
application;
b read/write the settings with the RSS (Remote Setting Software) application;
b remotely control (ON / OFF) the device with the CSS (Control Command
Software) application.
These softwares are available upon request.

SMS (System Manager Software)


SMS is a software to monitor LV and/or MV electrical energy.
The SMS family includes a software range depending on the application and
function, from single product monitoring to the management of a multiple building:
c Power Meter and Circuit Monitor units
c LV devices
c Sepam units.

31

Masterpact

Schneider Electric

Connections
Overview of solutions

Functions
and characteristics

Rear connection
vertical

056432

056433

horizontal

Simply turn a horizontal rear connector 90 to make it a vertical connector.

056434

Front connection

056436

056435

Mixed connection

056437

Three types of connection are available:


c vertical or horizontal rear connection
c front connection
c mixed connection.
The solutions presented are similar in
principle for all Masterpact NT and NW
fixed and drawout devices..

Note.
Masterpact circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors, requiring no particular treatment.

32

Masterpact

Schneider Electric

Optional accessories

Masterpact NT06 to NT16


fixed
rear
connection

fixed

front
connection

rear
connection

front
connection

drawout
rear
connection

front
connection

rear
connection

E47064

front
connection

E46427

E46428

E79058

Interphase
barriers

E46428

Cable lug
adapters

E46426

E46426

Vertical connection
adapters

E46427

Bare-cable connectors
and connector shield

Masterpact NW08 to NW63


drawout

E46428

Type of accessory

max. 4000 A

E46431

E46431

Spreaders

E46889

Disconnectable
front-connection
adapter

E47068

E47067

E47066

Safety shutters
with padlocking

Arc chute screen

E70745

Shutter position
indication and locking

Masterpact M replacement kit


A set of connection parts is available to allow replacement of a Masterpact M08 to
M32 circuit breaker by a Masterpact NW without modifying the busbars (please
consult us).

Mounting on a switchboard backplate using special brackets


Masterpact NT and NW fixed front-connected circuit breakers can be installed
on a backplate without any additional accessories.
Masterpact NW circuit breakers require a set of special brackets.

33

Masterpact

Schneider Electric

056438

Functions
and characteristics

Connections
Optional accessories

Bare-cable connectors and connector shield


The connectors can be mounted on fixed front-connected devices to allow
connection using bare cables. They are supplied with a connector shield.
They are designed to connect four 240 mm2 cables each.

056440

Vertical-connection adapters

056441

Mounted on front-connected devices or craddle, the adapters facilitate connection


to a set of vertical busbars.

Cable-lug adapters
Cable-lug adapters are used in conjunction with vertical rear connectors or with
vertical-connection adapters.
They can be used to connect a number of cables fitted with lugs.
To ensure adequate mechanical strength, the connectors must be secured together
via spacers.

056415

Interphase barriers
These barriers are flexible insulated partitions used to reinforce isolation of
connection points in installations with busbars, whether insulated or not.
For Masterpact NT/NW devices, they are installed vertically between rear
connection terminals.

056442

Spreaders

E70746

Mounted on the front or rear connectors, spreaders are used to increase the
distance between bars in certain installation configurations.

Arc chute screen


For Masterpact NT fixed, front connected and using vertical-connection adapters
front oriented, it is mandatory to install arc chute screen in order to comply with the
safety perimeter.
I
O
push

push

ON

OFF

rged
discha

O OFF

34

Masterpact

Schneider Electric

056443

Disconnectable front-connection adapter

056445

Mounted on a fixed front-connected device, the adapter simplifies replacement of a


fixed device by enabling fast disconnection from the front.

Safety shutters

E47476

Mounted on the craddle, the safety shutters automatically block access to the
disconnecting contact cluster when the device is in the disconnected or test
positions (degree of protection IP 20) When the device is removed from its craddle,
no live parts are accessible.
The shutter-locking system is made up of a moving block that can be padlocked
(padlock not supplied). The block:
* prevents connection of the device
* locks the shutters in the closed position
For Masterpact NW08 to NW63
A support at the back of the craddle is used to store the blocks when they are not
used.
* 2 blocks for NW08 to NW40
* 4 blocks for NW40b to NW63.

Shutter position indication and locking on front face


This option located on the craddle front plate indicates that the shutters are closed.
It is possible to independently or separately padlock the two shutters using one to
three padlocks (not supplied).

35

Masterpact

Schneider Electric

Locking
On the device

E47062

Functions
and characteristics

3
NW

H1
1250 12kV

0V
Ui 100
8kV
Uimp

Uimp

Ue
(V)
220/240
480/690
gic
Microlo

Ir

Icu
(kA)
100
85

70

Ig
Isd I n
Ii

Ap

t
rese

I
O
push

push

OFF

disc

ON

harg

4
5
6

ed

O OFF

7
Ics =

IEC

Icu
100%

947-2

UTE VDE

012

BS CEI

UNE

NEMA

1 reset button for mechanical


trip indication
2 OFF pushbutton
3 OFF position lock
4 electrical closing
pushbutton
5 ON pushbutton
6 springs charged indication
7 pushbutton locking
8 contact position indication
9 operation counter

53

056448

056446

056447

Access to pushbuttons
protected by transparent
cover

Pushbutton locking using a


padlock

OFF position locking using a


padlock

Pushbutton locking
The transparent cover blocks access to the pushbuttons used to open and close
the device.
It is possible to independently lock the opening button and the closing button. The
locking device is often combined with a remote operating mechanism.
The pushbuttons may be locked using either:
c three padlocks (not supplied)
c lead seal
c two screws.

Device locking in the OFF position


The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
c using padlocks (one to three padlocks, not supplied)
c using keylocks (one or two different keylocks, supplied).
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
c one keylock
c one keylock mounted on the device + one identical keylock supplied separately
for interlocking with another device
c two different key locks for double locking.
Profalux and Ronis keylocks are compatible with each other.
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux, Kirk or Castell).
Accessory-compatibility
For Masterpact NT: 3 padlocks or 1 keylock
For Masterpact NW: 3 padlocks and/or 2 keylocks

056449

Cable-type door interlock

OFF position locking using a


keylock

This option prevents door opening when the circuit breaker is closed and prevents
circuit breaker closing when the door is open.
For this, a special plate associated with a lock and a cable is mounted on the right
side of the circuit breaker.
With this interlock installed, the source changeover function cannot be
implemented.

36

Masterpact

Schneider Electric

E47063

On the craddle

3
4
5
6
7
8
9

1
2
3
4
5
6
7

mismatch protection
door interlock
racking interlock
keylock locking
padlock locking
position indicator
craddle front plate
(accessible with cubicle
door closed)
8 racking-handle entry
9 reset button
10 racking-handle storage

10

056451

056450

Disconnected position locking


Mounted on the craddle and accessible with the door closed, these devices lock
the circuit breaker in the disconnected position in two manners:
c using padlocks (standard), up to three padlocks (not supplied)
c using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
c one keylock
c two different keylocks for double locking
c one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux, Kirk or Castell).

056417

Disconnected position
locking by padlocks

Disconnected position
locking by keylocks

Door interlock

Connected, disconnected and test position locking


The connected, disconnected and test positions are shown by an indicator.
The exact position is obtained when the racking handle blocks. A release button is
used to free it.
On request, the disconnected position locking system may be modified to lock
the circuit breaker in any of the three positions, connected, disconnected and
test.

Door interlock catch


Mounted on the right or left-hand side of the craddle, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be
closed without having to disconnect the circuit breaker.

056452

Racking interlock
Racking interlock

This device prevents insertion of the racking handle when the cubicle door is open.

Cable-type door interlock


This option is identical for fixed and drawout versions.

Racking interlock between crank and OFF pushbutton

056453

This option makes it necessary to press the OFF pushbutton in order to insert the
racking handle and holds the device open until the handle is removed.
Mismatch protection

Automatic spring discharge before breaker removal


This option discharges the springs before the breaker is removed from the craddle.

Mismatch protection
Mismatch protection ensures that a circuit breaker is installed only in a craddle with
compatible characteristics. It is made up of two parts (one on the craddle and one
on the circuit breaker) offering twenty different combinations that the user may
select.

37

Masterpact

Schneider Electric

056418

Functions
and characteristics

Indication contacts

Indication contacts are available:


c in the standard version for relay
applications
c in a low-level version for control of PLCs
and electronic circuits.
M2C and M6C contacts may be
programmed via the Micrologic P and H
control units.

ON/OFF indication contacts (OF)


Two types of contacts indicate the ON or OFF position of the circuit breaker:
c microswitch type changeover contacts for Masterpact NT
c rotary type changeover contacts directly driven by the mechanism for Masterpact
NW. These contacts trip when the minimum isolation distance between the main
circuit-breaker contacts is reached.
OF

NT

supplied as standard
maximum number
breaking capacity (A)
p.f.: 0.3
AC12/DC12

standard
V AC 240/380
480
690
V DC 24/48
125
250

ON/OFF indication contacts


(OF) (microswitch type)

low-level
V AC 24/48
240
380
V DC 24/48
125
250
* standard contacts: 10 A; optional contacts: 6 A.

NW

4
4
4
12
minimum load: 100mA/24V
6
10/6*
6
10/6*
6
6
2.5
10/6*
0.5
10/6*
0.3
3
minimum load: 2mA/15V DC
5
6
5
6
5
3
5/2.5
6
0.5
6
0.3
3

Fault-trip indication contacts (SDE)

056462

056419

Circuit-breaker tripping due to a fault is signalled by:


c a red mechanical fault indicator (reset)
c one changeover contact (SDE).
Following tripping, the mechanical indicator must be reset before the circuit breaker
may be closed.
ON/OFF indication contacts
(OF) (rotary type)

SDE

NT/NW

supplied as standard
maximum number
breaking capacity (A)
p.f.: 0.3
AC12/DC12

standard
V AC 240/380
480
690
V DC 24/48
125
250
low-level

Additional fault-trip
indication contacts (SDE)

V AC 24/48
240
380
V DC 24/48
125
250

1
2
minimum load: 100mA/24V
5
5
3
3
0.3
0.15
minimum load: 2mA/15V DC
3
3
3
3
0.3
0.15

Combined connected/closed contacts (EF)


The contact combines the device connected and the device closed
information to produce the circuit closed information.
Supplied as an option for Masterpact NW, it is mounted in place of the connector of
an additional OF contact.
056455

EF
Combined contacts

NW

maximum number
breaking capacity (A)
p.f.: 0.3
AC12/DC12

standard
V AC 240/380
480
690
V DC 24/48
125
250
low-level
V AC 24/48
240
380
V DC 24/48
125
250

38

Masterpact

8
minimum load: 100mA/24V
6
6
6
2.5
0.8
0.3
minimum load: 2mA/15V DC
5
5
5
2.5
0.8
0.3

Schneider Electric

056456

CE, CD and CT connected/


disconnected/test position
carriage switches

Connected, disconnected and test position carriage


switches

056413

Three series of optional auxiliary contacts are available for the craddle:
c changeover contacts to indicate the connected position (CE)
c changeover contacts to indicate the disconnected position (CD). This position
is indicated when the required clearance for isolation of the power and auxiliary
circuits is reached.
c changeover contacts to indicate the test position (CT). In this position, the
power circuits are disconnected and the auxiliary circuits are connected.
Additional actuators
A set of additional actuators may be installed on the craddle to change the
functions of the carriage switches.
M2C programmable
contacts: circuit-breaker
internal relay with two
contacts

NT
contacts
maximum number

standard
V AC 240
380
480
690
V DC 24/48
125
250

M6C programmable
contacts: circuit-breaker
external relay with six
independent changeover
contacts controlled from the
circuit breaker via a threewire connection.

low-level
V AC 24/48
240
380
V DC 24/48
125
250

M2C / M6C programmable contacts


These contacts, used with the Micrologic P and H control units, may be
programmed via the control unit keypad or via a supervisory station with the COM
communication option. They require an external power supply module.
They indicate:
c the type of fault
c instantaneous or delayed threshold overruns.
They may be programmed:
c with instantaneous return to the initial state
c without return to the initial state
c with return to the initial state following a delay.
characteristics

M2C/M6C
V AC
V DC

M2C: 24 V DC
power supplied
by control unit
(consumption
100 mA).

100mA/24V
5
3
1.8
1.5
0.4
0.15

240
380
24
48
125
250

M6C: external 24 V DC power supply required (consumption


100 mA).
E59470

484

474

minimum load
breaking
capacity (A)
p.f.: 0.7

E59469

S1

S2

S3

12 10 18 16

24 22

S4

S6

S5

S1 S2

11

14

20

471

056430

CE/CD/CT
3 3 3
9 0 0
6 3 0
6 0 3
minimum load: 100mA/24V
8
8
8
8
8
8
6
6
2.5
2.5
0.8
0.8
0.3
0.3
minimum load: 2mA/15V DC
5
5
5
5
5
5
2.5
2.5
0.8
0.8
0.3
0.3

standard
with additional actuators

breaking capacity (A)


p.f.: 0.3
AC12/DC12

NW

CE/CD/CT
3 2 1

39

Masterpact

Schneider Electric

Remote operation
Remote ON / OFF

Two solutions are available for remote


operation of Masterpact devices:
c a point-to-point solution
c a bus solution with the COM
communication option.

The remote ON / OFF function is used to remotely open and close the circuit
breaker. It is made up of:
c an electric motor (MCH) equipped with a springs charged limit switch contact
(CH)
c two voltage releases:
v a closing release (XF)
v an opening release (MX).
Optionally, other functions may be added:
c a ready to close contact (PF)
c an electrical closing pushbutton (BPFE)
c remote reset following a fault.
A remote-operation function is generally combined with:
c device ON / OFF indication (OF)
c fault-trip indication (SDE).

056407

Functions
and characteristics

E46041

Wiring diagram of a point-to-point remote ON / OFF function

spring
charged
B3

opening
order

closing
order

B2

C2

ready
to close
A2

252

fault
254

82

open
84

closed
12

14

MCH
PF
MX

OF1
SDE

XF

CH
B1

C1

A1

251

81

11

E46042

Wiring diagram of a bus-type remote ON / OFF function

spring
charged
B3

opening
order
B2
C2

closing
order
A2
C3

A3

MCH

MXcom

XFcom

CH

Note:
An opening order always takes priority over a closing
order.
If opening and closing orders occur simultaneously, the
mechanism discharges without any movement of the
main contacts. The circuit breaker remains in the open
position (OFF).
In the event of maintained opening and closing orders,
the standard mechanism provides an anti-pumping
function by blocking the main contacts in open position.
Anti-pumping function. After fault tripping or intentional
opening using the manual or electrical controls, the
closing order must first be discontinued, then reactivated
to close the circuit breaker.
When the automatic reset after fault trip (RAR) option is
installed, to avoid pumping following a fault trip, the
automatic control system must take into account the
information supplied by the circuit breaker before issuing
a new closing order or blocking the circuit breaker in the
open position (information on the type of fault, e.g.
overload, short-time fault, earth fault, earth leakage,
short-circuit, etc.).

B1

C1

A1

COM

OF

supervisor

PF
SDE
CH

40

Masterpact

Schneider Electric

056420

056468

Electric motor (MCH)


The electric motor automatically charges and recharges the spring mechanism
when the circuit breaker is closed. Instantaneous reclosing of the breaker is thus
possible following opening. The spring-mechanism charging handle is used only as
a backup if auxiliary power is absent.
The electric motor (MCH) is equipped as standard with a limit switch contact (CH)
that signals the charged position of the mechanism (springs charged).
characteristics
power supplyV AC 50/60 Hz
V DC
operating threshold
consumption (VA or W)
motor overcurrent
charging time
operating frequency
CH contact

48/60 - 100/130 - 200/240 - 277- 380/415 - 400/440 - 480


24/30 - 48/60 - 100/125 - 200/250
0.85 to 1.1 Un
180
2 to 3 In for 0.1 second
maximum 3 seconds for Masterpact NT
maximum 4 seconds for Masterpact NW
maximum 3 cycles per minute
10 A at 240 V

Voltage releases (XF and MX)

056421

Electric motor (MCH) for


Masterpact NT

Electric motor (MCH) for


Masterpact NW

XF and MX voltage releases

Closing release (XF)


The XF release remotely closes the circuit breaker if the spring mechanism is
charged.
Opening release (MX)
The MX release instantaneously opens the circuit breaker when energised. The
supply can be maintained or automatically disconnected.
characteristics
power supplyV AC 50/60 Hz
V DC
operating threshold
consumption (VA or W)

056457

circuit-breaker response
time at Un

Ready to close contacts


(PF)

XF

MX

24 - 48 - 100/130 - 200/250 - 277 - 380/480


12 - 24/30 - 48/60 - 100/130 - 200/250
0.85 to 1.1 Un
0.7 to 1.1 Un
hold: 4.5
hold: 4.5
pick-up: 200
pick-up: 200
55 ms 10 (Masterpact NT)
50 ms 10
70 ms 10 (NW i 4000A)
80 ms 10 (NW > 4000A)

Ready to close contact (PF)


The ready to close position of the circuit breaker is indicated by a mechanical
indicator and a PF changeover contact. This signal indicates that all the following
are valid:
c the circuit breaker is in the OFF position
c the spring mechanism is charged
c a maintained opening order is not present:
v MX energised
v fault trip
v remote tripping (second MX or MN)
v device not completely racked in
v device locked in OFF position
v device interlocked with a second device.
characteristics
supplied as standard
maximum number
breaking capacity
p.f.: 0.3
AC12/DC12

NT/NW

standard
V AC 240/380
480
690
V DC 24/48
125
250
low-level
V AC 24/48
240
380
V DC 24/48
125
250

41

Masterpact

1
1
minimum load: 100mA/24V
5
5
3
3
0.3
0.15
minimum load: 2mA/15V DC
3
3
3
3
0.3
0.15

Schneider Electric

Remote operation
Remote ON / OFF (cont.)

Functions
and characteristics

056469

Electrical closing pushbutton (BPFE)

E46044

Located on the front panel, this pushbutton carries out electrical closing of the
circuit breaker. It is generally associated with the transparent cover that protects
access to the closing pushbutton.
Electrical closing via the BPFE pushbutton takes into account all the safety
functions that are part of the control/monitoring system of the installation.
The BPFE connects to the closing release (XF) in place of the COM module.

remote
closing
order

Electrical closing pushbutton (BPFE).

A2

BPFE

A3

XF com
A1

Remote reset after fault trip

E46045

Electrical reset after fault trip (Res)


Following tripping, this function resets the fault trip indication contacts (SDE) and
the mechanical indicator and enables circuit breaker closing.
Power supply: 110 / 130 V AC and 200 / 240 V AC

reset
order
K2

SDE2

K1

Automatic reset after fault trip (RAR)


Following tripping, a reset of the mechanical indicator (reset button) is no longer
required to enable circuit-breaker closing. The mechanical (reset button) and
electrical (SDE) indications remain in fault position until the reset button is pressed.

42

Masterpact

Schneider Electric

056458

Remote tripping

This function opens the circuit breaker via an electrical order. It is made up of:
c a shunt release (second MX)
c or an undervoltage release (MN)
c or a delayed undervoltage release (MN + delay unit).
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency OFF button to obtain instantaneous opening of the circuit breaker.

E46554

E46553

E46043

Wiring diagram for the remote-tripping function


opening
order

delayed
opening
order

opening
order

10

12

056421

time delay
unit

MX or MN voltage release
C12

D2

instantaneous
opening
order
MN

MN

MX2
C11

D2

D1

D1

Voltage releases (second MX)


When energised, the MX voltage release instantaneously opens the circuit breaker.
A continuous supply of power to the second MX locks the circuit breaker in the OFF
position.
characteristics
power supplyV AC 50/60Hz
V DC
operating threshold
permanent locking function
consumption (VA or W)
circuit-breaker response
time at Un

24 - 48 - 100/130 - 200/250 - 277- 380/480


12 - 24/30 - 48/60 - 100/130 - 200/250
0.7 to 1.1 Un
0.85 to 1.1 Un
pick-up: 200
hold: 4.5
50 ms 10

Instantaneous voltage releases (MN)


The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35% and 70% of its rated voltage. If there is no supply on
the release, it is impossible to close the circuit breaker, either manually or
electrically. Any attempt to close the circuit breaker has no effect on the main
contacts. Circuit-breaker closing is enabled again when the supply voltage of the
release returns to 85% of its rated value.
characteristics
power supplyV AC 50/60 Hz
V DC
operating
opening
threshold
closing
consumption (VA or W)
circuit-breaker response
time at Un

24 - 48 - 100/130 - 200/250 - 380/480


24/30 - 48/60 - 100/130 - 200/250
0.35 to 0.7 Un
0.85 Un
pick-up: 200
hold: 4.5
40 ms 5 pour NT
90 ms 5 pour NW

MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
characteristics
power supply
V AC 50-60 Hz /DC
operating threshold
consumption (VA or W)
circuit-breaker response
time at Un

43

Masterpact

non-adjustable
adjustable
opening
closing
non-adjustable
adjustable

100/130 - 200/250
48/60 - 100/130 - 200/250 - 380/480
0.35 to 0.7 Un
0.85 Un
pick-up: 200 hold: 4.5
0.25 s
0.5 s - 0.9 s - 1.5 s - 3 s
Schneider Electric

Functions
and characteristics

Accessories

056463

Auxiliary terminal shield (CB)


Optional equipment mounted on the craddle, the shield prevents access to the
terminal block of the electrical auxiliaries.

056464

Operation counter (CDM)

E47535

The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with manual and electrical control functions.

Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP 40 (circuit breaker installed free standing: IP30) .
It is available in fixed and drawout versions.

Blanking plate (OP) for escutcheon


Used with the escutcheon, this option closes off the door cut-out of a cubicle not
yet equipped with a device. It may be used with the escutcheon for both fixed and
drawout devices.

Transparent cover (CP) for escutcheon


Optional equipment mounted on the escutcheon, the cover is hinged and secured
by a screw. It increases the degree of protection to IP 54, IK10. It adapts to both
fixed and drawout devices.

016819

Escutcheon (CDP) with blanking plate

Transparent cover (CP) for


Escutcheon

44

Masterpact

Schneider Electric

45

Masterpact

Schneider Electric

Functions
and characteristics

Source-changeover systems
Presentation

87921

Remote-operated source-changeover systems


This is the most commonly employed system. No intervention by human operators
is required. The switch from the normal to the replacement source is controlled
electrically.
A remote-operated source-changeover system is made up of two or three circuit
breakers or switch-disconnectors linked by an electrical interlocking system
implemented in a number of manners. Device control is backed up by a mechanical
interlocking system that protects against the consequences of an electrical
malfunction and inhibits incorrect manual operation.

Automatic source-changeover systems

029693

Service sector:
c hospital operating rooms
c safety systems for tall buildings
c computer rooms (banks, insurance companies, etc.)
c lighting systems in shopping centres.

When a remote-operated source-changeover system is combined with an


automatic controller, the sources can be controlled automatically according to a
number of programmed operating modes.
This solution provides optimal energy management:
c switching to a replacement source depending on any external conditions;
c management of power sources;
c regulation;
c emergency source replacement, etc.
A communications function for dialogue with a supervisor is available for the
automatic controller.

IMG0021

Industry:
c assembly lines
c propulsion systems on ships
c essential auxiliaries in thermal power stations.

Infrastructure:
c port and railway installations
c runway lighting systems
c control systems for military installations.

46

Masterpact

Schneider Electric

Mechanical interlocking

056427

Electrical interlocking of two or three


devices is used to create a remoteoperated source-changeover system. A
basic mechanical interlocking system
enhances the reliability of system
operation.

To ensure a continuous supply of power, certain electrical installations are


connected to two power sources:
c a normal source N;
c a replacement source R which supplies the installation when source N is not
available.
A source-changeover system switches between the two sources. The system may
include an automatic controller which manages switching according to external
conditions. A source-changeover system may comprise two or three circuit
breakers or switch-disconnectors.

Interlocking of two devices using connecting rods


The two devices must be stack mounted.
This function requires:
c an adaptation fixture on the right side of each device;
c a set of connecting rods with no-slip adjustments.
The complete interlock kit is supplied for assembly by the customer.
Maximum vertical distance between the fixing planes: 900 mm
Combinations of Masterpact Normal and Replacement devices
Masterpact NT and NW devices may not be used together in a source-changeover system.
The two devices must both be fixed devices or drawout devices to maintain correct alignment
of the mechanisms.

Interlocking of two or three devices using cables


Using cables, the devices may be stack mounted or installed side-by-side.
Interlocking of two devices (Masterpact NT or NW)
This function requires:
c an adaptation fixture on the right side of each device;
c a set of cables with no-slip adjustments.
Maximum distance between the fixing planes (vertical or horizontal): 2000 mm

Interlocking of three devices (only Masterpact NW)


This function requires:
c an adaptation fixture (different for each type of interlocking) on the right side of
each device;
c two or three sets of cables with no-slip adjustments.
Maximum distance between the fixing planes (vertical or horizontal): 1000 mm
Installation
The complete interlock kit is supplied for assembly by the customer.
Combinations of Masterpact Normal and Replacement devices
All combinations of Masterpact NT and NW devices may be used together in a sourcechangeover system. Interlocked devices may be fixed or drawout, three or four pole, with
different ratings and sizes.

47

Masterpact

Schneider Electric

Functions
and characteristics

Source-changeover systems
Electrical interlocking

Electrical interlocking is used with the


mechanical interlocking system. It controls
switching between sources. An automatic
controller may be added to take into
account information from the distribution
system.

Electrical interlocking requires an electrical control device.


This function can be implemented in one of two ways:
c using the IVE electrical interlocking unit
c by an electrician using the electrical systems presented in the diagrams in the
Source-changeover systems section of this catalogue.

Characteristics of the IVE unit


c external connection terminal block:
v inputs: control of devices
v outputs: status of the SDE contacts on the Normal and Replacement devices.
c connector to the two Normal and Replacement devices:
v inputs:
- status of the OF contacts on each device (ON or OFF)
- status of the SDE contacts on the Normal and Replacement devices
v outputs: power supply for motor mechanisms.
c control voltage:
v 24 to 250 V DC
v 48 to 415 V 50/60 Hz
v 440 V 60 Hz.
The control voltage for the IVE electrical interlocking unit must be identical to that
of the operating mechanism.

Necessary equipment
Each device must be equipped with:
c a remote-operation system made up of:
v MCH gear motor
v MX or MN opening release
v XF closing release
v PF ready to close contact
c an available OF contact
c a CE connected-position carriage switch on drawout devices.

types of mechanical interlocking

possible combinations

standard configurations

ref.

(presented in section Source-changeover systems)


E30736

2 devices

Q1

Q2

Q1
0

Q2
0

electrical interlocking
51156903
automatic controller with permanent
replacement source
51156904
automatic controller with engine generator set 51156905

0
1

1
0

Q1
0
1
0
1
0

Q2
0
0
0
1
1

Q3
0
0
1
0
0

automatic controller with permanent replacement source:


without lockout after fault
51156906
with lockout after fault
51156907
automatic controller with engine generator set:
without lockout after fault
51156908
with lockout after fault
51156909

Q1
0
1
0
0

Q2
0
0
1
0

Q3
0
0
0
1

electrical interlocking:
without lockout after fault
with lockout after fault

51156910
51156911

Q1
0
1
0
0
1
0
1

Q2
0
0
1
0
1
1
0

Q3
0
0
0
1
0
1
1

electrical interlocking:
without lockout after fault
with lockout after fault
automatic controller

51156912
51156913
51156914

E30737

3 devices: 2 Normal sources and 1 Replacement source

Q1

Q2

Q3

E30738

3 devices: 3 sources, only 1 device closed

Q1

Q2

Q3

E30739

3 devices: 2 sources and 1 coupling

Q1

Q2

Q3

Lockout after fault option: this option makes it necessary to manually reset the device following fault tripping.

48

Masterpact

Schneider Electric

Associated automatic controllers

By combining a remote-operated sourcechangeover system with an integrated BA


or UA automatic controller, it is possible to
automatically control source transfer
according to user-selected sequences.
These controllers can be used on sourcechangeover systems comprising 2 circuit
breakers.
For source-changeover systems
comprising 3 circuit breakers, the
automatic control diagram must be
prepared by the installer as a complement
to to diagrams provided in the electrical
diagrams section of this catalogue.

controller

BA

compatible circuit breakers

4-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources off)

c
c
c
c

c
c
c
c

automatic operation
Monitoring of the Normal
source and automatic changeover
Generator set startup control
Generator set shutdown control
Load shedding and reconnection of non-priority circuits
Changeover to the Replacement
source if one of the phases of the Normal phase is absent

c
c
c
c

test
By opening the P25M circuit breaker
supplying the controller
By pressing the test button on the front of the controller

053058R

UA

All Compact NS
and Masterpact circuit breakers

c
c

indications
Circuit breaker status indication on the front
of the controller: on, off, fault trip
Automatic mode indicating contact

Selection of type of Normal source


(single-phase or three-phase)
Voluntary transfer to Replacement source
c
(e.g. energy management commands)
During peak-tariff periods (energy management commands),
forced operation on Normal source
if Replacement source not operational
Additional contact (not part of controller).
c
Transfer to Replacement
source only if contact is closed.
(e.g. used to test the frequency of UR).
Setting of maximum startup time
for the replacement source

other functions

BA controller

c
c

options
communication option

053058

power supply
control voltages (1)

220 to 240 V 50/60 Hz


380 to 415 V 50/60 Hz
440 V 60 Hz

c
c
c

c
c
c

0.35 Un i voltage i 0.7 Un


0.5 Un i voltage i 0.7 Un
voltage u 0.85 Un

c
c
c

operating thresholds
undervoltage
phase failure
voltage presence

characteristics of output contacts


rated thermal current (A)
minimum load

UA controller

8
10 mA at 12 V

utilisation category (IEC 947-5-1)


operational current (A)
24 V
48 V
110 V
220/240 V
250 V
380/415 V
440 V
660/690 V

AC12
8
8
8
8
5
4
-

AC
AC13
7
7
6
6
-

AC14
5
5
4
4
-

AC15
6
5
4
3
-

DC12
8
2
0.6
0.4
-

DC
DC13
2
-

(1) The controller is powered by the ACP auxiliaries control plate. The same voltage
must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms.
If this voltage is the same as the source voltage, then the Normal and Replacement
sources can be used directly for the power supply. If not, a BC type or equivalent
isolation transformer must be used.

49

Masterpact

Schneider Electric

Display modules

Perfectly integrated in the Compact


and Masterpact ranges, Display modules
are designed for use with Micrologic control
units to provide instant and highly intuitive
access to all
the information provided by the circuit
breakers, including device status, current,
voltage and power values, etc.

DMB300 and DMC300 display modules use the power and communications
capabilities of the Micrologic control units to centralise the display of electrical
values, status conditions and alarms of one or more Compact
or Masterpact circuit breakers.
The mounting and cabling system for the display modules ensures fast,
easy and reliable installation.
Start-up is immediate with no configuration or programming required.
Digipact display modules are high-performance devices combining:
c simple and easy-to-read dials
c powerful and accurate digital processing.
Their small size and extensive communications capabilities make for easy and
flexible installation and operation.

057454

Functions
and characteristics

Display modules

DMB300

DMC300

Associated circuit breakers


Type

Compact or Masterpact equipped with


Micrologic control units
1 to 4
1 to 16

Number

Display
Screen type
Screen size
Entry
DMB300 display module: basic and harmonic measurements

Black and white


240 x 64 pixels
5 buttons

Colour, touch screen


5, 320 x 240 pixels
Touch screen

A
A
A

A
A
A

Information displayed

E79078

Currents (per phase)


Currents I1, I2, I3, IN
Maximum current
Earth-fault and earth-leakage currents
Demand current
Maximum demand current
Total harmonic distortion (THD)
Maximum total harmonic distortion
Amplitudes of individual harmonics
Waveform capture

P
P
P
P
P

H
H
H
H
H
H
H

P
P
P
P
P
P

H
H
H
H
H
H
H
H
H

Power
Active (P), reactive (Q) and apparent (S) power
Power factor and cos
Maximum power (P, Q, S)
Demand power (P, Q, S)
Maximum demand power (P, Q, S)

P
P
P
P
P

Metering
Active, reactive and apparent energy

Voltages
Phase-to-phase voltages (U1-2, U2-3, U3-1)
Minimum/maximum phase-to-phase voltages
Phase-to-neutral voltages (V1-N, V2-N, V3-N)
Minimum/maximum phase-to-neutral voltages
Frequency
Voltage imbalance (% per phase)
Total harmonic distortion (% per phase)
Maximum total harmonic distortion (% per phase)
Amplitudes of individual harmonics

DMC300 display module: measurements, harmonic analysis,


diagnosis

P
P
P
P
P

H
H
H
H
H
H
H
H
H

P
P
P

H
H
H

P
P

H
H
H
H
H

H
H
H
H
H

P
P
P
P
P

H
H
H
H
H

On-line help
On-line help is available for each type
of information supplied by the module
Circuit-breaker diagnostics
Identification of control units
Reading of protections
Circuit-breaker status
Type of trip
Current alarms
Maintenance indicator
Installation diagnosis
Indication of faulty devices
Fault log

Associated Micrologic control unit


A = Micrologic A
P = Micrologic P
H = Micrologic H

A
A
A
A

P
P
P
P
P

H
H
H
H
H

A
A
A
A

P
P
P
P
P
P

H
H
H
H
H
H

A
A

P
P

H
H

Installation and start-up


Mounting
Connection

50

Masterpact

Mounted through door, without tools,


using 6 spring-clips supplied with the mod.
Prefabricated wiring systems

Schneider Electric

24 V DC
power

E59178

Connection of DMB300 display module

Wiring system
The wiring system is designed for low-voltage
power switchboards. Installation requires no tools
or special skills.
The prefabricated wiring ensures both data
transmission (ModBus protocol) and 24V DC power
distribution for the display module and the
communications modules on the Micrologic control
units.

2
E59081A

ON ON

ON
n 4n 4 4 ON
n
n 3n 3
n 4
n 2n 2 n 3
n 3
n 1n 1 n 2
n 2
OUTOUT n 1
IN IN
T

IN

ON

OU

3
Reset

push
push

70

NX 32

ON

Ir

Ig
Isd I n
Ii

Ap

reset

Icu (kA)
100
100
85
Icw 85kA/1s

cat.B

Ics =

discharge

CDM 303:
Connection cable between
display module and junction
block

H2

Ue (V)
220/440
525
690

OFF

Micrologic

100%

Icu
50/60Hz

O OFF

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

012

VDE

53

com

DMB300
Digipact

volets
shutters

Test

1
2
I

select

E59180A

NW

1251

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

H1

Uimp

Ui 1000V
8kV
Uimp

Micrologic

Ir

Ig
Isd I n
Ii

Ap

reset

I ON

OOFF

push

push

discharged

O OFF

Ics =

IEC

100%

Icu

947-2

UTE VDE

012

BS CEI

ON

NEMA

UNE

53

IN

NW

1251

n 2

n 3

n 4

ON

H1

Uimp

Ui 1000V
8kV
Uimp

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

n 1
OUT

Micrologic

Ir

Ig
Isd I n
Ii

Ap

reset

I ON

OOFF

push

push

discharged

O OFF

Ics =

IEC

100%

947-2

UTE VDE

Icu

BS CEI

CJB 306 junction block

NEMA

UNE

53

E59179

012

Masterpact circuit breakers equipped with Micrologic control


units and the ModBus eco COM option
CCP 303:
Connection cable between
Masterpact or Compact and
junction block

Connection of DMC300 display module


Maximum distance between module and circuit breaker: 1200 m
5

E59082A

E59176A

NW

1251

H1

Uimp

Ui 1000V
8kV
Uimp

NW

12kV

Ir

Ap

reset
Ir

I ON

OOFF

Ig
Isd I n
Ii

Ap

I ON

OOFF

discharged

O OFF

Ics =

IEC

100%

NX 32

ON

d
discharge

Icu (kA)
100
100
85
Icw 85kA/1s

cat.B
Ics =

012

H2

Ue (V)
220/440
25
525
690

OFF

reset

100%

Icu
50/60Hz

O OFF

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

VDE

Ics =

BS CEI

UNE

NEMA

IEC

012

NW

1251

H1

Uimp

Ui 1000V
8kV
Uimp

NW

12kV

Ap

Ir

I ON

OOFF

Ig
Isd I n
Ii

Ap

I ON

OOFF

discharged

Ics =

IEC

push
push

NX 32

ON

100%

d
discharge

O OFF

BS CEI

UNE

NEMA

IEC

100%

947-2

UTE VDE

012

BS CEI

UNE

NEMA

53

Icu (kA)
100
100
85

100%

Icu

NW

50/60Hz

1251

70

NW

12kV

Ig
Isd I n
Ii

H1

Uimp

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

Micrologic

Ir

1251

Ui 1000V
8kV
Uimp

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

VDE

H1

Uimp

Ui 1000V
8kV
Uimp

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

Ics =

947-2

53

Icu

Icw 85kA/1s

cat.B
Ics =

Icu

H2

Ue (V)
220/440
525
690

OFF

reset

push

push

O OFF

UTE VDE

012

Ap

12kV

Icu
(kA)
100
85

reset

push

discharged

70

CCR 301:
Roll of RS485 cable
(2 RS485 wires + 2 power
supply wires)

H1

Uimp

Ue
(V)
220/240
480/690

70

reset

push

Ig
Isd I n
Ii

NEMA

Micrologic

Ig
Isd I n
Ii

O OFF

Reset

UNE

1251

Ui 1000V
8kV
Uimp

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

Ir

Ir

Icu

BS CEI

53

Micrologic

Micrologic

100%

947-2

UTE VDE

53

E59177A

Ap

Icu

947-2

UTE VDE

push
push

70

Ig
Isd I n
Ii

push

push

discharged

Reset

12kV

Icu
(kA)
100
85

reset

push

push

Ir

H1

Uimp

Ue
(V)
220/240
480/690

70
Micrologic

Ig
Isd I n
Ii

O OFF

Micrologic

1251

Ui 1000V
8kV
Uimp

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70
Micrologic

Micrologic
Ap

reset
Ir

I ON

OOFF

Ig
Isd I n
Ii

Ap

reset

I ON

push

OOFF

push

discharged

O OFF

Ics =

IEC

100%

947-2

UTE VDE

012

push

push

discharged

O OFF

Icu

BS CEI

Ics =

UNE

NEMA

IEC

100%

947-2

UTE VDE

53

012

Icu

BS CEI

UNE

NEMA

53

CSD 309:
SubD 9-pin connector for
colour-coded connection of
wires to screw terminals

Masterpact circuit breakers equipped with Micrologic control units and the ModBus eco COM option

51

Masterpact

Schneider Electric

52

Masterpact

Schneider Electric

Dimensions and connection

Masterpact

Presentation
Functions and characteristics

1
9

Masterpact NT06 to NT16


Fixed 3/4-pole device
Drawout 3/4-pole device

54
58

Masterpact NW08 to NW32


Fixed 3/4-pole device
Drawout 3/4-pole device

62
64

Masterpact NW40
Fixed 3/4-pole device
Drawout 3/4-pole device

66
68

Masterpact NW40b to NW63


Fixed 3/4-pole device
Drawout 3/4-pole device

70
72

NT/NW accessories
NT/NW external modules

74
76

Electrical diagrams
Installation recommendations
Additional characteristics
References

53

Masterpact

81
91
115
121

Schneider Electric

NT06 to NT16 circuit breakers


Fixed 3/4-pole device

Dimensions
and connection

Dimensions
E47191B

105 (3P)
175 (4P)

105
188
94

E47190B

Y
178
136
105

210

X
123

6,5

39
15

125 (3P)
195 (4P)

3
13

150,5

125
13

Rear mounting detail


(on upright or backplate)
E47194B

Bottom mounting (on base plate or rails)

E47193A

E47192B

6 6,5

4 6,5
25

100

X
39

100

18 mini
39 maxi

136,5

194 mini (3P)


264 mini (4P)

125

Rear panel cutouts


E47197A

A (*)

E47196A

E47195A

E59443A

Door cutout

77

125

125 (3P)
195 (4P)

Safety clearances

154

125 (3P)
195 (4P)

A (*)

125

62,5

194 mini

62
44

40

130

108 (1)
133 (2)

194 (1)
244 (2)

A
B

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

100
60

F : Datum.

216 (1)
266 (2)

100 (3P)
170 (4P)

62
106
100

97 (1)
122 (2)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.
A(*) An overhead clearance of 50 mm is required to remove the arc chutes.
An overhead clearance of 20 mm is required to remove the terminal block.

54

Masterpact

Schneider Electric

E47210A

Connections

E47200A

Detail
43,5

E47199A

E47198A

Horizontal rear connection

70

70

70

15
123
67,5

X
67,5
44

E47201B

123

25

15

9,5 12,5
60

167,5
12,5

F
2 11

Detail
E47204A

43,5

E47203A

E47202A

Vertical rear connection

70

70

70
15
View A

97

E47205B

97

60
12,5
9,5

12,5

167,5
F

44
25
2 11
View A detail

12

E47208A

Detail
E47207B

150

View A
70

326

44
25

70

70

Top connection
E47209B

E47206A

Front connection

Bottom connection
2 11

9,5

13

150

13
2 11

25
44

9,5

View A detail

164
F

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

55

Masterpact

Schneider Electric

NT06 to NT16 circuit breakers


Fixed 3/4-pole device

Dimensions
and connection

Connection

E47213A

E47212A

E47211A

Front connection with spreaders


95

95

70

View A

70

15

202

Y
434
95

E47214A

95
70

95

70

70

12,5

202

View A

12,5

15

179
F

98

95

E47221A

E47219A

E47220A

Rear connection with spreaders


95

70

70

123
15

15

82,5

52,5

Y
E47222A

123

95

95
70

95

70

70

219,5

12,5

234,5

12,5

Spreader detail

25

38,5

13,5

25

13,5

15
5 11

13,5

38,5
=

13,5

=
30

30
82 52

15

77
25

30
82 52

15

5 11

82 52

15
5 11

5 11

25

25
52

38,5
25

30
82 52

77

Left or right spreader for 3P


E47294A

77

Left or right spreader for 4P


E47293A

77
38,5

Middle spreader for 3P


E47292A

E47234A

Middle left or middle right


spreader for 4P

25

25

52

52

52

View A detail

F : Datum

Note:
X and Y are the symmetry planes for a 3-pole device.

56

Masterpact

Schneider Electric

E47210A

Connections

E47216A

116,5

E47217A

E47215A

Front connection via vertical connection adapters


70

70

70
15
View A

21

221

N
E47218A

472

89
= =

25

12,5
15

21 (1)
101

221

21

21
3 11

15

20

View A detail
190,5
253
F

15

E47232A

221

E47233A

E47231A

Front connection via vertical connection adapters fitted with bare cable connectors.
70

70

70
15

50
View A

271
21

221

572

E47230A

Y
184

17

50

50

21

50

50

80
221
271

15

5 13

5 11

View A detail

50

15

340,5
357,5
F

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

(1) 2 connection possibilities on vertical connection adapters (21 mm between centres)

57

Masterpact

Schneider Electric

NT06 to NT16 circuit breakers


Drawout 3/4-pole device

Dimensions
and connection

E47172A

Dimensions
E47171C

210
mini

127,5 (3P)
197,5 (4P)

160,5
188
94

Y
46 (*)

199

123
5

45,5

60 mini

90 (3P)
160 (4P)

231

90

(*) disconnected position

Bottom mounting (on base plate or rails)

Rear mounting detail


(on upright or backplate)

E47175B

Y
X

E47173B

E47174B

4 6,5

6 6,5

X
25

24

150

50

25 100

100
216
231
F

90 (3P)
160 (4P)

109 (3P)
179 (4P)

B
C

170 mini (3P)


240 mini (4P)

109

Rear panel cutout


E47178A

Door cutout
E47177B

E47176B

E59444A

Safety clearances

90

230 mini

259 (1)
303 (2)

234
117

40
180
F

A
B
C

109 (1)
130,8 (2)
161 (1)
183 (2)

Insulated
parts

Metal
parts

Energised
parts

0
10
0

0
10
0

30
60
30

102,5 (3P)
172,5 (4P)

102,5

259 (1)
307 (2)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.

F : Datum.

58

Masterpact

Schneider Electric

E47189A

Connections

E47181A

Detail
E47180A

E47179A

Horizontal rear connection

49

70

70

70

15

67,5
228

N
E47201B

67,5
114

44
25

9,5 12,5

15

267,5
F

60
12,5
2 11

Detail
70

E47183A

E47182A

Vertical rear connection

70

70
15

49

97

E47184A

View A

N
E47205B

97

60
12,5
9,5

12,5

267,5
F

44
25
2 11
View A detail

Detail
15

12,5

70

E47187A

E47186B

70

View A

70

171

N
X

Top connection
9,5

12,5

Bottom connection

44

140

235

336

25

37,9
26

83

131

52

26
37,9

9,5

100

2 11

25

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

9,5

2 11

E47188B

E47185A

Front connection

44

9,5

View A detail

59

Masterpact

Schneider Electric

NT06 to NT16 circuit breakers


Drawout 3/4-pole device

Dimensions
and connection

Connection

E47225A

E47224A

E47223A

Front connection with spreaders


95

95

70

View A

70

238
223

Y
E47226A

X
207

95

95

70

95

70

70
View A

192

12,5

12,5

250
F

Rear connection with spreaders

25

38,5

13,5

25

13,5

15
5 11

13,5

38,5
=

13,5

=
30

30
82 52

15

77
25

30
82 52

15

5 11

82 52

15
5 11

5 11

25

25
52

38,5
25

30
82 52

77

Left or right spreader for 3P


E47294A

77

Left or right spreader for 4P


E47293A

77
38,5

Middle spreader for 3P


E47292A

E47234A

Middle left or middle right


spreader for 4P

25

25

52

52

52

View A detail

Note:
X and Y are the symmetry planes for a 3-pole device.

F : Datum

60

Masterpact

Schneider Electric

E47189A

Connections

E47227A

E47228A

15

E47229A

Front connection via vertical connection adapters fitted with bare cable connectors.
70

70

70
View A

15

50
71
292
21

583

E472230A

171

15

184
17

50

50

50

140
21

50

80

261

5 13

71

5 11

View A detail
50

15

193,5
F

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

61

Masterpact

Schneider Electric

NW08 to NW32 circuit breakers


Fixed 3/4-pole device

Dimensions
and connection

E46050A

Dimensions
189 (3P)
304 (4P)

189
308
154

E46055A

Y
191
150
260

X
161
11

57

233

200 (3P)
315 (4P)

11

11

Mounting detail

E46052A

E46051A

Mounting on base plate or rails

200

9,5

25

72
15 mini
60 maxi

38
162

218,5
200 (3P)
315 (4P)

E46054A

A (*)

200

9,5

Door cutout
A (*)

E46053A

Safety clearances
E59445A

124
162

295 mini (3P)


410 mini (4P)

295 mini

270 (1)
316 (2)
135 (1)
158 (2)

15

205
F

325 (1)
364 (2)

A
B

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

100
60

F : Datum.

162,5 (1)
182 (2)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.
A(*) An overhead clearance of 110 mm is required to remove the arc chutes.
An overhead clearance of 20 mm is required to remove the terminal block.

62

Masterpact

Schneider Electric

E46004A

NX 08

HA1012kV
Uimp

Ui 1000V
Ue (V)
690

s
50kA/1
50/60Hz
AS
UNE
IEC 947-2
BS CEI
EN 60947-2
VDE
UTE

maste

rpact

NBMA

II

N GERIN
MERLI

Connections
Horizontal rear connection

Dtail

20

E46056A

E46086A

E46351A

27

115

115

115

20 150

N
76

E46057A

X
93

13

38

161

= =

25

12,5

20

47

233,5
3 11,5

Detail
E46058A

27

E46089A

E46087A

Vertical rear connection

14,5

115

115

115
20
View A

68

X
E46059A

141

47

14,5

12,5
13
=

233,5

3 11,5

76
38
25

View A detail

E46090A

20

12,5

E46060A

Detail

E46088A

Front connection

115

115

230,5

E46061B

475

View A

Top connection

115

Bottom connection

76
25 25

13

12,5

219,5

3 11,5

3 11,5
12,5

12,5

219

View A detail

25 25

13

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

63

Masterpact

Schneider Electric

NW08 to NW32 circuit breakers


Drawout 3/4-pole device

Dimensions
and connection

E46352A

Dimensions

E46506A

400
mini

220,5 (3P)
335,5 (4P)

220,5
308
154

Y
56
(*)

238,5

X
200,5

128

11

383,5

200

60 mini

400

(*) Disconnected position

Mounting detail

E46353B

E46354A

Mounting on base plate or rails

2 11,5 x 22
11,5

10

175

110
103

10,5

175
283

167,5 (3P)
282,5 (4P)

Door cutout

E59446A

E46356A

E46355A

Safety clearances

162,5

300 mini (3P)


415 mini (4P)

300 mini

270 (1)
379 (2)

X 135 (1)

222 (2) 153,3 (1)

100
225
F

A
B

325 (1)
364 (2)

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

0
60

F : Datum.

162,5 (1)
182 (2)

47 (1)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.
A(*) An overhead clearance of 110 mm is required to remove the arc chutes.

64

Masterpact

Schneider Electric

E46005A

NX 08

HA10 12kV
Uimp

Ui 1000V
Ue (V)
690

50kA/1s
50/60Hz
UNE
IEC 947-2
BS CEI
EN 60947-2
VDE
UTE

AS NBMA

act II
masterp

GERIN
MERLIN

Connections
Detail
E46363A

E46360A

E46357A

Horizontal rear connection

115

115

115

27
20

20

76

E46057A

296
93

13

38
= =

25

12,5

184
47

20
3 11,5

14,5

298,5
F

Detail
E46364A

E46361A

E46358A

Vertical rear connection

115

115

115
20
View A

27

X
141

E46059A

68

Y
47

14,5

12,5
13
=
=

298,5

3 11,5

76
38
25

F
View A detail

20
12,5

E46365A

Detail
E46362A

E46359A

Front connection

115

151

E46819B

400

View A

115

Top connection

115

Bottom connection

76
25 25

224

13

12,5
3 11,5

3 11,5
12,5

284

12,5

View A detail

25 25

13

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

65

Masterpact

Schneider Electric

NW40 circuit breakers


Fixed 3/4-pole device

Dimensions
and connection

E46050A

Dimensions
189 (3P)
304 (4P)

189
308
154

E46055A

Y
191
150
260

161
11

57

200 (3P)
315 (4P)

11

233

11

Mounting detail
E46052A

E46051A

Mounting on base plate or rails

200

Y
9,5

25

72
15 mini
60 maxi

124
162

38
162

218,5

200 (3P)
315 (4P)

A (*)

A (*)

295 mini (3P)


410 mini (4P)

E46054A

E59445A

9,5

Door cutout
E46053A

Safety clearances

200

295 mini

270 (1)
316 (2)
135 (1)
158 (2)

15

205
F

325 (1)
364 (2)

A
B

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

100
60

F : Datum.

162,5 (1)
182 (2)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.
A(*) An overhead clearance of 110 mm is required to remove the arc chutes.
An overhead clearance of 20 mm is required to remove the terminal block.

66

Masterpact

Schneider Electric

E46484A

NX 08

HA1012kV
Uimp

Ui 1000V
Ue (V)
690

s
50kA/1
50/60Hz
UNE
IEC 947-2
BS CEI
EN 60947-2
VDE
UTE

maste

rpact

AS NBMA

II

N GERIN
MERLI

Connections
Horizontal rear connection
E46485A

E46351A

27

20

20 150

X
93
161
20
233,5
F

150

150

115
52,5

E46490A

E46489B

Detail
150

115

115

12,5
14,5

25 25 25

52,5

17,5

17,5

135
12,5

47

E46550A

4 11,5

N
332,5 (4P)

100
12,5

12,5

25 25 25

14,5

217,5

47

27

E46488A

E46486A

Vertical rear connection

117,5

X
190,5

233,5
F

115

115

115
20

E46491A

E46058A

Detail
47
14,5
12,5

View A

12,5

25

25

20

25

125

25

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

5 11,5

67

Masterpact

Schneider Electric

NW40 circuit breakers


Drawout 3/4-pole device

Dimensions
and connection

E46506A

Dimensions
220,5 (3P)
335,5 (4P)

E46352A

400
mini

220,5
308
154

Y
56
(*)

238,5

X
200,5

128

11

383,5

200
400

60 mini
(*) Disconnected position

Mounting on base plate or rails

Mounting detail

E46353B

E46354A

2 11,5 x 22
11,5

10

175

10,5

110
103

175
F

283
F
167,5 (3P)
282,5 (4P)

Door cutout

E59446A

E46356A

E46355A

Safety clearances

162,5

300 mini (3P)


415 mini (4P)

300 mini

270 (1)
379 (2)

X 135 (1)

222 (2) 153,3 (1)

100
225
F

A
B

325 (1)
364 (2)

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

0
60

F : Datum.

162,5 (1)
182 (2)

47 (1)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.
The safety clearances take into account the space required to remove the arc chutes.

68

Masterpact

Schneider Electric

E46005A

NX 08

HA10 12kV
Uimp

Ui 1000V
Ue (V)
690

50kA/1s
50/60Hz
UNE
IEC 947-2
BS CEI
EN 60947-2
VDE
UTE

AS NBMA

act II
masterp

GERIN
MERLIN

Connections

E46492A

E46360A

Horizontal rear connection

27
20
20

296
93
184
20

298,5
F

150

150

115

E46490A

E46496B

Detail
150

115

115

52,5

135
12,5

12,5
14,5

25 25 25

52,5
17,5

17,5

47

332,5

E46550A

4 11,5

217,5

100
12,5

12,5

25 25 25

14,5
47

E46491A

E46493A

E46495A

Vertical rear connection


47
14,5
12,5

27

12,5

25
25

117,5

20

25

125

25

X
5 11,5
190,5

View A detail

298,5
F

E46364A

Detail
115

115

115
20
View A

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

69

Y
Masterpact

Schneider Electric

NW40b to NW63 circuit breakers


Fixed 3/4-pole device

Dimensions
and connection

Dimensions
E46282A

534 3P)
764 (4P)

189
308
154

E46055A

Y
191
150
260

161

57

545 (3P)
775 (4P)

11

233

11

Mounting detail

E46283A

E46284A

Mounting on base plate or rails

200

9,5

25

72

124
162

38

15 mini
60 maxi

162

218,5

545 (6P)
775 (8P)

Safety clearances
A (*)

9,5

Door cutout
A (*)

639 mini (3P)


839 mini (4P)

E46286A

295 mini

E46285A

E59445A

200

270 (1)
316 (2)
135 (1)
158 (2)

15

205
F

325 (1)
364 (2)

A
B

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

100
60

F : Datum

162,5 (1)
182 (2)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.
A(*) An overhead clearance of 110 mm is required to remove the arc chutes.
An overhead clearance of 20 mm is required to remove the terminal block.

70

Masterpact

Schneider Electric

E46281A

NX 63

HA
Uimp

12kV

Ui 1000V
Ue (V)
690

Icw 85kA/1s
50/60Hz
AS
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE

pact
master

NBMA

II

GERIN
MERLIN

Connections

E46551A

Horizontal rear connection (NW40b - NW50)

E46287A

20

E46289A

47

230
115

230

115

115

115

230
115

115

115

20 150

20 93

161

E46057A

76
13

38

253,5

25

= =

12,5

F
47
3 11,5

E46290A

Dtail
E46552A

E46288A

Prises arrire verticales (NW40b - NW50)

14,5

47

230
115

230

115

115

115

230
115

115

115

68

20
View A

X
141

N
Y
47
14,5

12,5
13

E46059A

253
253,5
F

=
76

=
3 11,5

38
25

View A detail

Vertical rear connection (NW63)

Detail
47

230

230

115

115

115

230
115

115

115
20

E46290A

E59536A

E59535A

115

117,5

View A

X
N

190,5

Y
47
14,5
12,5

253
253,5

E46491A

12,5

25
25
20

25

125

25
5 11,5

Note:
Recommended connection screws: M10 s/s class A4 80
Tightening torque: 50 Nm with contact washer.

View A detail

71

Masterpact

Schneider Electric

NW40b to NW63 circuit breakers


Drawout 3/4-pole device

Dimensions
and connection

565,5 (3P)
795,5 (4P)

E46498A

E46487A

Dimensions
400
mini

220,5
308
154

Y
56
(*)

238,5

X
200,5

128

40

60 mini

11

383,5

200
400

(*) Disconnected position

Mounting detail

E46508A

Mounting on base plate or rails

Y
E46499A

250
53

250
333
23

6 11 x 34
325 (3P)
450 (4P)

Safety clearances

F
151 (3P)
162,5 (4P)

174 (3P)
287,5 (4P)

Door cutout

646 mini (3P)


876 mini (4P)

300 mini

Y
E46500A

E59446A

E46501A

270 (1)
379 (2)

X 135 (1)

222 (2) 153,3 (1)

150
275
F

A
B

47 (1)

Insulated
parts

Metal
parts

Energised
parts

0
0

0
0

0
60

F : Datum.

325 (1)
364 (2)

162,5 (1)
182 (2)

(1) Without escutcheon


(2) With escutcheon
Note:
X and Y are the symmetry planes for a 3-pole device.

72

Masterpact

Schneider Electric

E46497A

NX 08

HA10 12kV
Uimp

Ui 1000V
Ue (V)
690

50kA/1s
50/60Hz
AS
UNE
IEC 947-2
BS CEI
EN 60947-2
VDE
UTE

NBMA

t II
masterpac

GERIN
MERLIN

Connections
Detail

E46507A

Horizontal rear connection (NW40b - NW50)

115

20

115

115

115

N
291

93

115

115

E46504A

20

Y
76

E46057A

E46502A

27

115

179

13

38
= =

25

12,5

20
47
3 11,5

14,5

348,5
F

Detail

E46494A

E46505A

Vertical rear connection (NW40b - NW50)

115

115

115

115

115

115

115
20

E46503A

27

View A

68

E46059A

X
141

47
14,5

12,5
13
=
=

348,5
F

3 11,5

76
38
25

View A detail

Detail

E59533A

E46505A

E59534A

Vertical rear connection (NW63)

115

115

115

115

115

115

115
20

27

View A

117,5

190,5

E46491A

N
X

47
14,5
12,5

12,5

25
25

348,5

20

25

125

25
5 11,5
View A detail

Note:
Recommended connection screws: M10 s/s class A4 80
Tightening torque: 50 Nm with contact washer

73

Masterpact

Schneider Electric

NT/NW accessories

Dimensions
and connection

Mounting on backplate with special brackets (Masterpact NW08 to NW32 fixed).


E46805A

429 (3P)
544 (4P)

E46806A

4 12

159

96

113

218,5

4,5

203,5

11

125

11

407 (3P)
522 (4P)

Disconnectable front-connection adapter (Masterpact NW08 to NW32 fixed)


Detail
67

115

E46812A

E46807A

E46809A

Horizontal rear connection

20

115

183

76

E46057A

115

13

38
25

= =

12,5

172

47
3 11,5

14,5

20
253,5
F

Detail
E46810A

67

E46811A

E46808A

Vertical rear connection

115

115

115
20
View A

231

E46059A

N
X

47
14,5

12,5
13

220

=
76

=
3 11,5

Note:
Recommended connection screws: M10 class 8.8
Tightening torque: 50 Nm with contact washer

253,5

38
25

View A detail

F Datum

74

Masterpact

Schneider Electric

Rear panel cutout (drawout devices)

E46271A

NW08 to NW40

E46272A

X
302

187

264

200,5 (3P)
315,5 (4P)

200,5
401 (3P)
516 (4P)

E46273A

E46274A

NW40b to NW63

X
297

182

314
478,5 (3P)
708,5 (4P)

200,5
679 (3P)
909 (4P)

Escutcheon
Masterpact NT
Fixed device

Drawout device

Y
E59887A

E59885A

275

313

27

27

27

27

13

27

317

253

Masterpact NW
Fixed device

Drawout device

Y
E59890A

E59889A

324

25

387

18
45

25
372
25

F Datum

25

372

75

Masterpact

Schneider Electric

NT/NW external modules

Dimensions
and connection

E47684A

E47683A

Connection of auxiliary wiring to terminal block


S : 0,6 mm2
S : 2,5 mm2

1
8

3,5
One conductor only per connection point

M6C relay module

11

15

13

17

23 25

81
S1
S2
S3
S4
S5
S6

M6c

9
5 7

3
S1

S3
2

11
24V

25
21 23
17 19
.
com
0V

46

E47689A

E47688A

99
21

19

S2
S6
S5
22 24
S4
18 20
14 16
10 12
6 8

13

15

17

19

M6c

25
21 23
17 19
.
com
0V
24V
S6
S5
24
20 22
16 18
14
10 12
6 8

9
5 7

11

21

23 25

S1
S2
S3
S4
S5
S6

S2

S1

S4

99

66

11

S3
2

46

External power supply module (AD)


E47690A

60

L4
L3

AD 22

t
Inpu C
24VD

2 6

60

73

ut
Outp C
24VD G2

0A

112

E47691A

G1

75

L4
L3

t
Inpu C
24VD
ut
Outp C
24VD

0A
AD 22

+
G2

G1

Battery module (BAT)


Mounting

E47692A

60

2 6

60
H4
H3

24V
BAT

t
Inpu C
24VD

73

ut
Outp C
24VD H1

112

75

E47693A

H2

H4
H3

24V
BAT

t
Inpu C
24VD

ut
Outp C
24VD

H1

H2

76

Masterpact

Schneider Electric

Delay unit for MN release


MNR

E47694A

57
1

4 5

81

S
3 6
0.5

10 12

73,5

73

E47695A

66

42

1.5
3
MN
r de R
UV
dateu
Retardelay for
Time

MN
UVR
30 V
100/1C
AC/D

2 4,2

4 5

72
S
3 6
0.5

30 V
100/1C
AC/D

1.5
3
MN
r de R
UV
dateu
Retardelay for
Time

MN
UVR

10 12

46

Craddle communication module


BatiBUS

E47686A

E47685A

ModBUS

90

Fault
Com.

CE

CD

CT

ss
Addre
.
sync

58

45

Breaker

us
modb
CCM

Disjoncteur

Rseau
shield
B B
A A
B B
A A
Network

++

54

External sensor for source ground return (SGR) protection


MGDF summer module

E58561

E47687A

Sensor

200

90

130
45
F
MDG

45

76
150

58

77

Masterpact

106

Schneider Electric

NT/NW external modules

Dimensions
and connection

External sensor for external neutral


Dimensions
400/1600 A (NT06 to NT16)

400/2000 A (NW08 to NW20)

4 14
E47700

E47699

GND VN VC

H1

H2

H1

4 14
H2

SG1
SG2
X1
X2
GND
VN
VC

35 76
X2 X1 SG2 SG1

177

44 102

208

174
206

2000/6300 A (NW40b to NW63)

8 14

H1

H2
SG1
SG2
X1
X2
GND
VN
VC

44

174

E47702

E47701

1000/4000 A (NW025 to NW40)

16 14

H1

H2
SG1
SG2
X1
X2
GND
VN
VC

44 127

127
44

H1

44

H2
SG1
SG2
X1
X2
GND
VN
VC

295

44

174

70

44
127

44

295

Installation
400/2000 A (NW08 to NW20)
E47696A

E47696

400/1600 A (NT06 to NT16)

2000/6300 A (NW40b to NW63)


E67969

E47697A

1000/4000 A (NW25 to NW40)

2 identical external sensor shipped as loosed part

78

Masterpact

Schneider Electric

Rectangular sensor for earth leakage protection (Vigi)


280 x 115 mm window

E47703A

E47704B

4 9

115

2 M3
M1 M

197
215

M1 M2 M3

70

280
362
380

470 x 160 mm window

E47717A

E47718B

8 9

146
2
M1 M

242
160
260

M3

M1 M2 M3

70

456
470
552
570

Busbars
window (mm)
weight (kg)

I i 1600 A

I i 3200 A

280 x 115
14

470 x 160
18

Busbars path
470 x 160 window
Busbars spaced 115 mm centre-to-centr
E47708

E47707

280 x 115 window


Busbars spaced 70 mm centre-to-centre

M1 M2 M3

M1 M2 M3

2 bars 50 x 10

E67971

E67970

4 bars 100 x 5

M1 M2 M3

M1 M2 M3

2 bars 100 x 5
4 bars 125 x 5

79

Masterpact

Schneider Electric

80

Masterpact

Schneider Electric

Electrical diagrams

Masterpact

Presentation
Functions and characteristics
Dimensions and connection

1
9
53

Masterpact NT06 to NT16


Masterpact NW08 to NW63
Masterpact NT and NW

82
84
86

Installation recommendations
Additional characteristics
References

81

Masterpact

91
115
121

Schneider Electric

Masterpact NT06 to NT16


Fixed and drawout devices

Electrical diagrams

The diagram is shown with circuits


de-energised, all devices open, connected
and charged and relays in normal position.

readyto-close

fault

fault

Z5

Z4

Z3

Z1

downstream cb
Z5

Z4

L3

Z3

L2

Z2

L1

Z1

Remote operation

upstream cb

AT

charged

Control unit

power

Z2

Power

BPF

M6C

MCH

Q
SDE1 MN
Res

UC2

B1

251

E46138A

A1

D1

E46135A

81

181

E46139A

or

or
E46133

471

E46132A

F2+

F1

T4

T3
X2

T2
X1

T1
SG2

M3
SG1

M2

M1

E46555B

Com UC1

CH

24 V DC

Remote operation

Control unit
Terminal block marking

PF

E46137A

M6C
or

K1

M2C

XF

MX1

E46136A

MX2

C1

SDE2

S1 S2

Micrologic

C11

B2

B3

254

A3

252

A2

C3

C2

C12

D2

84

82

K2

184

182

Q3

Q2

Q1

484

474

Z5

Z4

Z3

Z2

Z1

V3

V2

V1

VN

BPO

UC3

UC4 / M2C / M6C

SDE2 / Res

E5 E6 Z5 M1 M2 M3

F2+

V3

/ 484

/ Q3

184

E3 E4 Z3 Z4 T3 T4

VN

V2

/ 474

/ Q2

182

E1 E2 Z1 Z2 T1 T2

F1

V1

/ 471

/ Q1

181

Control unit

K2

SDE1
84

MN / MX2
D2

/ C12

82
/

K1

81

D1

/ C11

MX1

XF

PF

MCH

C2

A2

254

B2

C3

A3

252

B3

C1

A1

251

B1

Remote operation

Com: E1-E6 communication

UC1 : Z1-Z5 zone selective interlocking;


Z1 = ZSI OUT SOURCE
Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE
Z4 = ZSI IN ST (short time)
Z5 = ZSI IN GF (earth fault)
M1 = Vigi module input (Micrologic 7)

SDE2: Fault-trip indication contact


or
Res : Remote reset
SDE1: Fault-trip indication contact (supplied as standard)
MN : Undervoltage release
or
MX2 : Shunt release

c
c

c
c

c
c

UC2 : T1, T2, T3, T4 = external neutral;


M2, M3 = Vigi module input
(Micrologic 7)

MX1 : Shunt release (standard or communicating)


XF

: Closing release (standard or communicating)

PF

: Ready-to-close contact

UC3 : F2+, F1 external 24 DC power


supply
VN external voltage connector (optional)

UC4 : optional external voltage connector

M2C : 2 programmable contacts (internal relay);


ext. 24V DC power supply required
or

M6C : 6 programmable contacts (external relay);


ext. 24V DC power supply required.

MCH: electric motor

or
Note:
When communicating MX or XF releases are used, the third wire
(C3,A3) must be connected even if the communication module is
not installed.

A : Digital ammeter
P: A + power meter + additional protection
H: P + harmonics

82

Masterpact

Schneider Electric

Craddle contacts

OF4

OF3

OF2

OF1

CD2

44

34

24

14

42

32

22

12

41

31

21

11

Indication contacts
OF4 / OF3 / OF2 / OF1 : ON/OFF indication contacts

914

912

314

312

324

E47074A

311

911

CE1

321

CE2

CD1

CE3

CE2

CE1

CT1

824

814

334

324

314

914

822

812

332

322

312

912

821

811

331

321

311

911

Craddle contacts
CD2: Disconnected
CD1 position
contacts

(*) Spring charging motor 440/480 V AC


(380 V motor + additional resistor)

CE3: Connected
CE2 position
CE1 contacts

CT1: Test
position
contacts

- 440/480 V
9

spring
charged
light
440/480 V

322

332

814

CE3

E46134A

821

E47075A

11

21

31

41

E46141A

812

824

12

822

CT1
CD1

Indication contacts

CN1

Test

OF1
CD2

E47484

connected

331

OF2

14

22

OF3

disconnected

811

OF4

24

32

closed

34

44

42

open

Craddle contacts

334

Indication contacts

11

R
B3 B2

MCH
380V

CH

B1
CN2

key:

- 440/480 V

Drawout device only

XXX

SDE1, OF1, OF2, OF3, OF4 supplied as standard


Interconnected connections
(only one wire per connection point)

83

Masterpact

Schneider Electric

Masterpact NW08 to NW63


Fixed and drawout devices

Electrical diagrams

The diagram is shown with circuits


de-energised, all devices open, connected
and charged and relays in normal position.

readyto-close

fault

fault

Z5

Z4

Z1

downstream cb
Z5

Z4

L3

Z3

upstream cb
L2

Z2

L1

Z1

Z3

power

Remote operation

AT

charged

Control unit

Z2

Power

BPF

M6C

B2

B3

254

A3

252

A2

C3

C2

C12

D2

84

82

K2

184

182

Q3

Q2

Q1

484

474

Z5

Z4

Z3

Z2

Z1

V3

V2

V1

VN

BPO

MCH

SDE1 MN

SDE2

S1 S2

Micrologic
U

MX2

XF

MX1

PF

CH

Res

E46139A

B1

251

E46138A

A1

E46137A

E46136A

C1

D1

81

181

E46135A

E46133

471

E46132A

F2+

T4

F1

T3
X2

T2
X1

M3

T1
SG2

24 V DC

E46555B

SG1

M2

M1

or

or

C11

M6C
ou

K1

M2C

Remote operation

Control unit
Terminal block marking

A
c
c

P
c
c

Com UC1

UC2

UC3

UC4

M2C / M6C

SDE2 / Res

E5 E6 Z5 M1 M2 M3

F2+

V3

484

/ Q3

184

E3 E4 Z3 Z4 T3 T4

VN

V2

474

/ Q2

182

E1 E2 Z1 Z2 T1 T2

F1

V1

471

/ Q1

181

Control unit

K2

SDE1
84

MN / MX2
D2

/ C12

82
/

K1

81

D1

/ C11

MX1

XF

PF

MCH

C2

A2

254

B2

C3

A3

252

B3

C1

A1

251

B1

Remote operation

Com: E1-E6 communication

UC1 : Z1-Z5 zone selective interlocking;


Z1 = ZSI OUT SOURCE
Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE
Z4 = ZSI IN ST (short time)
Z5 = ZSI IN GF (earth fault)
M1 = Vigi module input (Micrologic 7)

c
c

c
c

c
c

UC2 : T1, T2, T3, T4 = external neutral;


M2, M3 = Vigi module input
(Micrologic 7)

UC3 : F2+, F1 external 24 DC power


supply
VN external voltage connector (optional)

UC4 : V1, V2, V3 optional external voltage


connector

M2C : 2 programmable contacts (internal relay);


ext. 24V DC power supply required
or

M6C : 6 programmable contacts


(to be connected to the external module
M6C);
ext. 24V DC power supply required

SDE2: Fault-trip indication contact


or
Res : Remote reset
SDE1: Fault-trip indication contact (supplied as standard)
MN : Undervoltage release
or
MX2 : Shunt release
MX1 : Shunt release (standard or communicating)
XF

: Closing release (standard or communicating)

PF

: Ready-to-close contact

MCH: electric motor

Note:
When communicating MX or XF releases are used, the third wire
(C3,A3) must be connected even if the communication module is
not installed.

A : Digital ammeter
P: A + power meter + additional protection
H: P + harmonics

84

Masterpact

Schneider Electric

Indication contacts

914

912

924

922

934

932

314

312

Test

324

814

332

812

824

822

834

832

..6

322

connected

disconnected

334

connected
and closed

..8

..4

..2

12

14

22

24

32

not
connected
or
connected
and open

closed

closed

34

42

44

open

Craddle contacts

EF . .

OF4

OF3

OF2

OF . .

OF1

OF

CT3
CD3

CD2

CD1

CE3

CE2

CT2

CT1

CE1

or

Indication contacts

911

921

931

E46142A

311

321

331

E46134A

811

CD3

CD2

CD1

114

834

824

814

334

324

314

934

924

914

122

112

832

822

812

332

322

312

932

922

912

131

121

111

831

821

811

331

321

311

931

921

911

or

or

or

OF3

OF2

OF1

44

34

24

14

244

234

224

214

144

134

124

42

32

22

12

242

232

222

212

142

132

41

31

21

11

241

231

221

211

141

or

or

or

or

or

EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11

CE3

CE2

CE1

CT3

or
CE6

CE5

CT2

CT1

or
CE4

CE9

CE8

CE7

248

238

228

218

148

138

128

118

364

354

344

394

384

374

246

236

226

216

146

136

126

116

362

352

342

392

382

372

245

235

225

215

145

135

125

115

361

351

341

391

381

371

Indication contacts
: ON/OFF
indication
contacts

821

Craddle contacts
OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11

OF4

OF4
OF3
OF2
OF1

831

E46131A

..5

..1

11

21

31

41

E46141A

E46140

CE

Craddle contacts
OF24
or
EF24

: ON/OFF
indication contacts
Combined connected-deconnected
indication contacts

OF23 or
EF23
OF22 or
EF22

CD3: Disconnected CE3: Connected


CD2 position
CE2 position
CD1 contacts
CE1 contacts

CT3: Test
CT2 position
CT1 contacts

or

or

CE6: Connected
CE5 position
CE4 contacts

CE9:Connected
CE8 position
CE7 contacts

OF21 or
EF21

or

OF14 or
EF14

CD6:Disconnected
CD5 position
CD4 contacts

key:

OF13 or
EF13

Drawout device only

OF12 or
EF12

XXX

SDE1, OF1, OF2, OF3, OF4 supplied as standard


Interconnected connections
(only one wire per connection point)

OF11 or
EF11

85

Masterpact

Schneider Electric

Masterpact NT and NW
Communications option
24 VDC external power supply

Electrical diagrams

E47593

Connection of the communications option


914
L3

812

314

912 812

312

SDE

MX1

com

911

PF

CT

CD

CE

Modbus
COM craddle

CE

BB
BB
B' A' B A

E6

E5

E4

E3

E2

E1

F2+

F1

T4

T3

T2

T1

M3

M2

CD

Digipact
COM craddle

+
(2)

CCP 303
M1

311

811

CT
+

B'
A'
B
A

device
communication
module

911

CCP 303

H1 H2

BB
BB

com

Micrologic

311

XF

CH

811

shield

Z5

Z4

Z3

Z2

Z1

V3

microswitch
built into
COM module
OF
V2

L2

V1

L1

VN

BAT
module

(1)

H3 H4

(2)

L3 L4

110/240 V AC
24/125 V DC

blue

white

yellow

brown

black

red

E1 E2 E3 E4
+
A B
+
/
/
E3 / E4
E5 / E6

Digipact
junction
block

G1 G2

AD
module

Modbus
junction
block
CJB306

E5 E6
A' B'
Modbus
BB BB + Digipact
twisted pair
twisted pair

24 V
0V

0V
24 VDC
1A

communication
power supply

24 V

24 VDC
DC 150

None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power-supply (AD module) is
required for certain operating configurations as indicated in the table below.
circuit breaker
voltage measurement inputs
M2C, M6C programmable contacts option
Protection function
Display function
Time-stamping function
Circuit-breaker status indications and
control via communications bus
Identification, settings, operation and
maintenance aids via communications bus

(1) draw-out device equipped with Modbus craddle COM.


(2) draw-out device equipped with Digipact craddle COM.
(3) except for Micrologic A control units (if current < 20% In).
(4) except for Micrologic A control units.
(5) time setting is manual and can be carried out
automatically by the supervisor via the communications bus.

closed
powered

open
powered

not powered

yes
no
no (3)
no
no

yes
no
no (4)
no
no

yes
no
yes
yes (5)
no

no (3)

no (4)

yes

The communications bus requires its own 24 V DC power source (E1, E2). This source
is not the same as the 24 V DC external power-supply module (F1-, F2+).
In case of using the 24 VDC external power supply (AD module), maximum cable length
between 24 VDC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The BAT battery module, mounted in series upstream of the AD module, ensures an
uninterrupted supply of power if the AD module power supply fails.
The voltage measurement inputs are standard equipment on the downstream
connectors of the circuit breaker.
External connections are possible using the PTE external voltage measurement input
option. With this option, the internal voltage measurement inputs are disconnected and
terminals VN, V1 and V2 are connected only to the control unit (Micrologic P and H only).
The PTE option is required for voltages less than 100 V and greater than 690 V (in which
case a voltage transformer is compulsory). For three-pole devices, the system is
supplied with terminal VN connected only to the control unit (Micrologic P and H).
When the PTE option is implemented, the voltage measurement input must be protected
against short-circuits. Installed as close as possible to the busbars, this protection
function is ensured by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat.
no. 21104 and 21117). This voltage measurement input is reserved exclusively for the
control unit and must not ever be used to supply other circuits outside the switchboard.

86

Masterpact

Schneider Electric

Examples using the COM communications option


Switchboard display unit

CDM303 + CSD309
E47976

This architecture provides remote display of the


variables managed by Micrologic control units
equipped with the eco COM Modbus module.
c I (Micrologic A)
c I, U, P, E (Micrologic P)
c I, U, P, E, THD (Micrologic H)
No programming is required.
For Micrologic A control unit (if current < 20% In), it is
recommended to use the 24 VDC external power
supply (AD module).

d < 1 km
DMB300

2
3
4

CCP303

switchboard
display unit

1
0
24 V
0V

Modbus
junction
block
CJB 306

24 VDC
1A

power circuit
breaker

Communicating switchboard

E47977

This configuration provides remote display and control


of Masterpacts equipped with the Modbus or Digipact
COM module. The Digipact bus can be combined with
the Modbus bus.

Software

PC running

PC running

Micrologic utilities
SMS

Micrologic utilities
SMS

PLC

PLC

TCP/IP

Communication
interface
RS 232C

Ethernet

RS 485

RS 485

Bus Modbus

communication
Bus

Data
concentrator

Bus Modbus

DC150

Device

UA150
source
change-ower

SC150
contraf
interface

PM150
measure

Masterpact
COM Digipact

Masterpact
COM Modbus

Digipact Bus

PM300
measure

Sepam

Vigilohm

Altivar

Modbus Bus

87

Masterpact

Schneider Electric

Masterpact NT and NW
Earth-fault and earth-leakage protection
Neutral protection
Zone selective interlocking

Electrical diagrams

External sensor (CT) for residual earth-fault protection


Z4

Z5

Z3

T4

Z2

T3

Z1

V3

L3

V2

L2

VN

L1

V1

E47591B

Q
I
Micrologic 6

F2+

F1

T2

T1

M3

M2

M1

Connection of current-transformer secondary


circuit for external neutral
Masterpact equipped with a Micrologic 6 A/P/H:
c shielded cable with 2 twisted pairs
c SG1 twisted with SG2
c X1 twisted with X2
c shielding connected to GND on one end only
c maximum length 5 meters
c cable cross-sectional area 0.4 to 1.5 mm2
c recommended cable: Belden 9552 or equivalent.
If supply is via the top, follow the shematics.
If supply is via the bottom, control wiring is identical;
for the power wiring, H1 is connected to the source
side, H2 to the load side.
For four-pole versions, for residual earth-fault
protection, the current transformer for the external
neutral is not necessary.
If the 2000/6300 current transformer is used:
c signals SG1 and SG2 must be wired in series
c signals X1 and X2 must be wired in parallel.
Connection for signal VN is required only for power
measurements (3 , 4 wires, 4CTs).

VN
H2

SG1
SG2
X1
X2

H1
GND

Z4
T4

Z5

Z3
T3

Z2

Z1

V3

V2

VN

Connection of the secondary circuit


Masterpact equipped with a Micrologic 6 A/P/H:
c unshielded cable with 1 twisted pair
c maximum length 150 meters
c cable cross-sectional area 0.4 to 1.5 mm2
c terminals 5 and 6 may not be used at the same time
c use terminal 5 for NW08 to 40
c use terminal 6 for NW40b to 63
c recommended cable: Belden 9409 or equivalent.

V1

External transformer for source ground return (SGR) earth-fault protection

Q
I
Micrologic 6

F2+

F1

T1

T2

M3

M2

M1

or

E47592

H1

88

H2

X1

12 5
1
3

X2

MDGF module
13 14

10 11
9
8

PE

Masterpact

Schneider Electric

Earth-leakage protection

Z4

Z5

Z3

T4

Z2

T3

Z1

V3

L3

V2

L2

VN

L1

V1

E47974B

Connection of the rectangular-sensor secondary


circuit
Masterpact equipped with a Micrologic 7 A/P/H:
c unshielded cable with 3 twisted conductors:
v M1, M2, M3 twisted together
c maximum length 4 metres
c cable cross-sectional area 0.4 to 1.5 mm2
c recommended cable: Belden 9493 or equivalent.

Q
I
Micrologic 7

F2+

F1

T2

T1

M3

M2

M1

M1
M2
M3

Neutral protection
c Three pole breaker:
v Masterpact equipped with Micrologic P or H
v the current transformer for external neutral is
necessary (the wiring diagram is identical to the one
used for the residual earth-fault protection).
c Four pole breaker:
v Masterpact equipped with Micrologic A, P or H
v the current transformer for external neutral is not
necessary.

A pilot wire interconnects a number of circuit breakers


equipped with Micrologic A/P/H control units, as illustrated
in the diagram above.
The control unit detecting a fault sends a signal upstream
and checks for a signal arriving from downstream. If there
is a signal from downstream, the circuit breaker remains
closed for the full duration of its tripping delay. If there is
no signal from downstream, the circuit breaker opens
immediately, whatever the tripping-delay setting.
Fault 1.
Only circuit breaker A detects the fault. Because it
receives no signal from downstream, it immediately opens
in spite of its tripping delay set to 0.3.
Fault 2.
Circuit breakers A and B detect the fault. Circuit breaker A
receives a signal from B and remains closed for the full
duration of its tripping delay set to 0.3. Circuit breaker B
does not receive a signal from downstream and opens
immediately, in spite of its tripping delay set to 0.2.

E47975B

Zone selective interlocking


upstream
circuit breaker

Z1
Z2
Z3
Z4
Z5

tsd = 0,3

fault 1

Z1
Z2
Z3
Z4
Z5

tsd = 0,2

fault 2

Z1
Z2
Z3
Z4
Z5

Note: the maximum permissible distance between


two devices is 3000 m and the maximum number
of devices is 100.

89

Masterpact

downstream
circuit breaker

Z1
Z2
Z3
Z4
Z5

Schneider Electric

90

Masterpact

Schneider Electric

Installation recommendations

Masterpact

Presentation
Functions and characteristics
Dimensions and connection
Electrical diagrams

1
9
53
81

Operating conditions
Installation in switchboard
Door interlock catch
Cable-type door interlock
Connection of MN, MX and XF voltage releases
Power connection
Recommended busbars drilling
Busbar sizing
Temperature derating
Power dissipation and input/output resistance
Derating in switchboards
Substitution kit
Additional characteristics
References

91

Masterpact

92
94
96
97
97
98
100
102
104
104
105
112
115
121

Schneider Electric

Operating conditions

Installation
recommendations

E51260B

Ambient temperature
Masterpact devices can operate under the following temperature conditions:
c the electrical and mechanical characteristics are stipulated for an ambient
temperature of -5 C to +70 C;
c circuit-breaker closing is guaranteed down to -35 C;
Storage conditions are as follows:
c -40 to +85C for a Masterpact device without its control unit
c -25C to +85C for the control unit.

E51261B

Test

Extreme atmospheric conditions


Masterpact devices have successfully passed the tests defined by the following
standards for extreme atmospheric conditions:
c IEC 68-2-1: dry cold at -55 C;
c IEC 68-2-2: dry heat at +85 C;
c IEC 68-2-30: damp heat (temperature +55 C, relative humidity 95%);
c IEC 68-2-52 level 2: salt mist.
Masterpact devices can operate in the industrial environments defined by standard
IEC 947 (pollution degree up to 4).
It is nonetheless advised to check that the devices are installed in suitably cooled
switchboards without excessive dust.

Test

Vibrations
E51262B

Masterpact devices are guaranteed against electromagnetic or mechanical


vibrations.
Tests are carried out in compliance with standard IEC 68-2-6 for the levels required
by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
c 2 to 13.2 Hz: amplitude 1 mm;
c 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.

Test

92

Masterpact

Schneider Electric

E51263B

Altitude

2000 m

At altitudes higher than 2000 metres, the modifications in the ambient air (electrical
resistance, cooling capacity) lower the following characteristics as follows:

E51264B

Test

Altitude (m)
Dielectric resistance
voltage (V)
Average insulation
level (V)
Maximum utilisation
voltage (V)
Average thermal
current (A) at 40 C

2000
3500

3000
3150

4000
2500

5000
2100

1000

900

700

600

690

590

520

460

1 x In

0.99 x In

0.96 x In

0.94 x In

Electromagnetic disturbances

Test

Masterpact devices are protected against:


c overvoltages caused by devices that generate electromagnetic disturbances;
c overvoltages caused by atmospheric disturbances or by a distribution-system
outage (e.g. failure of a lighting system);
c devices emitting radio waves (radios, walkie-talkies, radar, etc.);
c electrostatic discharges produced by users.
Masterpact devices have successfully passed the electromagnetic-compatibility
tests (EMC) defined by the following international standards:
c IEC 60947-2, appendix F;
c IEC 60947-2, appendix B (trip units with earth-leakage function).
The above tests guarantee that:
c no nuisance tripping occurs;
c tripping times are respected.

93

Masterpact

Schneider Electric

Installation in switchboard

Installation
recommendations

E47652A

E47651A

E47650A

Possible positions

Power supply

E47653A

Masterpact devices can be supplied either from the top or from the bottom without
reduction in performance, in order to facilitate connection when installed in a
switchboard.

Mounting the circuit-breaker

E47656A

E47657A

It is important to distribute the weight of the device uniformily over a rigid mounting
surface such as rails or a base plate.
This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm).
This eliminates any risk of deformation which could interfere with correct operation
of the circuit breaker.
Masterpact devices can also be mounted on a vertical plane using the special
brackets.

E47658A

Mounting on rails.

Mounting with vertical brackets.

94

Masterpact

Schneider Electric

E47659A

Partitions
Sufficient openings must be provided in partitions to
ensure good air circulation around the circuit breaker;
For high currents, of 2500 A and upwards, the metal
supports or barriers in the immediate vicinity of a
conductor must be made of non-magnetic material A;
Metal barriers through which a conductor passes must
not form a magnetic loop.

a
A

a
E47661A

E47660A

A : non magnetic material

Busbars

non magnetic
material

E47662B

The mechanical connection must be exclude the


possibility of formation of a magnetic loop around a
conductor.

E47663A

Increases the length of the tracking path between


phases;
Reduces the risk of short circuits being caused by
objects falling from above onto circuit breaker
connections.

E47664

Interphase barrier

351 (NT)
453 (NW)

Dimensions and weights

Main dimensions in mm (H x W x D)

Masterpact
drawout
fixed

3P
4P
3P
4P

NT06/12
322 x 288 x 280
322 x 358 x 280
301 x 276 x 211
301 x 346 x 211

NW08/40
439 x 441 x 395
439 x 556 x 395
352 x 422 x 297
352 x 537 x 297

NW40b/63
479 x 786 x 395
479 x 1016 x 395
352 x 767 x 297
352 x 997 x 297

3P
4P
3P
4P

NT06/12
30
39
14
18

NW08/40
90
120
60
80

NW40b/63
225
300
120
160

Weight (kg)

Masterpact
drawout
fixed

95

Masterpact

Schneider Electric

Door interlock catch

Mounted on the right or left-hand side of the craddle,


this device inhibits opening of the cubicle door when
the circuit breaker is in connected or test
position. It the breaker is put in the connected
position with the door open, the door may be closed
without having to disconnect the circuit breaker.

E47669B

Installation
recommendations

15
(1)
8

(2)

Catch not supplied


17

Dimensions (mm)
Type
NT08-16 (3P)
NT08-16 (4P)
NW08-40 (3P)
NW08-40 (4P)
NW40b-63 (3P)
NW40b-63 (4P)

(1)
135
205
215
330
660
775

(2)
168
168
215
215
215
215

Breaker in connected or test position


E47670A

Door cannot be opened

door

Dimensions (mm)

F
(1)
(2)

Type
NT
NW

(1)
5
83

(2)
23
103

Breaker in disconnected position


E47671A

Door can be opened

Note: The door interlock can either be mounted on the


right side or the left side of the breaker.
F Datum.

96

Masterpact

Schneider Electric

Cable-type door interlock


Connection of MN, MX and XF
voltage releases
NT/NW
Cable-type door interlock

E59115A

E59113A

This option prevents door opening when the circuit breaker is closed and prevents
circuit breaker closing when the door is open.
For this, a special plate associated with a lock and a cable is mounted on the right
side of the circuit breaker.
With this interlock installed, the source changeover function cannot be
implemented.

E59114B

46
121
165
10

79

84

52

Wiring of voltage releases


During pick-up, the power consumed is approximately 150 to 200 VA. For low
control voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage
and the cross-sectional area of cables.
Recommanded maximum cable lengths (meter)
12 V
2,5 mm2
MN
U source 100 %
U source 85 %

MX-XF U source 100 % 21


U source 85 %
10

24 V
1,5 mm2

12
6

2,5 mm2
58
16
115
75

48 V
1,5 mm2
35
10
70
44

2,5 mm2
280
75
550
350

1,5 mm2
165
45
330
210

Note: the indicated length is that of each of the two wires

97

Masterpact

Schneider Electric

E47676A

aa

If cables are used for the power connections, make


sure that they do not apply excessive mechanical
forces to the circuit breaker terminals.
For this, make the connections as follows:
c extend the circuit breaker terminals using short bars
designed and installed according to the
recommendations for bar-type power connections:
v for a single cable, use solution B opposite
v for multiple cables, use solution C opposite.
c in all cases, follow the general rules for connections
to busbars:
v position the cable lugs before inserting the bolts
v the cables should firmly secured to the framework of
the switchboard.

E47675A

Cables connections

Power connection

Installation
recommendations

E47673A

E47677A

E47672A

The busbars should be suitably adjusted to ensure


that the connection points are positioned on the
terminals before the bolts are inserted B
The connections are held by the support which is
solidly fixed to the framework of the switchboard, such
that the circuit breaker terminals do not have to
support its weight C. (This support should be placed
close to the terminals).

E47674A

Busbars connections

Electrodynamic stresses
The first busbar support or spacer shall be situated within a maximum distance
from the connection point of the breaker (see table below). This distance must be
respected so that the connection can withstand the electrodynamic stresses
between phases in the event of a short circuit.

Maximum distance A between busbar to circuit breaker connection and the first busbar
support or spacer with respect to the value of the prospective short-circuit current.
Isc (kA)
30
50
65
80
100
150
distance A (mm)
350
300
250
150
150
150

98

Masterpact

Schneider Electric

Clamping
Correct clamping of busbars depends amongst other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same
consequences as under-tightening.
For connecting busbars (Cu ETP-NFA51-100) to the circuit breaker, the tightening
torques to be used are shown in the table below.
These values are for use with copper busbars and steel nuts and bolts, class 8.8.
The same torques can be used with AGS-T52 quality aluminium bars (French
standard NFA 02-104 or American National Standard H-35-1).

E47665

E47667B

E47668

Examples

6
1 terminal screw factory-tightened to 16 Nm (NW), 13 Nm (NT)
2 breaker terminal
3 busbar
4 bolt
5 washer
6 nut

Tightening torques

nominal (mm)
drilling (mm)
10

11

tightening torque (Nm)


with grower or
flat washers

with contact
or corrugatec
washers

37.5

50

E47331A

E47330A

E47329A

Busbar drilling
Examples

E47680A

Isolation distance

X
Dimensions (mm)
Ui
600 V
1000 V

X min
8 mm
14 mm

Busbar bending
When bending busbars maintain the radius indicated below(a smaller radius would
cause cracks).
E47679A

E47678A

r
e

Dimensions (mm)
e
5
10

99

radius of curvature r
min

recommended

5
15

7.5
18 to 20

Masterpact

Schneider Electric

Recommended busbars drilling


Masterpact NT06 to NT16

Installation
recommendations

12,5

12,5

25

38,5
25

9,5 12,5

13,5

25 25

12,5

38,5
=

25

13,5

82 52

38,5
=

25

13,5

5 11

15
5 11

5 11

25

25

13,5

=
30

82 52

15

2 11

25

25

52

52

38,5
=

25
30

82 52

15

77

30
82 52

15
5 11

Left or right spreader


for 3P

77

30

60
12,5

12,5

Left or right spreader


for 4P

77

15
12 maxi

Middle spreader
for 3P
E59326A

E59325A

E59324A

25

77

80
15

12,5
12 maxi

12,5

Middle left or middle


right spreader for 4P

44

E59310A

25,5

12,5
12 maxi

25

63

E59328A

25

50

E59327A

12,5
12 maxi

E59309A

50
12,5

Rear connection with spreaders


E59308A

E59308A

Rear connection

52

52

12 maxi

25

E59329A

12,5

12 maxi

25

12,5

50

12,5

12 maxi

25
12,5

12,5

E59315 A

40

E59314A

32

E59313A

E59312A

E59311A

Vertical rear connection


63

12 maxi

25

12,5

80

12 maxi

25

12,5 12,5

12,5

12,5

60
12,5
9,5

12,5

25 44

2 11

12,5

12,5
12 maxi

25

12,5

25

Bottom connection

25

9,5

E59331A

44
25

12,5
12 maxi

12,5

Top connection
E59330A

50

2 11

89
= =

63
25,5

80
15

15

12,5
12 maxi

25

12,5

E59310A

50

E59309A

E59308A

Front connection via vertical connection adapters

E59332A

E59308A

Front connection

12,5

12 maxi

25 25

12,5

12,5
15

21
13

101

21
3 11

13
2 11

15
25
44

20

9,5

100

Masterpact

Schneider Electric

Masterpact NW08 to NW63

12,5

12,5
12 maxi

E59333A

25

25,5

80
15

15

12,5
12 maxi

12,5

25

25 25

12,5

100
28

22

12 maxi

12,5

25 25

E59323A

13

= =

25

28

12 maxi

76
38

100
22

E59317A

63

NW40b to NW50
E59316A

50

E59310A

E59309A

E59308A

Horizontal rear connection NW08 to NW38

12 maxi

25 25

12,5

12,5

115

115

115

115

115

39

39

39

39

39

12,5
47

3 11,5

14,5

25

12,5

12 maxi

25

12,5

12,5

12,5 12,5

100

25

25
12 maxi

25

12,5

80

E59322A

63

25

25

12 maxi

25

E59334A

50

E59321A

E59319A

E59318A

40

E59320A

Vertical rear connection NW08 to NW32, NW40b to NW50

12 maxi

25
12,5

12,5

12 maxi

25
12,5

12,5

47
14,5

12,5
13
=
76

=
3 11,5

38
25

50
12,5

12,5
12 maxi

25

12,5

80
15

15

12,5
12 maxi

25

12 maxi

25 25

12,5

12,5

Bottom connection

76
25 25

13

12,5

E59336A

E59335A

63
25,5

Top connection

E59310A

E59309A

E59308A

Front connection NW08 to NW32

3 11,5

3 11,5
12,5

25 25

13

101

Masterpact

Schneider Electric

Busbar sizing

Installation
recommendations

Basis of tables:
c maximum permissible busbars temperature: 100 C
c Ti: temperature around the circuit breaker and its
connection
c busbar material is unpainted copper.

E47681A

Front or rear horizontal connection

maximum
service
current

Ti : 40 C
no. of 5 mm
thick bars

NT06
NT06
NT08 or NW08
NT10 or NW10
NT12 or NW12

400
630
800
1000
1250

NT16 or NW16
NT16 or NW16
NW20
NW20
NW25
NW25
NW32
NW32
NW32
NW40
NW40
NW50
NW50

1400
1600
1800
2000
2200
2500
2800
3000
3200
3800
4000
4500
5000

2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
3b.50 x 5
3b.63 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
6b.100 x 5

Masterpact

no. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.40 x 10
2b.40 x 10
2b.50 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.80 x 10
3b.100 x 10
4b.100 x 10
5b.100 x 10
6b.100 x 10
7b.100 x 10

Ti : 50 C
no. of 5 mm
thick bars
2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
2b.80 x 5
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
6b.100 x 5
8b.100 x 5

no. of 10 mm
thick bars

Ti : 60 C
no. of 5 mm
thick bars

no. of 10 mm
thick bars

1b.30 x 10
1b.40 x 10
1b.50 x 10
2b.50 x 10
2b.50 x 10

2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.63 x 5
3b.63 x 5

1b.30 x 10
1b.40 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10

2b.50 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
3b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
7b.100 x 10

3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.80 x 5
4b.100 x 5
5b.100 x 5
8b.100 x 5

2b.63 x 10
3b.50 x 10
2b.80 x 10
3b.63 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.80 x 10
4b.100 x 10
5b.100 x 10
6b.100 x 10
7b.100 x 10

With Masterpact NT, it is recommanded to use 50 mm wideness bars (see "Recommended busbars drilling")

Example
Conditions:
c drawout version
c horizontal busbars
c Ti: 50 C
c service current: 1800 A.
Solution:
For Ti = 50 C, use an NW20 which can be connected
with three 80x5 mm bars or two mm 63x10 bars.

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

102

Masterpact

Schneider Electric

Basis of tables:
c maximum permissible busbars temperature: 100 C
c Ti: temperature around the circuit breaker and its
connection
c busbar material is unpainted copper.

E47682A

Rear vertical connection

Masterpact

NT06
NT06
NT08 or
NT10 or
NT12 or
NT16 or
NT16 or

NW08
NW10
NW12
NW16
NW16
NW20
NW20
NW25
NW25
NW32
NW32
NW32
NW40
NW40
NW50
NW50
NW63
NW63

Maximum
service
current

Ti: 40 C
no. of 5 mm
thick bars

400
630
800
1000
1250
1400
1600
1800
2000
2200
2500
2800
3000
3200
3800
4000
4500
5000
5700
6300

2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.63 x 5
2b.80 x 5
2b.80 x 5
2b.100 x 5
2b.100 x 5
4b.80 x 5
4b.100 x 5
5b.100 x 5
6b.100 x 5

no. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.63 x 10
1b.80 x 10
1b.80 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
7b.100 x 10
8b.100 x 10

Ti: 50 C
no. of 5 mm
thick bars
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.63 x 5
2b.80 x 5
2b.80 x 5
2b.100 x 5
2b.100 x 5
4b.80 x 5
4b.100 x 5
6b.100 x 5
6b.100 x 5

no. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.63 x 10
1b.80 x 10
2b.50 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.100 x 10
3b.100 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
6b.100 x 10
7b.100 x 10
8b.100 x 10

Ti: 60 C
no. of 5 mm
thick bars
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.63 x 5
3b.50 x 5
3b.50 x 5
3b.63 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5

no. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10
2b.50 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
3b.80 x 10
3b.80 x 10
4b.80 x 10
4b.100 x 10
4b.100 x 10
4b.100 x 10
6b.100 x 10
7b.100 x 10
8b.100 x 10

Example
Conditions:
c drawout version
c vertical connections
c Ti: 40 C
c service current: 1100 A.
Solution :
For Ti = 40 C use an NT12 or NW12 which can be
connected with two 63 x 5 mm bars or with
one 63 x 10 mm bar.

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

103

Masterpact

Schneider Electric

Temperature derating

Installation
recommendations

Temperature derating
The table below indicates the maximum current rating,
for each connection type, as a function of the ambient
temperature around the circuit breaker and the
busbars.
Circuit breakers with mixed connections have the
same derating as horizontally connected breakers.
For ambient temperatures greater than 60 C,
consult us.
Ti: temperature around the circuit breaker and its
connection
version

drawout

connection

front or rear horizontal

temp. Ti

40

45

fixed
50

55

rear vertical
60

40

45

front or rear horizontal


50

55

60

40

45

NT06 H1/L1
NT08 H1/L1
NT10 H1/L1
NT12 H1
NT16 H1

630
800
1000
1250
1600

630
800
1000
1250
1520 1480 1430 1600

NW08 N/H/L
NW10 N/H/L
NW12 N/H/L
NW16 N/H/L
NW20 H1/H2/H3
NW20 L1
NW25 H1/H2/H3
NW32 H1/H2/H3
NW40 H1/H2/H3

800
1000
1250
1600
2000
2000
2500
3200
4000

3100 3000 2900


3900 3750 3650

800
1000
1250
1600
2000
2000
2500
3200
4000

800
1000
1250
1600
2000

2500
3200
3850 4000

NW40b H1/H2
NW50 H1/H2
NW63 H1/H2

4000
5000

4000
5000
6300

4000
5000
6200

1980 1890
1900 1850 1800

50

55

630
800
1000
1250
1560 1510 1600

rear vertical
60

40

45

50

55

60

630
800
1000
1250
1550 1600

800
1000
1250
1600
1920 2000

2500
3200
3900 3800 4000

4000
5000
6300

Power dissipation and input / output


resistance
Total power dissipation is the value measured at IN,
50/60 Hz, for a 3 pole or 4 pole breaker (values above
the power P = 3RI2).
The resistance between input / output is the value
measured per pole (cold state).
version
NT06 H1/L1
NT08 H1/L1
NT10 H1/L1
NT12 H1
NT16 H1
NW08 N1
NW08 H/L
NW10 N1
NW10 H/L
NW12 N1
NW12 H/L
NW16 N1
NW16 H/L
NW20 H/L
NW25 H1/H2/H3
NW32 H1/H2/H3
NW40 H1/H2/H3
NW40b H1/H2
NW50 H1/H2
NW63 H1/H2

drawout

fixed

power dissipation (Watts)

input/output resistance (ohm)

power dissipation (Watts)

input/ouput resistance (ohm)

55/115 (H1/L1)
90/140 (H1/L1)
150/230 (H1/L1)
250
460
137
100
220
150
330
230
480
390
470
600
670
900
550
590
950

38/72
38/72
38/72
36
36
42
30
42
30
42
27
37
27
27
19
13
11
7
7
7

30/45
50/80
80/110
130
220
62
42
100
70
150
100
220
170
250
260
420
650
390
420
660

26/39
26/39
26/39
26
26
19
13
19
13
19
13
19
13
13
8
8
8
5
5
5

104

Masterpact

Schneider Electric

Derating in switchboard

Factors affecting switchboard design

Basis of tables

The temperature around the circuit breaker and its


connections:
This is used to define the type of circuit breaker to be
used and its connection arrangement.
Vents at the top and bottom of the cubicles:
Vents considerably reduce the temperature inside the
switchboard, but must be designed so as to respect
the degree of protection provided by the enclosure.
For weatherproof heavy-duty cubicles, a forced
ventilation system may be required.
The heat dissipated by the devices installed in the
switchboard:
This is the heat dissipated by the circuit breakers
under normal conditions (service current).
The size of the enclosure:
This determines the volume for cooling calculations.
Switchboard installation mode:
Free-standing, against a wall, etc.
Horizontal partitions:
Partitions can obstruct air circulation within the
enclosure.

c switchboard dimensions
c number of circuit-breakers installed
c type of breaker connections
c drawout versions
c ambient temperature outside of the switchboard: Ta
(IEC 60439-1).

Masterpact NT06-16 H1/L1 (switchboard 2000 x 400 x 400 mm)


Type

NT06 H1/L1

NT08 H1/L1

NT10 H1/L1

NT12 H1

NT16 H1

2b. 40x5

2b. 50x5

3b. 63x5

3b. 63x5

1250

1250

1400

1520

Switchboard composition
4
3
2
1
Connection type

E47710A

Busbar dimensions (mm)


4
Ventilated switchboard
( IP31)
3
Ta = 35C 2
1
4
3
Ta = 45C
2000
2
1
4
3
Ta = 55C 2
1

3b. 80x5
3b. 63x5

630

630

800

800

2b. 63x5
H1/L1
H1/L1
1000/1000 1000/1000

630

630

800

800

1000/950 1000/1000

1250

1250

1330

1440

630

630

800

800

1000/890 1000/960

1200

1250

1250

1340

630

630

800

800

1000/960 1000/1000

1250

1250

1330

1400

630

630

800

800

1000/910 1000/980

1220

1250

1260

1330

630

630

800

800

1000/860 1000/930

1150

1230

1200

1260

3b. 50x5

400 400

4
3
2
Ta = 35C
1
4
3
Ta = 45C 2
1
4
3
Ta = 55C 2
1

E47709A

Non ventilated
switchboard ( IP54)

2000

400 400

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

105

Masterpact

Schneider Electric

Derating in switchboards

Installation
recommendations

Masterpact NT06-08 H1/L1 (switchboard 2300 x 1100 x 500 mm)


Type
Switchboard composition

NT06 H1/L1

NT08 H1/L1

2b. 40x5

2b. 50x5

5
4
3
2
1

Connection type
Busbar dimensions (mm)
Ventilated switchboard ( IP31)
E47712B

Ta = 35C

2300

Ta = 45C

200
300

600

Ta = 55C

500

Non ventilated switchboard ( IP54)

E47711B

Ta = 35C

2300

Ta = 45C

200
300
500

600

Ta = 55C

5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1

630

630

630

630

630

630

630

630

630

630

630

630

630
630

630
630
630

630
630
630
630

630
630

630
630
630

630
630
630
630

630
630

630
630
630

630
630
630
630

630
630

630
630
630

630
630
630
630

630
630

630
630
630

630
630
630
630

630
630

630
630
630

630
630
630
630

630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630

800

800

800

800

800

800

800

800

800

800

800

800

800
800

800
800
800

800
800
800
800

800
800

800
800
800

800
800
800
800

800
800

800
800
800

800
800
800
800

800
800

800
800
800

800
800
800
800

800
800

800
800
800

800
800
800
800

800
800

800
800
800

800
800
800
800

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

106

Masterpact

Schneider Electric

Masterpact NT10-16 H1/L1 (switchboard 2300 x 1100 x 500 mm)


Type
Switchboard composition

NT10 H1/L1

NT12 H1

NT16 H1

3b. 63x5

3b. 63x5

3b. 80x5

5
4
3
2
1

Connection type
Busbar dimensions (mm)
Ventilated switchboard ( IP31)
E47712B

Ta = 35C

2300

Ta = 45C

200
300

600

Ta = 55C

500

Non ventilated switchboard ( IP54)


E47711B

Ta = 35C

2300

Ta = 45C

Ta = 55C
200
300

5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
5
4
3
2
5
4
3
2

H1/L1

2b. 63x5
H1/L1 H1/L1

3b. 63x5

3b. 50x5

H1/L1
1000/1000
1000/1000 1000/1000
1000/1000 1000/1000 1000/1000 1000/1000

1000/1000
1000/1000 1000/1000
1000/960 1000/1000 1000/1000 1000/1000

1000/920
1000/950 1000/930
1000/900 1000/1000 1000/970 1000/950

1000/950
1000/1000 1000/960
1000/1000 1000/1000 1000/1000 1000/970
1000/900
1000/950 1000/910
1000/950 1000/1000 1000/960 1000/930
1000/850
1000/900 1000/860
1000/880 1000/970 1000/910 1000/870

1250

1250

1250

1250

1250

1210

1250

1250
1250

1250
1250
1250

1460

1600

1500
1550

1250

1250
1250

1250
1250
1250

1400

1500

1420
1480

1250

1250
1250

1250
1250
1250

1300

1400

1330
1370

1250

1250
1250

1250
1250
1250

1400

1500

1370
1400

1250

1250
1250

1180
1190
1220

1350

1430

1300
1320

1250

1200
1210

1120
1130
1150

1250

1350

1210
1250

600

500

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

107

Masterpact

Schneider Electric

Derating in switchboards

Installation
recommendations

Masterpact NW08-10 N/H/L (switchboard 2300 x 800x 900 mm)


Type

NW08 N/H/L

NW10 N/H/L

2b. 50x5

3b. 63x5

Switchboard composition
4
3
2
1
Connection type
Busbar dimensions (mm)

2b. 63x5
Ventilated switchboard ( IP31)
E47714A

Ta = 35C

2300

Ta = 45C

Ta = 55C
900

800

Non ventilated switchboard ( IP54)


E47713A

Ta = 35C

2300

Ta = 45C

Ta = 55C
900

800

4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1

800

800

800

800

800

800

800

800
800

800
800
800

800

800
800

800
800
800

800

800
800

800
800
800

800

800
800

800
800
800

800

800
800

800
800
800

800

800
800

800
800
800

800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800

1000

1000

1000

1000

1000

1000

1000

1000
1000

1000
1000
1000

1000

1000
1000

1000
1000
1000

1000

1000
1000

1000
1000
1000

1000

1000
1000

1000
1000
1000

1000

1000
1000

1000
1000
1000

1000

1000
1000

1000
1000
1000

Note
The values indicated in these tables have been extrapolated from test data arnd
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

108

Masterpact

Schneider Electric

Masterpact NW12-16 N/H/L (switchboard 2300 x 800 x 900 mm)


Type

NW12 N1

NW12 H/L

NW16 N1

NW16 H/L

3b. 63x5
3b. 50x5

3b. 63x5
3b. 50x5

3b. 80x5
3b. 63x5

3b. 80x5
3b. 63x5

Switchboard composition
4
3
2
1
Connection type
Busbar dimensions (mm)
Ventilated switchboard ( IP31)
E47714A

Ta = 35C

2300

Ta = 45C

Ta = 55C
900

800

Non ventilated switchboard ( IP54)


E47713A

Ta = 35C

2300

Ta = 45C

Ta = 55C
900

800

4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1

1250

1250

1200

1250

1200

1130

1250

1250
1250

1250
1250
1250

1250

1250
1250

1250
1250
1250

1250

1250
1250

1250
1250
1250

1250

1250
1250

1240
1250
1250

1250

1210
1250

1170
1210
1250

1200

1140
1200

1100
1170
1200

1250

1250
1250 1250

1250
1250
1250

1550

1600

1600
1600

1600

1600

1600
1600

1250

1250
1250 1250

1250
1250
1250

1470

1600

1500
1600

1600

1600

1600
1600

1250

1250
1250 1250

1250
1250
1250

1380

1500

1380
1500

1520

1600

1470
1600

1250

1250
1250 1250

1250
1250
1250

1440

1550

1425
1550

1600

1600

1600
1600

1250

1250
1250 1250

1250
1250
1250

1360

1470

1360
1470

1500

1600

1500
1600

1250

1250
1250 1250

1250
1250
1250

1280

1380

1280
1380

1400

1520

1400
1520

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

109

Masterpact

Schneider Electric

Derating in switchboards

Installation
recommendations

Masterpact NW20-40 N/H/L (switchboard 2300 x 800 x 900 mm)


Type

NW20 H1/H2/H3

NW20 L1

NW25 H1/2/3

NW32 H1/2/3

NW40 H1/2/3

3b. 100x5

3b. 100x5

4b. 100x5

3b. 100x10

4b. 100x10

Switchboard composition
4
3
2
1
Connection type
Busbar dimensions (mm)
Ventilated switchboard ( IP31)
E47714A

Ta = 35C

2300

Ta = 45C

Ta = 55C
900

800

Non ventilated switchboard ( IP54)


E47713A

Ta = 35C

2300

Ta = 45C

Ta = 55C
900

800

4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1

2000

2000

2000
2000

2000

2000

1830
2000

2375

2500

3040

3200

3320

3700

2000

2000

2000
2000

1810

1960

1750
1920

2250

2380

2880

3100

3160

3500

2000

2000

1880
2000

1700

1850

1640
1800

2100

2250

2690

2900

2960

3280

2000

2000

2000
2000

1800

1900

1750
1890

2125

2275

2650

2850

3040

3320

1900

1960

1900
1960

1680

1810

1660
1800

2000

2150

2550

2700

2880

3120

1800

1920

1780
1920

1590

1700

1550
1700

1900

2020

2370

2530

2720

2960

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

110

Masterpact

Schneider Electric

Masterpact NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500 mm)


Type

NW40b H1/H2

NW50 H1/H2

NW63 H1/H2

5b. 100x10

7b. 100x10

8b. 100x10

4000

4000

4700

5000

6050

4000

4000

4450

4850

5670

4000

4000

4200

4600

5350

4000

4000

4350

4650

5290

4000

4000

4100

4400

5040

3840

3840

3850

4150

4730

Switchboard composition
4
3
2
1
Connection type
Busbar dimensions
Ventilated switchboard ( IP31)

E47716B

Ta = 35C

Ta = 45C
2300

Ta = 55C

4
3
2
1
4
3
2
1
4
3
2
1

1500
1400

Non ventilated switchboard ( IP54)

E47715B

Ta = 35C

Ta = 45C
2300

Ta = 55C

4
3
2
1
4
3
2
1
4
3
2
1

1500
1400

Note
The values indicated in these tables have been extrapolated from test data and
theoretical calculations. These tables are only intended as a guide and cannot replace
industrial experience or a temperature rise test.

111

Masterpact

Schneider Electric

Substitution kit
Fixed / drawout devices
800 to 3200 A

Installation
recommendations

It is possible to replace a Masterpact (M08 to M32) with a new Masterpact (NW08


to NW32) with the same power rating.
Substitution is possible for the following types of circuit breakers:
c N1, H1, H2 for both fixed and drawout versions
c L1 for drawout versions up to 2000 A.

Mounting diagram
Fixed version

Drawout version

Y
29,5 X 25

E59219A

E59218B

Y
14

2 11,5 x 22

124
162
150

9,5

14

4 6,5

11,5

10

110

211 X 6

175

11
200 (3P)
315 (4P)

10,5

11

2 11 X 6

200

167,5 (3P)
282,5 (4P)
267,5 (4P)

: Masterpact NW
: Masterpact M

162,5

Fixing points are identical for Masterpact (M08 to M32) and Masterpact (NW08 to NW32),
except for the four-pole craddle.

Door cut-out
c without an escutcheon, the cut-out is identical (270 x 325 mm).
c with the former escutcheon, the cut-out is identical (270 x 325 mm).
c with the new escutcheon, the cut-out is different.
Drawout version

295 mini (3P)


410 mini (4P)

300 mini (3P)


415 mini (4P)

E59221A

E59220A

Fixed version

295 mini

300 mini

270 (1)
379 (2)

270 (1)
316 (2)
135 (1)
158 (2)

325 (1)
364 (2)

X 135 (1)

222 (2) 153,3 (1)

162,5 (1)
182 (2)

325 (1)
364 (2)

162,5 (1)
182 (2)

47 (1)

Power connections
Select a set of retrofit connectors to replace the standard connectors and avoid any
modifications to the busbars (see the retrofit section in "orders and quotations")

Note:
(1) Without escutcheon
(2) With escutcheon
References X and Y represent the symmetry planes for
three-pole devices

112

Masterpact

Schneider Electric

E59217A

NW08 to NW32

M08 to M32

Electrical diagrams
Correspondences between Masterpact NW and Masterpact M terminal blocks

AT

BPF

B4

262

B2

B3

C2
C2

254

C12
C12

252

D4
D2

A4

84
84

C3

82
82

K2

Q3

184

BPO

182

Z5

Q2

Z21

Z21

Z4

Q1

Z22
Z3

484

Z11
Z2

474

Z12
Z1

V3

V2

V1

equivalent functions
using M2C or M6C

VN

charged

ALR, V, MR6, R
options

L3

254

L2

252

L1

A3

A2

power

ready to
close

Remote operation

fault

Control unit

fault

E59222A

Power

MCH

Q
I

SDE1

SDE2

S1 S2

Micrologic
U

MN

MX1

MX2

XF
PF

CH

Res

A1

251

B1

251

B1

C11
C11

A1

D1
D1

C1

81

K1

181

F2+
F2+

471

F1

T4

F1

X2

X1

T3

T2

T1
SG2

SG1

M3

M2

M1

or

(1)

or

or

C1

M6C

81

M2C

24 V DC

Craddle contacts

372

374

914

912

922

924

932

312
934

314

314

322
324

312

324

332
334

Test

322

334

354

332

352

814

364
824

connected

812

362
822

disconnected

832

..4
..4

..6

..2
..2

12

14

12

connected
and closed

834

not connected
or connected
and open

closed

14

22

24

22

24

32

34

32

closed

34

42

44

42

44

open

..8

E59223A

Indication contacts

EF . .
OF4

OF3

OF2

OF1

OF . .

OF

CT3
CD3

CD2

CD1

CE3

CE2

CT2

CT1

CE1

or

911

311
311

371

321
321

921

331
331

931

811
351

..1
..1

821

11
11

New or additional functions

361

21
21

Identical to Masterpact M

831

31
31

..5

41
41

CE

Different than Masterpact M

(1) The current transformer for the external neutral must be replaced

113

Masterpact

Schneider Electric

114

Masterpact

Schneider Electric

Additional characteristics

Masterpact

Presentation
Functions and characteristics
Dimensions and connection
Electrical diagrams
Installation recommendations

Tripping curves
Limitation curves
References

115

Masterpact

1
9
53
81
91

116
118
121

Schneider Electric

Tripping curves

Additional
characteristics

E46350

Micrologic 2.0
10 000
5 000

Ir = 0,41 x In

2 000
1 000
500
200
100

tr = 0,5...24 s

50
20
10
5
t(s)
2

Isd = 1,510 x Ir

1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Micrologic 5.0, 6.0, 7.0


E46276

10 000
5 000

Ir = 0,41 x In

2 000
1 000
500
200
100

tr = 0,524 s

50
20
10
5
t(s)

Isd = 1,510 x Ir

2
1

I2t ON

.5
.2

0,4

0,3

0,3

0,2

0,2

0,1

.1
.05
.02
.01

0,4

I2t OFF

0,1
0

Ii = 215 x In . OFF

.005
.002
.001
.5 .7 1

3 4 5 7 10
x Ir

116

Masterpact

20

7 10

20 30

x In

Schneider Electric

Earth-fault protection (Micrologic 6.0)


E46266

10 000
5 000
2 000

Ig = AJ x In (1)
1200 A max.

1 000
500
200
100
50
20
10
5
t(s)

I2t ON

2
1
.5
.2
I2 t

.1
.05

0.4

0.4

0.3
0.2
0.1

0.3
0.2
0.1

OFF

.02
.01
.005
.002
.001
.05.07 .1

.2 .3 .4 .5 .7 1

7 10

200 300

I / In

(1)

Ig = In x
Ig < 400 A
400 A i Ig i 1200 A
Ig > 1200 A

0,3
0,2
500

0,3
0,3
640

0,4
0,4
720

0,5
0,5
800

0,6
0,6
880

0,7
0,7
960

0,8 0,9 1
0,8 0,9 1
1040 1120 1200

E47587

IDMTL curve (Micrologic P and H)


100 000

HVF

10 000
5 000
2 000
1 000
EIT

500
t(s)

200
100

VIT

50
SIT

20
10

DT

5
2
1
.5

.5 .7

4 5

10

20

I / Ir

117

Masterpact

Schneider Electric

Limitation curves
Current limiting

Additional
characteristics

Voltage 380/415 V AC
E47519

300

Masterpact
NW H3

200
Masterpact
NW L1

100
80
70
60
50

Masterpact
NT L1

40
30
20
10

20

30

40

60

100

200

kA rms

E47520

Voltage 660/690 V AC
300

Masterpact
NW H3

200

Masterpact
NW L1
k

100
80
70
60
50

Masterpact
NT L1

40
30
20
10

20

30

40

60

100

200

kA rms

118

Masterpact

Schneider Electric

Energy limiting

Voltage 380/415 V AC
E47521

10

5
3

Masterpact
NW H3

2
10

Masterpact
NW L1

5
2

As

3
2
10

Masterpact
NT L1
5
3
2
10

10

20

30

40

60

100

150 200

300

kA rms

Voltage 660/690 V AC
9

E47522

10

5
Masterpact
NW H3

3
2
8

10

Masterpact
NW L1
5
2

As

3
2
7

10

Masterpact
NT L1

5
3
2
6

10

10

20

30

40

60

100

150 200

300

kA rms

119

Masterpact

Schneider Electric

120

Masterpact

Schneider Electric

Masterpact

References

Presentation
Functions and characteristics
Dimensions and connection
Electrical diagrams
Installation recommendations
Additional characteristics

1
9
53
81
91
121

Accessories for communication Bus


Order form
NT06 to NT16 fixed circuit breakers

122
123

Circuit breaker selection


Indication contacts
Remote operation

124
126
127

NT06 to NT16 drawout circuit breakers

128

Circuit breaker selection


Chassis locking and accessories
Indication contacts
Remote operation

128
130
131
132

Accessories for NT06 to NT16 fixed


and drawout circuit breakers
NT06 to NT16 fixed switch-disconnectors

133

Circuit breaker selection

136

NT06 to NT16 drawout switch-disconnectors


Circuit breaker selection

138

NW08 to NW63 fixed circuit breakers


Circuit breaker selection
Indication contacts
Remote operation

140
142
143

NW08 to NW63 drawout circuit breakers


Circuit breaker selection
Chassis locking and accessories
Indication contacts
Remote operation

144
146
148
149

Accessories for NW08 to NW63 fixed


and drawout circuit breakers
NW08 to NW63 fixed switch-disconnectors

150

Circuit breaker selection

152

NW08 to NW63 drawout switch-disconnectors

121

Circuit breaker selection

154

Retrofit solutions

156

Connection for fixed devices


Connection for drawout devices

156
157

Masterpact

Schneider Electric

Orders and quotations

Accessories for
communication Bus

Digipact display module


DMB300 display module
E67954

50894

DMC300 display module


E67955

50895

Spare parts
Memory card DMC300PCM

50959

Digipact Bus pre-wired system


Data concentrator DC150
110-240 V AC, 50/60 Hz and 115-125 V DC

50823

E79014

Auxiliary supply voltage

Junction block
50778

E67956

Junction block for internal Bus

Cables
E67957

Cable for internal bus

20-meter roll (0.75 mm2)


100-meter roll (0.75 mm2)

50779
50780

Modbus pre-wired system


Connection block
50963

CSD309 RS485 9 pins SubD connector

50964

CDM303 display module cable (L: 3 m)

50960

CCP303 RS485 Modbus cable + power (L: 3 m) (Micrologic)


CCS303 RS485 Modbus cable (L: 3 m) (Modbus slave)

50961
50962

CCR301 power + RS485 roll cable (L: 60 m) (Bus Modbus)

50965

E67959

E67958

CJB306 6 connections RS485 block + power

E67961

E79015

E67960

Cables

Converter
RS485/RS232 (ACE909) 12 V DC power supply included
RS485/RS232
RS485/Ethernet
RS485/Ethernet (SMS compatible)
(1) see catalogue Telemecanique.
(2) see catalogue Square D.

122

Masterpact

50786
TSX SCA72
174 CEV 300-10
3050 EGW2

(1)
(1)
(2)

Schneider Electric

Order form
Masterpact NT and NW

Locking

To indicate your choices, check the applicable square


boxes
and enter the appropriate information
in the rectangles

Basic device

VBP - ON/OFF pushbutton locking


OFF position locking
VCPO - by padlocks
VSPO - by keylocks
Locking kit
without
keylocks
1 lock

Quantity

Masterpact type
NT, NW
Frame size
06 to 63
Sensor rating
A
Circuit breaker
N1, H1, H2, H3, L1
Switch-disconnector
NA, HA, HF
Number of poles
3 or 4
Option : Neutral on right side
Type of device
Fixed
Drawout with chassis
Chassis alone
Drawout without chassis

VSPD - chassis locking in


''disconnected'' position

VPEC - door interlock

Micrologic control unit


A - ammeter
2.0 A
P - power meter

5.0 A

6.0 A

7.0 A

5.0 P

6.0 P

7.0 P

5.0 H
6.0 H
7.0 H
TCE - external sensor (CT) for neutral + earth-fault
protection

2 locks (different key profiles) for NW


Locking kit
Profalux
Ronis
without
keylocks
1 lock
1 lo ck + 1 lock with
same key profile
2 locks (different key profiles)
Optional connected - disconnected - test position locking
Latch on right-hand side of chassis
Latch on left-hand side of chassis

Indication contacts

TCW - external sensor for SGR protection


Rectangular sensor
280 x 115
for earth-leakage
470 x 160
protection

Additional
1 block of 4 OF for NW
EF - combined ''connected/closed'' contacts
1 EF 5 A - 240 V AC for NW
1 EF low-level for NW
SDE - ''fault-trip'' indication contacts
1 SDE 5 A - 240 V AC
Standard
Additional
1 SDE 5 A - 240 V AC
1 SDE low-level
Programmable contacts
2 M2C contacts
6 M6C contacts
Carriage switches
low-level
6 A - 240 V AC
CE - ''connected'' position
Maxi. 3 for NT and NW
Maxi. 2 for NT and 3 for NW
CD - ''disconnected'' position
Maxi. 1 for NT and 3 for NW
CT - ''test'' position
AC - actuator for additional carriage switches

LT - long-time rating plug (standard setting 0.4 to 1 x Ir)


Low setting option 0.4 to 0.8 Ir
High setting option 0.8 to 1 Ir
LT OFF option
PTE - external voltage measurement input
AD - external power-supply module
BAT - battery module

Communication
Digipact
Modbus
Modbus

Connection
Horizontal
Top
Vertical
Top
Front
Top
Bare-cable connectors
4 x 240 mm2 + connector shield
Vertical-connection adapters
Cable-lug adapters
Interphase barriers
Spreaders
Disconnectable front-connection
adapter

1 lock + 1 lock with


same key profile

OF - ON/OFF indication contacts


Standard
4 OF 6 A - 240 V AC (10 A - 240 V AC and low-level for NW)
Max. 4
qty
Alternate
1 OF low-level for NT
(replaces a standard contact)

TCE - external sensor (CT) for double neutral protection


(Micrologic P and H with 3-poles)

Eco COM

Ronis

VPOC - racking interlock


IPA - cable-type door interlock
IBPO - racking interlock between crank and OFF pushbutton for NW
DAE - automatic spring discharge before breaker removal for NW
VDC - mismatch protection

H - harmonic meter

COM

Profalux

Max. 2

qty

Max. 8
Max. 8

qty
qty

qty
qty
qty
qty

Remote operation

Bottom
Bottom
Bottom

Remote ON/OFF

NT-FC fixed
NT-FC, fixed, draw.
NT-FC, fixed, draw.
NT, NW-fixed, draw.
NT-fixed, drawout
NW-fixed

Remote tripping

VO - safety shutters on chassis


NT, NW
VIVC - shutter position indication NW
and locking

MCH - gear motor


XF - closing voltage release
MX - opening voltage release
PF - ''ready to close'' contact

V
V
V

low-level
6 A - 240 V AC
BPFE - electrical closing pushbutton
Res - electrical reset option
RAR - automatic reset option
MN - undervoltage release
V
R - delay unit (non-adjustable)
Rr - adjustable delay unit
2nd MX - shunt release
V

Accessories

Key for Micrologic control units:


2.0 : basic protection (long-time + inst.)
5.0 : selective protection (long-time + short-time + inst.)
6.0 : selective + earth-fault protection
(long-time + short-time + inst. + earth-fault)
7.0 : selective + earth-leakage protection
(long-time + short-time + inst. + earth-leakage)

CDM - mechanical operation counter


CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover
OP - blanking plate
Brackets for mounting on backplates

123

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
fixed circuit breakers
Circuit breaker selection

A Masterpact fixed circuit breaker is


described by 4 catalogue numbers
corresponding to:
b the basic circuit breaker
b a control unit
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories many also be
added.

Basic circuit breaker


Type H1

NT06
NT08
NT10
NT12
NT16

In (A at 40C)
630
800
1000
1250
1600

3P
4P
Icu (kA for U = 220/415 V) - Ics = 100% Icu
42
47110
47115
42
47120
47125
42
47130
47135
42
47140
47145
42
47150
47155

In (A at 40C)
630
800
1000

3P
4P
Icu (kA for U = 220/415 V) - Ics = 100% Icu
150
47112
47117
150
47122
47127
150
47132
47137

Type L1

E46423

NT06
NT08
NT10

Option
Neutral on the right

(*)

Micrologic control unit


"ammeter" A
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A

basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47282
47285
47286
47287

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47289
47290
47291

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47293
47294
47295

"power meter" P
Micrologic 5.0 P
Micrologic 6.0 P
Micrologic 7.0 P

"harmonic meter" H
Micrologic 5.0 H
Micrologic 6.0 H
Micrologic 7.0 H

Communication option
Modbus COM
Modbus COM eco
Digipact COM
(*) consult us

47405
47406
47409

Auxiliaries and accessories:


b for fixed devices: see page 126
b for fixed or drawout devices: see page 133
Switch-disconnector version: see page 136
Source changeover assembly: see page 133

124

Masterpact

Schneider Electric

Front connection
4P

47328
47329

47330
47331

Bare-cable connectors + 1 connector shield for 4 x 240 mm2 cables


3P (3 parts)
4P (4 parts)

47333
47334

Vertical connection adapters 630/1600 A


3P (3 parts)
4P (4 parts)

33642
33643

Cable lug adapters 630/1600 A


3P (3 parts)
4P (4 parts)

33644
33645

E47757

3P
Top
Bottom

630/1600 A

E46427

E46426

E46887

Front connection accessories

Interphase barriers
33648

E79060

3P/4P (3 parts)

E74437

Arc chute screen


3P
4P

47335
47336

Rear connection

E46429

Vertical connection
3P

4P

630/1600 A

Top
Bottom

33604
33605

33614
33615

3P

4P

630/1600 A

Top
Bottom

33606
33607

33616
33617

E46430

Horizontal connection

E79060

Rear connection accessories


Interphase barriers
3P/4P (3 parts

33648

Common accessories for front and rear connections


Spreaders
E46431

630/1600 A

3P
4P
For front and horizontal rear connection

33622
33623

240 mm2

33013
33014
33015
33016

E47820

Cable lug kits

300 mm2

3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)

125

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
fixed circuit breakers (cont.)
Indication contacts

E46463

ON/OFF indication contacts (OF)


Changeover contacts (6 A - 240 V)
1 low-level OF to replace 1 standard OF (4 max.)

4 (standard)
47339

E47758

"Fault trip" indication contacts (SDE)


Changeover contact (5 A - 240 V)
1 additional SDE (5 A - 240 V)
1 additional low-level SDE

1 (standard)
47340
47341

E46434

Programmable contacts (*) (programmed via Micrologic control unit)


2 contacts (M2C) (5 A - 240 V)
6 changeover contacts (M6C) (5 A - 240 V)
(*) for Micrologic control units P and H only.

47403
47404

E46435

M2C

M6C

126

Masterpact

Schneider Electric

Remote operation

Remote ON/OFF

E46436

Gear motor
AC 50/60 Hz

DC

48 V
100-130 V
200-240 V
277-415 V
440-480 V
24-30 V
48-60 V
100-130 V
200-250 V

MCH
47391
47395
47396
47398
47400
47390
47391
47392
47393

E46437

Instantaneous voltage releases


Standard
AC 50/60 Hz
DC

Communicating
AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC
12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

Closing release
XF
47349
47350
47351
47352
47353
47354
47355
XF com
47310
47311
47312
47313
47314
47315
47316

Opening release
MX
47359
47360
47361
47362
47363
47364
47365
MX com
47320
47321
47322
47323
47324
47325
47326

E46438

"Ready to close" contact (1 max.)


PF
47342
47343

1 changeover contact (5 A - 240 V)


1 low-level changeover contact

E46439

Electrical closing pushbutton


BPFE
47512

1 pushbutton

E46660

Remote reset after fault trip


Electrical reset
110-130 V AC
220-240 V AC
Automatic reset
Adaptation

Res
47344
47345
RAR
47346

(*)

Remote tripping

E46437

Instantaneous voltage release


AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

2nd MX
47369
47370
47371
47372
47373
47374
47375

or

MN
47380
47381
47382
47383
47385

MN delay unit
E46694

R (non-adjustable)
AC 50/60 Hz
DC

48-60 V
100-130 V
200-250 V
380-480 V

33684
33685

Rr (adjustable)
33680
33681
33682
33683

(*) no charge.

127

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
drawout circuit breakers
Circuit breaker selection

A Masterpact drawout circuit breaker is


described by 5 catalogue numbers
corresponding to:
b the basic circuit breaker
b a control unit
b a chassis
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories many also be
added.

Basic circuit breaker


Type H1
3P
4P
In (A at 40C) Icu (kA for U = 220/415 V) - Ics = 100% Icu
630
42
47200
47205
800
42
47210
47215
1000
42
47220
47225
1250
42
47230
47235
1600
42
47240
47245

NT06
NT08
NT10
NT12
NT16

Type L1
3P
4P
In (A at 40C) Icu (kA for U = 220/415 V) - Ics = 100% Icu
630
150
47202
47207
800
150
47212
47217
1000
150
47222
47227

E46441

NT06
NT08
NT10

Option
Neutral on the right

(*)

Micrologic control unit


"ammeter" A
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A

basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
33525
33532
33533
33534

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47297
47298
47299

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47301
47302
47303

3P
33722
33723

4P
33725
33726

3P
33723

4P
33726

"power meter" P
Micrologic 5.0 P
Micrologic 6.0 P
Micrologic 7.0 P

"harmonic meter" H
Micrologic 5.0 H
Micrologic 6.0 H
Micrologic 7.0 H

Chassis
For type H1
630/1250 A
1600 A

For type L1
630/1000 A

Communication option
Modbus COM
Modbus eco COM
Digipact COM
(*) consult us

Chassis
33852
33855

Circuit breaker
47485
33843
47489

Auxiliaries and accessories:


b for drawout devices: see page 130
b for fixed or drawout devices: see page 133
Switch-disconnector version: see page 136
Source changeover assembly: see page 133

128

Masterpact

Schneider Electric

E46440

Chassis front connection


630/1600 A

Top
Bottom

3P

4P

33727
33728

33733
33734

Front connection accessories


33642
33643

Cable lug adapters 630/1600 A


3P (3 parts)
4P (4 parts)

33644
33645

E46427

E46426

Vertical connection adapters 630/1600 A


3P (3 parts)
4P (4 parts)

Chassis rear connection

E46429

Vertical connection
630/1600 A

Top
Bottom

630/1600 A

Top
Bottom

3P

4P

33729
33730

33735
33736

3P

4P

33731
33732

33737
33738

E46430

Horizontal connection

E46428

Rear connection accessories


Interphase barriers
3P/4P (3 parts)

33768

Common accessories for front and rear connection


Spreaders
E46431

630/1600 A

3P
4P
For front and horizontal rear connection.

33622
33623

240 mm2

33013
33014
33015
33016

E47820

Cable lug kits

300 mm2

3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)

129

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
drawout circuit breakers (cont.)
Chassis locking and accessories

Chassis locking
"Disconnected" position locking
E46685

By padlocks
Standard
By keylocks
Profalux

1 lock
1 lock + 1 lock with same key profile
2 locks (different key profiles)
Ronis
1 lock
1 lock + 1 lock with same key profile
2 locks (different key profiles)
Optional disconnected/test/connected position locking
Locking kit without locks for
Profalux
Ronis
Castell
Kirk

33773
33774
33775
33776
33777
33778
33779

Right-hand side of chassis (VPECD)


Left-hand side of chassis (VPECG)

33786
33787

Racking interlock (VPOC)

33788

(*)

33769
33770
33771
33772

E46464

Door interlock (1 part)

E46465

Racking interlock

Breaker mismatch protection


33767

E47765

Breaker mismatch protection (VDC)

Chassis accessories
Arc chute cover
Standard

Terminal shield

3P
4P

33763
33764

Safety shutters (VO)

3P
4P

33765
33766

E46700

3P/4P

E46698

Auxiliary terminal shield (CB)

E46699

Safety shutters

(*) no charge.

130

Masterpact

Schneider Electric

Indication contacts

E46467

ON/OFF indication contacts (OF)


Changeover contacts (6 A - 240 V)

4 (standard)

1 low-level OF to replace 1 standard OF (4 max.)

33806

E47759

"Fault trip" indication contacts (SDE)


Changeover contact (5 A - 240 V)

1 (standard)

1 additional SDE (5 A - 240 V)

47430

1 additional low-level SDE

47431

E46686

Programmable contacts (*) (programmed via Micrologic control unit)


2 contacts M2C (5 A - 240 V)

47483

6 changeover contacts M6C (5 A - 240 V)


(*) for Micrologic control units P and H only.

47484

E46687

M2C

M6C

E46661

Carriage switches (connected / disconnected / test position)


Changeover contacts (6A - 240 V)
1 connected position contact (3 max.)
1 test position contact (1 max.)
1 disconnected position contact (2 max.)
And/or low-level changeover contacts
1 connected position contact (3 max.)
1 test position contact (1 max.)
1 disconnected position contact (2 max.)

33751
33752
33753
33754
33755
33756

Auxiliary terminals for chassis alone


3 wire terminal (30 parts)
6 wire terminal (10 parts)
Jumpers (10 parts)

47071
47072
47900

131

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
drawout circuit breakers (cont.)
Remote operation

Remote ON/OFF

E46662

Gear motor
AC 50/60 Hz

DC

48 V
100-130 V
200-240 V
277-415 V
440-480 V
24-30 V
48-60 V
100-130 V
200-250 V

MCH
47461
47465
47466
47468
47470
47460
47461
47462
47463

Instantaneous voltage release


Standard
AC 50/60 Hz
DC

Communicating
AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC
12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

Closing release
XF
47439
47440
47441
47442
47443
47444
47445
XF com
47411
47412
47413
47414
47415
47416
47417

Opening release
MX
33809
33810
33811
33812
33813
33814
33815
MX com
33791
33792
33793
33794
33795
33796
33797

E46664

"Ready to close" contact (1 max.)


PF
47432
47433

1 changeover contact (5 A - 240 V)


1 low-level changeover contact

E46439

Electrical closing pushbutton


BPFE
47512

1 pushbutton

E46660

Remote reset after fault trip


Electrical reset
110-130 V AC
220-240 V AC
Automatic reset
Adaptation

Res
47434
47435
RAR
47346

(*)

Remote tripping

E46663

Instantaneous voltage release


AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

2nd MX
47449
47450
47451
47452
47453
47454
47455

or

MN
33819
33820
33821
33822
33824

MN delay unit
E46694

R (non-adjustable)
AC 50/60 Hz
DC

48-60 V
100-130 V
200-250 V
380-480 V

33684
33685

Rr (adjustable)
33680
33681
33682
33683

(*) no charge.

132

Masterpact

Schneider Electric

Accessories for NT06 to NT16


fixed and drawout circuit breakers

Circuit breaker locking


Pushbutton locking device
33897

E46666

By padlocks

OFF position locking


By padlocks + BPFE support
E46666

47514
By keylocks + BPFE support
Profalux
1 lock
1 lock + 1 lock with same key profile
Ronis
1 lock
1 lock + 1 lock with same key profile
Locking kit without locks for
Profalux
Ronis
Kirk
Castell

47519
47520
47521
47522
47515
47516
47517
47518

Other circuit breaker accessories


Mechanical operation counter
33895

E46667

operation counter CDM

E46670

E46669

E46668

Escutcheon and accessories


Escutcheon
Transparent cover (IP 54)
Escutcheon blanking plate

Fixed
33718

Drawout
33857
33859
33858

EscutcheonCoverBlanking plate

Mechanical interlocking for source changeover

E47760

Interlocking using connecting rods


Complete assembly with 2 adaptation fixtures + rods
2 Masterpact NT fixed devices
2 Masterpact NT drawout devices

33912
33913

Interlocking using cables (*)


Choose 2 adaptation fixtures (1 for each breaker) + 1 set of cables
1 adaptation fixture for Masterpact NT fixed devices
1 adaptation fixture for Masterpact NT drawout devices
1 set of 2 cables
(*) Can be used with any combination of NT or NW, fixed or drawout devices.

33200
33201
33209

E70742

Cable-type door interlock


1 complete assembly for Masterpact NT fixed devices
1 complete assembly for Masterpact NT drawout devices

133

Masterpact

33920
33921

Schneider Electric

Orders and quotations

Accessories for NT06 to NT16


fixed or drawout circuit breakers
(cont.)

Accessories for Micrologic control units


External sensors
33576

E46671

External sensor for earth-leakage protection (TCE)


Sensor rating 400/1600 A (for Micrologic P and H with 3P devices)

Rectangular sensor for earth-leakage protection


280 mm x 115 mm
E46672

33577

Source ground return (SGR) earth fault protection


External sensor (SGR)

33579

E46671

MDGF summing module

48891

Voltage measurement input (for breakers supplied via bottom terminals)


Voltage measurement input
Fixed
E46674

Drawout

47506
47507

E46674

Long-time rating plug (limits setting range for higher accuracy)


Standard

0.4 to 1 x Ir

33542

Low-setting option

0.4 to 0.8 x Ir

33543

High-setting option

0.8 to 1 x Ir

33544

Without long-time protection

off

33545

Zone Selective Interlocking option for Micrologic P and H


ZSI

Standard

E47787

External power supply module

L4
L3

t
Inpu
24VDC
Output
24VDC G2

0A
AD 22
G1

24-30 V DC
48-60 V DC
125 V DC
110 V AC
220 V AC
380 V AC

54440
54441
54442
54443
54444
54445

1 24 V battery

54446

Battery module

Test equipment
Mini test kit
E59921

33594

Portable test kit


E59554

33595

Special settings
For circuit breaker derating
Catalogue number to be added to those describing the circuit breaker rating
Rating
NT08
NT10
NT12
NT16
400
47053
47053
630
33091
33091
33091
800
33092
33092
33092
1000
33093
33093
1250
33094
Note: for ratings In = 100 or 250 A, please contact us.

134

Masterpact

Schneider Electric

135

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
fixed switch-disconnectors
Switch-disconnector selection

A Masterpact fixed switch-disconnector is


described by 3 catalogue numbers
corresponding to:
b the basic switch-disconnector
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories many also be
added.

Basic switch-disconnector
Type HA

NT06
NT08
NT10
NT12
NT16

In (A at 40C)
630
800
1000
1250
1600

3P
Icm (kA peak for U = 220/690 V)
60
47159
60
47161
60
47163
60
47165
60
47167

4P
47160
47162
47164
47166
47168

Communication option
47405
47409

E46675

Modbus COM
Digipact COM

Auxiliaries and accessories:


b for fixed devices: see page 126
b for fixed or drawout devices: see page 133
Source changeover assembly: see page 133

136

Masterpact

Schneider Electric

Front connection
4P

47328
47329

47330
47331

Bare-cable connectors + 1 connector shield for 4 x 240 mm2 cables


3P (3 parts)
4P (4 parts)

47333
47334

Vertical connection adapters 630/1600 A


3P (3 parts)
4P (4 parts)

33642
33643

Cable lug adapters 630/1600 A


3P (3 parts)
4P (4 parts)

33644
33645

E47757

3P
Top
Bottom

630/1600 A

E46427

E46426

E46887

Front connection accessories

Interphase barriers
33648

E79060

3P/4P (3 parts)

Rear connection

E46429

Vertical connection
3P

4P

630/1600 A

Top
Bottom

33604
33605

33614
33615

3P

4P

630/1600 A

Top
Bottom

33606
33607

33616
33617

E46430

Horizontal connection

E79060

Rear connection accessories


Interphase barriers
3P/4P (3 parts)

33648

Common accessories for front and rear connection


Spreaders
E46431

630/1600 A

3P
4P
For front and horizontal rear connection

33622
33623

240 mm2

33013
33014
33015
33016

E47820

Cable lug kits

300 mm2

3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)

137

Masterpact

Schneider Electric

Orders and quotations

NT06 to NT16
drawout switch-disconnectors
Switch-disconnector selection

A Masterpact drawout switch-disconnector


is described by 4 catalogue numbers
corresponding to:
b the basic switch-disconnector
b a chassis
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories many also be
added.

Basic switch-disconnector
Type HA
In (A at 40C)
630
800
1000
1250
1600

NT06
NT08
NT10
NT12
NT16

3P
Icm (kA peak for U = 220/690 V)
60
47248
60
47250
60
47252
60
47254
60
47256

4P
47249
47251
47253
47255
47257

Chassis
630/1250 A
1600 A

3P
33722
33723

4P
33725
33726

E00000

Communication option
COM Modbus
COM Digipact

Chassis
33852
33855

Switch-disconnector
47485
47489

Auxiliaries and accessories:


b for drawout devices: see page 130
b for fixed or drawout devices: see page 133
Source changeover assembly: see page 133

138

Masterpact

Schneider Electric

E46440

Chassis front connection


630/1600 A

Top
Bottom

3P

4P

33727
33728

33733
33734

Front connection accessories


33642
33643

Cable lug adapters 630/1600 A


3P (3 parts)
4P (4 parts)

33644
33645

E46427

E46426

Vertical connection adapters 630/1600 A


3P (3 parts)
4P (4 parts)

Chassis rear connection

E46429

Vertical connection
630/1600 A

Top
Bottom

630/1600 A

Top
Bottom

3P

4P

33729
33730

33735
33736

3P

4P

33731
33732

33737
33738

E46430

Horizontal connection

Rear connection accessories


E46428

Interphase barriers
3P/4P (3 parts)

33768

Common accessories for front and rear connection


Spreaders
E46431

630/1600 A

3P
4P
For front and horizontal rear connection

33622
33623

240 mm2

33013
33014
33015
33016

E47820

Cable lug kits

300 mm2

3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)

139

Masterpact

Schneider Electric

Masterpact: price list

NW08 to NW63
fixed circuit breakers
Circuit breaker selection

Unit price (excl.VAT) in French francs

A Masterpact fixed circuit breaker is


described by 4 catalogue numbers
corresponding to:
b the basic circuit breaker
b a control unit
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories may also be
added.

Basic circuit breaker


Type N1

NW08
NW10
NW12
NW16

Type H1

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW63

E46442

3P
4P
In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu
800
42
48000
48007
1000
42
48014
48021
1250
42
48028
48035
1600
42
48042
48049
3P
4P
In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu
800
65
48001
48008
1000
65
48015
48022
1250
65
48029
48036
1600
65
48043
48050
2000
65
48057
48064
2500
65
48070
48076
3200
65
48082
48087
4000
65
48092
48097
4000
100
48106
48109
5000
100
48112
48115
6300
100
48118
48121

Type H2
Basic circuit breaker y 4000 A
E46443

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW63

Basic circuit breaker u 4000 A

3P
4P
In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu
800
100
48002
48009
1000
100
48016
48023
1250
100
48030
48037
1600
100
48044
48051
2000
100
48058
48065
2500
100
48071
48077
3200
100
48083
48088
4000
100
48093
48098
4000
150
48107
48110
5000
150
48113
48116
6300
150
48119
48122

Option
Neutral on the right

(*)

Micrologic control unit


"ammeter" A
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A

basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47282
47285
47286
47287

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47289
47290
47291

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
47293
47294
47295

"power meter" P
Micrologic 5.0 P
Micrologic 6.0 P
Micrologic 7.0 P

"harmonic meter" H
Micrologic 5.0 H
Micrologic 6.0 H
Micrologic 7.0 H

Communication option
Modbus COM
Modbus COM eco
Digipact COM
(*) consult us.

48188
47406
48192

Auxiliaries and accessories:


b for fixed devices: see page 22
b for fixed or drawout devices: see page 30
Switch-disconnector version: see page 32
Source changeover assembly: see page 30
BTP207E-50200-NW.fm/20

Schneider Electric

Masterpact: price list

NW08 to NW63
fixed circuit breakers (cont.)
Circuit breaker selection (cont.)

Unit price (excl.VAT) in French francs

E46444

Front connection
800/1600 A
2000 A
2500/3200 A

Top
Bottom
Top
Bottom
Top
Bottom

3P
48128
48130
48124
48125
48129
48131

4P
48153
48155
48126
48127
48154
48156

3P
48421
48422

4P
48424
48425

3P
48133
48138
48134
48139

4P
48158
48163
48159
48164

Front connection accessories


E46889

Disconnectable front connection


1600 A
2000/3200 A

Rear connection

E46445

Vertical connection
800/2000 A
2500/3200 A
4000 A
4000b/5000 A
6300 A

Top
Bottom
Top
Bottom
Top

48135

48160

Bottom

48140

48165

Top

48136

48161

Bottom

48141

48166

Top

48137

48162

Bottom

48142

48167

Top
Bottom
Top
Bottom
Top
Bottom
Top
Bottom

3P
48143
48148
48144
48149
48145
48150
48146
48151

4P
48168
48173
48169
48174
48170
48175
48171
48176

E46446

Horizontal connection
800/2000 A
2500/3200 A
4000 A
4000b/5000 A

Rear connection accessories


Interphase barriers
48599

E46428

3P/4P (3 parts)

47829

E47788

Brackets for mounting on a backplate


2 parts

Schneider Electric

BTP207E-50200-NW.fm/21

Masterpact: price list

NW08 to NW63
fixed circuit breakers (cont.)
Indication contacts

Unit price (excl.VAT) in French francs

E46432

ON/OFF indication contacts (OF)


Block of 4 changeover contacts (6 A - 240 V)
1 additional block of 4 contacts (2 max.)

1 block (standard)
48198

E46665

"Fault trip" indication contacts (SDE)


Changeover contact (5 A - 240 V)
1 additional SDE (5 A - 240 V)
1 additional low-level SDE

1 (standard)
48200
48201

E46434

Programmable contacts (*) (programmed via Micrologic control unit)


2 contacts M2C (5 A - 240 V)
6 changeover contacts M6C (5 A - 240 V)
(*) for Micrologic control units P and H only.

47403
47404

E46435

M2C

M6C

BTP207E-50200-NW.fm/22

Schneider Electric

Masterpact: price list

NW08 to NW63
fixed circuit breakers (cont.)
Remote operation

Unit price (excl.VAT) in French francs

Remote ON/OFF

E46447

Gear motor
AC 50/60 Hz

DC

48 V
100-130 V
200-240 V
250-277 V
380-415 V
440-480 V
24-30 V
48-60 V
100-130 V
200-250 V

MCH
48207
48211
48212
48213
48214
48215
48206
48207
48208
48209

E46437

Instantaneous voltage releases


Standard
AC 50/60 Hz
DC

Communicating
AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48/60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC
12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

Closing release
XF
47349
47350
47351
47352
47353
47354
47355
XF com
47310
47311
47312
47313
47314
47315
47316

Opening release
MX
47359
47360
47361
47362
47363
47364
47365
MX com
47320
47321
47322
47323
47324
47325
47326

E46438

"Ready to close" contact (1 max.)


1 changeover contact (5 A - 240 V)
1 low-level changeover contact

PF
47342
47343

E46677

Electrical closing pushbutton


BPFE
48534

1 pushbutton

E46665

Remote reset after fault trip


Electrical reset
110-130 V AC
220-240 V AC
Automatic reset
Adaptation

Res
48202
48203
RAR
47346

(*)

Remote tripping

E46437

Instantaneous voltage release


AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

2nd MX
47369
47370
47371
47372
47373
47374
47375

or

MN
47380
47381
47382
47383
47385

MN delay unit
E46694

R (non-adjustable)
AC 50/60 Hz
DC

48-60 V
100-130 V
200-250 V
380-480 V

33684
33685

Rr (adjustable)
33680
33681
33682
33683

(*) no charge.

Schneider Electric

BTP207E-50200-NW.fm/23

Masterpact: price list

NW08 to NW63
drawout circuit breakers
Circuit breaker selection

Unit price (excl.VAT) in French francs

E46448

A Masterpact drawout circuit breaker is


described by 5 catalogue numbers
corresponding to:
b the basic circuit breaker
b a control unit
b a chassis
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories may also be
added.

Basic circuit breaker


3P

4P

Type N1
NW08
NW10
NW12
NW16

In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu


800
42
48230
48237
1000
42
48244
48251
1250
42
48258
48265
1600
42
48272
48279

Type H1
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW63

In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu


800
65
48231
48238
1000
65
48245
48252
1250
65
48259
48266
1600
65
48273
48280
2000
65
48287
48294
2500
65
48300
48306
3200
65
48312
48317
4000
65
48322
48327
4000
100
48336
48339
5000
100
48342
48345
6300
100
48348
48351

Type H2

E46449

Basic circuit breaker + chassis y 4000 A

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW63

In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu


800
100
48232
48239
1000
100
48246
48253
1250
100
48260
48267
1600
100
48274
48281
2000
100
48288
48295
2500
100
48301
48307
3200
100
48313
48318
4000
100
48323
48328
4000
150
48337
48340
5000
150
48343
48346
6300
150
48349
48352

Type H3
NW20
NW25
NW32
NW40

In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu


2000
150
48289
48296
2500
150
48302
48308
3200
150
48314
48319
4000
150
48324
48329

Type L1
Basic circuit breaker + chassis u 4000 A

NW08
NW10
NW12
NW16
NW20

In (A at 40C) Icu (kA for U = 220/440 V) - Ics = 100% Icu


800
150
48233
48240
1000
150
48247
48254
1250
150
48261
48268
1600
150
48275
48282
2000
150
48290
48297

Option
Neutral on the right

(*)

Micrologic control unit


"ammeter" A
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A

basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
48358
48360
48361
48362

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
48363
48364
48365

selective protection
selective + earth-fault protection
selective + earth-leakage protection

3P/4P
48366
48367
48368

"power meter" P
Micrologic 5.0 P
Micrologic 6.0 P
Micrologic 7.0 P

"harmonic meter" H
Micrologic 5.0 H
Micrologic 6.0 H
Micrologic 7.0 H
(*) consult us.

BTP207E-50200-NW.fm/24

Schneider Electric

Masterpact: price list

NW08 to NW63
drawout circuit breakers (cont.)
Circuit breaker selection (cont.)

Unit price (excl.VAT) in French francs

E70740

Chassis
3P

4P

48391
48392

48403
48404

48392
48393
48394
48395
48396
48397

48404
48405
48406
48407
48408
48409

48394
48395
48396

48406
48407
48408

48399
48400

48411
48412

For type N1
800/1250 A
1600 A

For type H1/H2


800/1600 A
2000 A
2500 A
3200 A
4000 A
4000b/6300 A

Chassis y 4000 A

For type H3
2000/2500 A
3200 A
4000 A

For type L1
800/1600 A
2000 A

Auxiliaries and accessories:


b for drawout devices: see page 26
b for fixed or drawout devices: see page 30
Switch-disconnector version: see page 32
Source changeover assembly: see page 30

Communication option
Chassis
Modbus COM
Modbus eco COM
Digipact COM

Circuit breaker

33852

48384
48385
48388

33855

E46450

Chassis front connection


800/1600 A
2000 A
2500/3200 A

Top
Bottom
Top

3P
48415
48418
48413

4P
48441
48444
48417

Bottom

48414

48420

Top
Bottom

48416
48419

48442
48445

3P

4P

Chassis rear connection

E46445

Vertical connection
800/2000 A
800/1600 A type L1
2500/3200 A
2000 A types H3/L1
4000 A

Top
Bottom
Top
Bottom
Top

48133
48138
48134
48139
48135

48158
48163
48159
48164
48160

Bottom

48140

48165

4000b/5000 A

Top

48136

48161

Bottom

48141

48166

Top

48137

48162

Bottom

48142

48167

800/2000 A
800/1600 A type L1
2500/3200 A
2000 A types H3/L1
4000 A

Top
Bottom
Top
Bottom
Top
Bottom

48143
48148
48144
48149
48145
48150

48168
48173
48169
48174
48170
48175

4000b/5000 A

Top

48146

48171

Bottom

48151

48176

6300 A

E46446

Horizontal connection

E46428

Rear connection accessories

Schneider Electric

Interphase barriers
3P/4P (3 parts)

48600

BTP207E-50200-NW.fm/25

Masterpact: price list

NW08 to NW63
drawout circuit breakers (cont.)
Chassis locking and accessories

Unit price (excl.VAT) in French francs

Chassis locking
"Disconnected" position locking
E46451

By padlocks
Standard
By keylocks
Profalux

1 lock
1 lock + 1 lock with same key profile
2 locks (different key profiles)
Ronis
1 lock
1 lock + 1 lock with same key profile
2 locks (different key profiles)
Optional disconnected/test/connected position locking
Locking kit without locks for
Profalux, Ronis
Kirk
Castell

48568
48569
48570
48572
48573
48574
33779

Right-hand side of chassis


Left-hand side of chassis

48579
48580

1 part

48582

(*)

48564
48565
48566

E46452

Door interlock (1 part)

E46453

Racking interlock

Racking interlock between crank and OFF pushbutton


1 part

48585

Automatic spring discharge before breaker removal


48554

E46688

1 part

Breaker mismatch protection


33767

E46456

Breaker mismatch protection VDC

(*) no charge.

BTP207E-50200-NW.fm/26

Schneider Electric

Masterpact: price list

NW08 to NW63
drawout circuit breakers (cont.)
Chassis locking and accessories (cont.)

Unit price (excl.VAT) in French francs

Chassis accessories
Arc chute cover
Standard

3P
4P
3P
4P

48595
48596
48597
48598

3P
4P
3P
4P

48587
48589
48588
48590

E46457

3P/4P

Auxiliary terminal shield (CB)


E46458

800/4000 A
4000b/6300 A

Safety shutters + locking block


E46459

800/4000 A
4000b/6300 A

Shutter locking block (for remplacement)


48591

E46460

2 parts for 800/4000 A

E46702

Front face shutter position indication and locking

Schneider Electric

800/4000 A
4000b/6300 A

3P/4P
3P
4P

48592
48593
48594

BTP207E-50200-NW.fm/27

Masterpact: price list

NW08 to NW63
drawout circuit breakers (cont.)
Indication contacts

Unit price (excl.VAT) in French francs

E46689

ON/OFF indication contacts (OF)


Block of 4 changeover contacts (6 A - 240 V)
1 additional block of 4 contacts (2 max.)

1 block (standard)
48468

E46690

Combined closed / connected contacts for use with 1 auxiliary contact


1 contact (5 A - 240 V) (8 max.)
or 1 low-level contact (8 max.)

48477
48478

E46691

"Fault trip" indication contacts (SDE)


Changeover contact (5 A - 240 V)
1 additional SDE (5 A - 240 V)
or 1 additional low-level SDE

1 (standard)
48475
48476

E46703

Programmable contacts (*) (programmed via Micrologic control unit)


2 contacts M2C (5 A - 240 V)
or 6 contacts M6C (5 A - 240 V)
(*) for Micrologic control units P and H only.

48382
48383

E46734

M2C

M6C

E46661

Carriage switches (connected / disconnected / test position)


Changeover contacts (8 A - 240V)
1 connected position contact (3 max.)
1 test position contact (3 max.)
1 disconnected position contact (3 max.)
and/or low-level changeover contacts
1 connected position contact (3 max.)
1 test position contact (3 max.)
1 disconnected position contact (3 max.)
Actuator for additional carriage switches

33751
33752
33753
33754
33755
33756
48560

Auxiliary terminals for chassis alone


3 wire terminal (30 parts)
6 wire terminal (10 parts)
Jumpers (10 parts)

BTP207E-50200-NW.fm/28

47898
47899
47900

Schneider Electric

Masterpact: price list

NW08 to NW63
drawout circuit breakers (cont.)
Remote operation

Unit price (excl.VAT) in French francs

Remote ON/OFF

E46692

Gear motor
AC 50/60 Hz

DC

48 V
100-130 V
200-240 V
250-277 V
380-415 V
440-480 V
24-30 V
48-60 V
100-130 V
200-250 V

MCH
48522
48526
48527
48528
48529
48530
48521
48522
48523
48524

E46693

Instantaneous voltage releases


Standard
AC 50/60 Hz
DC

Communicating
AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC
12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

Closing release
XF
48480
48481
48482
48483
48484
48485
48486
XF com
48448
48449
48450
48451
48452
48453
48454

Opening release
MX
48490
48491
48492
48493
48494
48495
48496
MX com
48457
48458
48459
48460
48461
48462
48463

E46695

"Ready to close" contact (1 max.)


1 changeover contact (5 A - 240 V)
1 low-level changeover contact

PF
48469
48470

E46677

Electrical closing pushbutton


BPFE
48534

1 pushbutton

E46691

Remote reset after fault trip


Electrical reset
110-130 V AC
220-240 V AC
Automatic reset
Adaptation

Res
48472
48473
RAR
47346

(*)

Remote tripping

E46693

Instantaneous voltage release


AC 50/60 Hz
DC

12 V DC
24-30 V DC, 24 V AC
48-60 V DC, 48 V AC
100-130 V
200-250 V
277 V AC
380-480 V AC

2nd MX
48510
48511
48512
48513
48514
48515
48516

or

MN
48501
48502
48503
48504
48506

MN delay unit
E46694

R (non-adjustable)
AC 50/60 Hz
DC

48-60 V
100-130 V
200-250 V
380-480 V

33684
33685

Rr (adjustable)
33680
33681
33682
33683

(*) no charge.

Schneider Electric

BTP207E-50200-NW.fm/29

Masterpact: price list

Accessories for NW08 to NW63


fixed and drawout circuit breakers

Unit price (excl.VAT) in French francs

Circuit breaker locking


Pushbutton locking device
48536

E46666

By padlocks

OFF position locking


By padlocks
E46735

48539
By padlocks and keylocks
Profalux

Ronis

1 lock
1 lock + 1 lock with same key profile
2 locks (different key profiles)
1 lock
1 lock + 1 lock with same key profile
2 locks (different key profiles)

48545
48546
48547
48549
48550
48551

Profalux, Ronis
Kirk
Castell

48541
48542
48543

Locking kit without locks for

Other circuit breaker accessories


Mechanical operation counter
48535

E46667

operation counter CDM

Escutcheon

Escutcheon
Transparent cover IP 54
Escutcheon blanking plate

E46736

E46680

E46679

Escutcheon and accessories

Cover

Fixed
48601
48605

Drawout
48603
48604
48605

Blanking plate

Mechanical interlocking for source changeover

E47762

Interlocking of 2 devices using connecting rods


Complete assembly with 2 adaptation fixtures + rods
2 Masterpact NW fixed devices
2 Masterpact NW drawout devices
Can be used with 1 NW fixed + 1 NW drawout.

48612
48612

Interlocking of 2 devices using cables (*)


Choose 2 adaptation fixtures (1 for each device + 1 set of cables)
1 adaptation fixture for Masterpact NW fixed devices
1 adaptation fixture for Masterpact NW drawout devices
1 set of 2 cables
(*) Can be used with any combination of NT or NW, fixed or drawout devices.

47926
47926
33209

Interlocking of 3 devices using cables


Choose 3 adaptation fixtures (1 complete set with 3 adaptation fixtures + cables
3 sources, only 1 device closed, fixed or drawout devices
2 sources + 1 coupling, fixed or drawout devices
2 normal + 1 replacement source, fixed or drawout devices

48610
48609
48608

Cable-type door interlock


1 complete assembly for Masterpact NW fixed or drawout device

BTP207E-50200-NW.fm/30

48614

Schneider Electric

Masterpact: price list

Accessories for NW08 to NW63


fixed and drawout circuit breakers
(cont.)

Unit price (excl.VAT) in French francs

Accessories for Micrologic control units


External sensors

E46671

External sensor for earth-fault protection (TCE)


Sensor rating

400/2000 A
1000/4000 A

34035
34036

4000/6300 A (for NW40b, NW50, NW63)

48182
33578

Source ground return (SGR) earth fault protection


External sensor (SGR)

33579

E46672

Rectangular sensor for earth-leakage protection


470 mm x 160 mm

E46671

MDGF summing module

48891

Voltage measurement input (for breakers supplied via bottom terminals)


Voltage measurement input
Fixed

47506

E46890

Drawout

48533

E46674

Long-time rating plug (limits setting range for higher accuracy)


Standard

0.4 at 1 x Ir

33542

Low-setting option

0.4 at 0.8 x Ir

33543

High-setting option

0.8 at 1 x Ir

33544

Without long-time protection

off

33545

Zone Selective Interlocking option for Micrologic P and H


ZSI

Standard

E47787

External power supply module

L4
L3

t
Inpu
24VDC
Output
24VDC G2

0A
AD 22
G1

24-30 V DC
48-60 V DC
125 V DC
110 V AC
220 V AC
380 V AC

54440
54441
54442
54443
54444
54445

1 24 V battery

54446

Battery module

Test equipment
Mini test kit
E59921

33594

Portable test kit


E59554

33595

Special settings
For circuit breaker derating
Catalogue number to be added to those describing the circuit breaker
Rating
NW08
NW10
NW12
NW16
400
47053
47053
630
33091
33091
33091
800
33092
33092
33092
1000
33093
33093
1250
33094
1600
2000
2500
Rating
NW40
NW40b
NW50
NW63
2000
33982
47821
2500
33983
47822
47822
3200
33984
47823
47823
47823
4000
47824
47824
5000
47825
Note: for ratings In = 100 or 250 A, please consult us.
Schneider Electric

NW20

33093
33094
33095

NW25

33094
33095
33982

NW32

33095
33982
33983

BTP207E-50200-NW.fm/31

Masterpact: price list

NW08 to NW63
fixed switch-disconnectors
Switch-disconnector selection

Unit price (excl.VAT) in French francs

E46681

A Masterpact fixed switch-disconnector is


described by 3 catalogue numbers
corresponding to:
b the basic switch-disconnector
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories may also be
added.

Basic switch-disconnector y 4000 A

Basic switch-disconnector
Type NA

NW08
NW10
NW12
NW16

3P
In (A at 40C) Icm (kA peak for U = 220/690 V)
800
88
48004
1000
88
48018
1250
88
48032
1600
88
48046

4P

3P
In (A at 40C) Icm (kA peak for U = 220/690 V)
800
105
48005
1000
105
48019
1250
105
48033
1600
105
48047
2000
105
48061
2500
135
48074
3200
135
48085
4000
135
48095
4000
187
48108
5000
187
48114
6300
187
48120

4P

3P
In (A at 40C) Icm (kA peak for U = 220/690 V)
800
187
48006
1000
187
48020
1250
187
48034
1600
187
48048
2000
187
48062
2500
187
48075
3200
187
48086
4000
187
48096

4P

48011
48025
48039
48053

Type HA

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW63

48012
48026
48040
48054
48068
48080
48090
48100
48111
48117
48123

E46682

Type HF

Basic switch-disconnector u 4000 A

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40

48013
48027
48041
48055
48069
48081
48091
48101

Communication option
Modbus COM
Digipact COM

48188
48192

Auxiliaries and accessories:


b for fixed devices: see page 22
b for fixed or drawout devices: see page 30
Source changeover assembly: see page 30
BTP207E-50200-NW.fm/32

Schneider Electric

Masterpact: price list

NW08 to NW63
fixed switch-disconnectors (cont.)
Switch-disconnector selection (cont.)

Unit price (excl.VAT) in French francs

E46444

Front connection
800/1600 A
2000 A
2500/3200 A

3P
48128
48130
48124
48125
48129
48131

4P
48153
48155
48126
48127
48154
48156

3P
48421
48422

4P
48424
48425

Top
Bottom
Top
Bottom

3P
48133
48138
48134
48139

4P
48158
48163
48159
48164

Top

48135

48160

Bottom

48140

48165

Top

48136

48161

Bottom

48141

48166

Top

48137

48162

Bottom

48142

48167

Top
Bottom
Top
Bottom
Top
Bottom
Top
Bottom

3P
48143
48148
48144
48149
48145
48150
48146
48151

4P
48168
48173
48169
48174
48170
48175
48171
48176

Top
Bottom
Top
Bottom
Top
Bottom

Front connection accessories


E46889

Disconnectable front connection


1600 A
2000/3200 A

Rear connection

E46445

Vertical connection
800/2000 A
2500/3200 A
4000 A
4000b/5000 A
6300 A

E46446

Horizontal connection
800/2000 A
2500/3200 A
4000 A
4000b/5000 A

Rear connection accessories


Interphase barriers
48599

E46428

3P/4P (3 parts)

47829

E47788

Brackets for mounting on a backplate


2 parts

Schneider Electric

BTP207E-50200-NW.fm/33

Masterpact: price list

NW08 to NW63
drawout switch-disconnectors
Switch-disconnector selection

Unit price (excl.VAT) in French francs

A Masterpact drawout switch-disconnector


is described by 4 catalogue numbers
corresponding to:
b the basic switch-disconnector
b a chassis
b a top connection
b a bottom connection
A communication option and various
auxiliaries and accessories may also be
added.

Basic switch-disconnector
Type NA

NW08
NW10
NW12
NW16

4P

3P
In (A at 40C) Icm (kA peak for U = 220/690 V)
800
105
48235
1000
105
48249
1250
105
48263
1600
105
48277
2000
105
48291
2500
135
48304
3200
135
48315
4000
135
48325
4000
187
48338
5000
187
48344
6300
187
48350

4P

3P
In (A at 40C) Icm (kA peak for U = 220/690 V)
800
187
48236
1000
187
48250
1250
187
48264
1600
187
48278
2000
187
48292
2500
187
48305
3200
187
48316
4000
187
48326

4P

48241
48255
48269
48283

Type HA

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW63

E46683

3P
In (A at 40C) Icm (kA peak for U = 220/690 V)
800
88
48234
1000
88
48248
1250
88
48262
1600
88
48276

48242
48256
48270
48284
48298
48310
48320
48330
48341
48347
48353

Type HF

E46684

Basic switch-disconnector + chassis y 4000 A

NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40

48243
48257
48271
48285
48299
48311
48321
48331

Chassis
Type NA
800/1250 A
1600 A

Basic switch-disconnector + chassis u 4000 A

3P
48391
48392

4P
48403
48404

3P
48392
48393
48394
48395
48396
48397

4P
48404
48405
48406
48407
48408
48409

Type HA/HF
800/1600 A
2000 A
2500 A
3200 A
4000 A
4000b/6300 A

Communication option
Modbus COM
Digipact COM

Chassis
33852
33855

Switch-disconnector
48384
48388

Auxiliaries and accessories:


b for drawout devices: see page 26
b for fixed or drawout devices: see page 30
Source changeover assembly: see page 30
BTP207E-50200-NW.fm/34

Schneider Electric

Masterpact: price list

NW08 to NW63
drawout switch-disconnectors
(cont.)

Unit price (excl.VAT) in French francs

Switch-disconnector selection (cont.)

E46450

Chassis front connection


Top
Bottom
Top
Bottom
Top
Bottom

3P
48415
48418
48413
48414
48416
48419

4P
48441
48444
48417
48420
48442
48445

800/2000 A
800/1600 A type L1
2500/3200 A
2000 A types H3/L1

Top
Bottom
Top
Bottom

3P
48133
48138
48134
48139

4P
48158
48163
48159
48164

4000 A

Top

48135

48160

Bottom

48140

48165

Top

48136

48161

Bottom

48141

48166

Top

48137

48162

Bottom

48142

48167

Top
Bottom
Top
Bottom
Top
Bottom
Top
Bottom

3P
48143
48148
48144
48149
48145
48150
48146
48151

4P
48168
48173
48169
48174
48170
48175
48171
48176

800/1600 A
2000 A
2500/3200 A

Chassis rear connection

E46445

Vertical connection

4000b/5000 A
6300 A

E46446

Horizontal connection
800/2000 A
800/1600 A type L1
2500/3200 A
2000 A types H3/L1
4000 A
4000b/5000 A

E46428

Rear connection accessories

Schneider Electric

Interphase barriers
3P/4P (3 parts)

48600

BTP207E-50200-NW.fm/35

Masterpact: price list

Retrofit solutions
Connection for fixed devices

Unit price (excl.VAT) in French francs

To replace a Masterpact M with a


Masterpact NW, order a retrofit device
(without connections) and select a set of
connectors corresponding to the replaced
device.
The Masterpact NW is installed in exactly
the same place as the old Masterpact M
device, without any modifications required
on the switchboard.

Horizontal rear connection


Device to be replaced

Connection to be ordered

Masterpact M08 to M12


Type N1/NI
Top
Bottom
Type H1/H2/HI/HF
Top
Bottom

3P
3 x 48951
3 x 48964

4P
4 x 48951
4 x 48964

3 x 48954
3 x 48965

4 x 48954
4 x 48965

3 x 48954
3 x 48965

4 x 48954
4 x 48965

3 x 48957
3 x 48958

4 x 48957
4 x 48958

1 x 48962
1 x 48961

1 x 48960
1 x 48960

Masterpact M16
Type N1/NI/H1/H2/HI/HF
Top
Bottom

Masterpact M20 and M25


Type N1/NI/H1/H2/HI/HF
Top
Bottom

Masterpact M32
Type H1/H2/HI/HF
Top
Bottom

BTP207E-50200-NW.fm/36

Schneider Electric

Masterpact: price list

Retrofit solutions (cont.)


Connection for drawout devices

Unit price (excl.VAT) in French francs

To replace a Masterpact M with a


Masterpact NW, order a retrofit device
(without connections) and select a set of
connectors corresponding to the replaced
device.
The Masterpact NW is installed in exactly
the same place as the old Masterpact M
device, without any modifications required
on the switchboard.

Vertical rear connection


Device to be replaced

Connection to be ordered

Masterpact M08 to M12


Type N1/NI
Top
Bottom
Type H1/H2/HI/HF
Top
Bottom

3P
3 x 48966
3 x 48966

4P
4 x 48966
4 x 48966

3 x 48969
3 x 48969

4 x 48969
4 x 48969

3 x 48969
3 x 48969

4 x 48969
4 x 48969

3 x 48970
3 x 48970

4 x 48970
4 x 48970

1 x 48974
1 x 48974

1 x 48978
1 x 48978

Masterpact M16
Type N1/NI/H1/H2/HI/HF
Top
Bottom

Masterpact M20 and M25


Type N1/NI/H1/H2/HI/HF
Top
Bottom

Masterpact M32
Type H1/H2/HI/HF
Top
Bottom

Horizontal rear connection


Device to be replaced

Connection to be ordered

Masterpact M08 to M12


Type N1/NI
Top
Bottom
Type H1/H2/HI/HF
Top
Bottom

3P
3 x 48951
3 x 48964

4P
4 x 48951
4 x 48964

3 x 48954
3 x 48965

4 x 48954
4 x 48965

3 x 48954
3 x 48965

4 x 48954
4 x 48965

3 x 48957
3 x 48958

4 x 48957
4 x 48958

Masterpact M16
Type N1/NI/H1/H2/HI/HF
Top
Bottom

Masterpact M20 and M25


Type N1/NI/H1/H2/HI/HF
Top
Bottom

Masterpact M32 neutral on left-hand side


Type H1/H2/HI/HF
Top
Bottom

1 x 48973
1 x 48973

1 x 48976
1 x 48977

Masterpact M32 neutral on right-hand side


Type H1/H2/HI/HF
Top
Bottom

Schneider Electric

1 x 48973
1 x 48973

1 x 48977
1 x 48976

BTP207E-50200-NW.fm/37

Masterpact: price list

Communication bus accessories


and Display Modules

Unit price (excl.VAT) in French francs

Display modules
DMB300
Max. 4 breakers

50894

4900

Color display module

Max. 16 breakers

50895

13388

50959

1715

CJB306: 6 SubD 9 pins connectors junction block

50963

502

CSD309: 9 pins SubD with screw terminals

50964

220

CDM303: display module pre-wired cable, 3 m length

50960

268

CCP303: Masterpact or Compact pre-wired cable (4 RS485 wires + 2 power wires) 3 m length 50961

192

E67954

Monochrome display module

E67955

DMC300

Spare parts
DMC300PCM: DMC300 memory card

RS485 Modbus pre-wired system

E67958

RS485 Modbus junction block

E67959

RS485 Modbus connector

E79015

E67960

RS485 Modbus cables

50965

2129

50823

6737

50778

411

50779
50780

385
1883

50786
TSX SCA72
174 CEV 300-10
3050 EGW2

8194
(1)
(1)
(2)

E67961

CCR301: RS485 roll cable (2 RS485 wires + 2 power wires) 60 m length

Digipact Bus pre-wired system


Data concentrator DC150
110-240 V AC, 50/60 Hz and 115-125 V DC

E79014

Auxiliary supply voltage

Junction block
E67956

Junction block for internal Bus

Cables
E67957

Cable for internal bus

20-meter roll (0.75 mm2)


100-meter roll (0.75 mm2)

Converter
RS485/RS232 (ACE909) 12 V DC power supply included
RS485/RS232
RS485/Ethernet
RS485/Ethernet (SMS compatible)
(1) see catalogue Telemecanique.
(2) see catalogue Square D.

BTP207E-50200-NW.fm/38

Schneider Electric

Masterpact: price list

Order form
Masterpact NT and NW

Unit price (excl.VAT) in French francs

To indicate your choices, check the applicable square


boxes
and enter the appropriate information
in the rectangles

Basic device

Quantity

Masterpact type
NT, NW
Frame size
06 to 63
Sensor rating
A
Circuit breaker
N1, H1, H2, H3, L1
Switch-disconnector
NA, HA, HF
Number of poles
3 or 4
Option : Neutral on right side
Type of device
Fixed
Drawout with chassis
Chassis alone
Drawout without chassis

Locking
VBP - ON/OFF pushbutton locking
OFF position locking
VCPO - by padlocks
Locking kit
VSPO - by keylocks
without
keylocks
1 lock

VSPD - chassis locking in


''disconnected'' position

VPEC - door interlock

Micrologic control unit


A - ammeter
2.0 A
P - power meter

5.0 A

6.0 A

7.0 A

5.0 P

6.0 P

7.0 P

H - harmonic meter
5.0 H
6.0 H
7.0 H
TCE - external sensor (CT) for neutral + earth-fault
protection
TCE - external sensor (CT) for double neutral protection
(Micrologic P and H with 3-poles)
TCW - external sensor for SGR protection
Rectangular sensor
280 x 115
for earth-leakage
470 x 160
protection
LT - long-time rating plug (standard setting 0.4 to 1 x Ir)
Low setting option 0.4 to 0.8 Ir
High setting option 0.8 to 1 Ir
LT OFF option
PTE - external voltage measurement input
AD - external power-supply module
BAT - battery module

Communication
COM
Eco COM

Digipact
Modbus
Modbus

Connection
Horizontal
Top
Vertical
Top
Front
Top
Bare-cable connectors
4 x 240 mm2 + connector shield
Vertical-connection adapters
Cable-lug adapters
Interphase barriers
Spreaders
Disconnectable front-connection
adapter

Bottom
Bottom
Bottom

Schneider Electric

1 lock + 1 lock with


same key profile

2 locks (different key profiles) for NW


Locking kit
Profalux
Ronis
without
keylocks
1 lock
1 lock + 1 lock with
same key profile
2 locks (different key profiles)
Optional connected - disconnected - test position locking
Latch on right-hand side of chassis
Latch on left-hand side of chassis

Indication contacts
OF - ON/OFF indication contacts
Standard
4 OF 6 A - 240 V AC (10 A - 240 V AC and low-level for NW)
Max. 4
qty
Alternate
1 OF low-level for NT
(replaces a standard contact)
Additional
1 block of 4 OF for NW
EF - combined ''connected/closed'' contacts
1 EF 5 A - 240 V AC for NW
1 EF low-level for NW
SDE - ''fault-trip'' indication contacts
1 SDE 5 A - 240 V AC
Standard
Additional
1 SDE 5 A - 240 V AC
1 SDE low-level
Programmable contacts
2 M2C contacts
6 M6C contacts
Carriage switches
low-level
6 A - 240 V AC
CE - ''connected'' position
Maxi. 3 for NT and NW
Maxi. 2 for NT and 3 for NW
CD - ''disconnected'' position
Maxi. 1 for NT and 3 for NW
CT - ''test'' position
AC - actuator for additional carriage switches

Max. 2

qty

Max. 8
Max. 8

qty
qty

qty
qty
qty
qty

Remote operation
Remote ON/OFF

Remote tripping

VO - safety shutters on chassis


NT, NW
VIVC - shutter position indication NW
and locking

Key for Micrologic control units:


2.0 : basic protection (long-time + inst.)
5.0 : selective protection (long-time + short-time + inst.)
6.0 : selective + earth-fault protection
(long-time + short-time + inst. + earth-fault)
7.0 : selective + earth-leakage protection
(long-time + short-time + inst. + earth-leakage)

Ronis

VPOC - racking interlock


IPA - cable-type door interlock
IBPO - racking interlock between crank and OFF pushbutton for NW
DAE - automatic spring discharge before breaker removal for NW
VDC - mismatch protection

NT-FC fixed
NT-FC, fixed, draw.
NT-FC, fixed, draw.
NT, NW-fixed, draw.
NT-fixed, drawout
NW-fixed

Profalux

MCH - gear motor


XF - closing voltage release
MX - opening voltage release
PF - ''ready to close'' contact

V
V
V

low-level
6 A - 240 V AC
BPFE - electrical closing pushbutton
Res - electrical reset option
RAR - automatic reset option
MN - undervoltage release
V
R - delay unit (non-adjustable)
Rr - adjustable delay unit
2nd MX - shunt release
V

Accessories
CDM - mechanical operation counter
CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover
OP - blanking plate
Brackets for mounting on backplates

BTP207E-50200-NW.fm/39