Coordinate with the final RCP layouts and resubmit the revised layouts with
the correct quantities, type, location etc. of the proposed light fittings in
coordination with the architectural / ID requirements for the BOH areas.
Indicate the lighting control schedules / schemes in the layout drawings for
the BOH areas.
Lighting for the RMU room shall be as per DEWA approval details
Wherever the light fittings are being supplied by the Contractor lighting
calculations shall be submitted for review along with the material submittal.