Ground Floor Power Layouts

Revise & Resubmit


-

Coordinate with other MEP services layouts and submit the coordinated
layout for review / approval.

Submit all the electrical rooms enlarged dimensional layouts.

Submit the electrical load distribution schedules for review.

Submit the cable tray sizing schedules with necessary calculation tables
separately for review / approval. Ensure to not to exceed the cable space
occupancy as specified.

Cleary identify the segregated distribution domain for all the floor DBs in the
layout.

Indicate all the relevant installation / sectional details for the electrical
outlets / equipment etc.

Indicate the dimensional reference for all the electrical points / outlets /
panels etc. w.r.t. nearby structural columns / walls etc.

The complete electrical installation works shall be carried out in full


compliance with the local authority approval and requirements.